CM2N3205E / 05.2001 Siemens Building Technologies
14/18 Landis & Staefa Division
Data point values and measured values can be called up as data under certain data
point numbers. The factory setting of all values is such that the controller will meet the
requirements of most plants. If necessary, they can be readjusted on an individual
basis.
Nr. Description Range Factory setting
1 B9 Frost temperature –50.0...+150.0 °C -----
2 Z3 Compensating variable –50.0...+150.0 °C -----
3 F91 Common fault relay A OFF / On -----
4 F92 Common fault relay b OFF / On -----
5 E6 Time channel1) OFF / On -----
6 Min. limitation Y30 0...100 % 0 %
7 Frost alarm value 2...15 °C 5 °C
8 Set value "standby controller" 2...50 °C 25 °C
9 P-band "frost prot. controller" 1...30 K 5 K
10 P-band "Standby controller" 1...200 K 10 K
11 Integral action time "standby controller" 0.00...10.00 min 3.00 min
12 KE room (cascade effect) 0.1...20 2.0
13 Integral action time "room" 0.00...40.00 min 8.00 min
14 P-band "heating" 1...200 K 20 K
15 Integral act.time "heating" 2) 0.00...10.00 min 2.30 min
16 P-band "HR" 1...200 K 15 K
17 Integral action time "HR" 2) 0.00...10.00 min 2.00 min
18 P-band "cooling" 1...200 K 15 K
19 Integral act.time "cooling" 2) 0.00...10.00 min 2.00 min
20 Switching interval SA 1...100 % 20 %
21 Switching differential 1...100 % 10 %
22 Starting point 20...40 °C 25 °C
23 End point 20...40 °C 30 °C
24 Delta 0...10 K 2 K
25 Starting point –30...+20 °C 5 °C
26 End point –30...+20 °C –20 °C
27 Delta 0...10 K 2 K
28 E1 Fire / smoke A / b A
29 E2 Fan, filter monitor A / b A
30 E3 Overload "pump/electric" A / b A
31 E4 Overload "chiller" A / b A
32 E5 Overcurrent "fan" A / b A
33 Frost alarm A / b A
34 E7 AUX 1 A / b A
35 E8 AUX 2 A / b A
36 Room sensor, min. –50.0...+150.0 °C 0 °C
37 Room sensor, max. –50.0...+150.0 °C 50 °C
38 Supply air sensor, min. –50.0...+150.0 °C 0 °C
39 Supply air sensor, max. –50.0...+150.0 °C 50 °C
40 Outside sensor, min. –50.0...+150.0 °C –35 °C
41 Outside sensor, max. –50.0...+150.0 °C 35 °C
42 Frost sensor, min. –50.0...+150.0 °C 0 °C 15)
43 Frost sensor, max. –50.0...+150.0 °C 15 °C 15)
44 Compensation, min. –50.0...+150.0 °C –5 °C
45 Compensation, max. –50.0...+150.0 °C 5 °C
46 B1 Room temperature –5.00...+5.0 K 0.0 K
47 B2 Supply air temperature –5.00...+5.0 K 0.0 K
48 B4 Outside temperature –5.00...+5.0 K 0.0 K
49 B9 Frost temperature –5.00...+5.0 K 0.0 K
50 Z3 Compensation –5.00...+5.0 K 0.0 K
51 Integral action time "fan" 3) 00.00...30.00 min 5.00 min
52 Min. HC pump running time 00.00...30.00 min 5.00 min
53 HC pump kick interval 00.00...24.00 h 24.00 h
54 Alarm delay "filter" 00.00...05.00 min 0.20 min
55 Alarm delay "AUX" 00.00...05.00 min 0.00 min
56 Time channel switch on time 4) 00.00...12.00 h 00.00 h
57 Startup logic (air damper) 5) 00.00...60.00 min 00.00 min
58 Power up start delay 00.00...30.00 min 00.00 min
59 E1 Fire/smoke CLSd/OPEn OPEn
60 E2 Fan, filter monitor CLSd/OPEn OPEn
61 E3 Overload "pump" CLSd/OPEn OPEn
62 E4 Overload "chiller" CLSd/OPEn OPEn
63 E5 Overcurrent "fan" CLSd/OPEn OPEn
64 E6 Time channel CLSd/OPEn OPEn
65 E7 AUX1 CLSd/OPEn OPEn
66 E8 AUX2 CLSd/OPEn OPEn
67 B1 Room temperature Auto/Pass/Act Auto
68 B2 Supply air temperature Auto/Pass/Act Auto
69 B4 Outside temperature Auto/Pass/Act Auto
70 B9 Frost temperature Auto/Pass/Act Auto
71 Z3 Compensation Auto/Pass/Act Auto
List of data points
Current measured values
Limitation of manipulated
variables
Set values of frost
protection/standby controller
Parameters of frost
protection / standby
controller
Control parameters of room
temperature controller
Control parameters of supply
air temperature controller
Switching points of
compressor
Summer compensation
Winter compensation
Alarm priorities
Measuring ranges of active
sensors
Measured value correction,
sensor inputs
Time elements
Active level I/Os
Preselection sensor
identification