
Installation:
• Openthedoorbyrotatingthedoorlocksanticlockwise.
• Mountthecontrolleronaverticalwall/platefreefrom
vibrationswithpropernutsandbolts.ReferFig.6for
mountingdimensions.
• Removetherubbergrommetsfortheincomingand
outgoingcableconnections.(ReferFig.2)
• Connectincomingandoutgoingcablesasfollows(Refer
Fig.2):
– Usepropercableglandstoensuredustproong.For
conduitentryusepackedwashers.
– SelectcorrectsizeofcablesfromTable1.
– Connectlineandmotorcablesexactlyasperwiring
diagrampastedinsidethecoverofthecontroller.
– Terminatetheincomingsupplycablesonterminal
blockTB1&outgoingcablestomotoronterminal
blockTB2,TB3(Tighteningtorque-Refertable2).
NOTE:LMRAissetinManualmode(Factorysetting)
WLCissetinDeliverymode(Factorysetting)
– Connecttheearthingconductortoterminalsmarked
(earth)onthecontrollerbodywithtorque1.2to
1.6Nm.
TheControllerisnowreadyforcommissioning.
• Initiallysettheoverloadrelayto0.58timestherated
motorcurrent.
• Setthetimerdialtothenearestvalueofstartingtime
availableonmotornameplate.
Ifitisnotavailable,thensetthedialtoapproximately
6-8secs.
• Closethedoorbyrotatingthedoorlocksclockwise.
Commissioning:
Forexactsettingoftimerandoverloadrelay,followthe
instructiongivenbelow:
Before switching ON recheck all external connections.
• Star-DeltaTimersettingforFASDController:
– FirstSwitchONtheRockerswitch(ControlOn/Off).
– Startthemotorbypressingthe‘ON’buttonshownin
Fig.1.
– Measurethetimetakenbythemotortonearly
reachratedspeedorsteadystatecurrentcondition
(indicatedwhenthemotorreachesasteadyhum).
– StopthemotorbyOFFbuttonshowning.1.
– Openthedoor&Setthetimertothismeasuredvalue
byrotatingthedialshowninFig.3.
• Overloadrelaysetting:
– Forcloserprotectionsettheoverloadrelaytoactual
phasecurrentasmeasuredbyanammeter.Inthe
absenceofanammeter,usetheproceduregiven
below:
– Startthemotorandletitrunfor30mins.Then
graduallyreducetherelaysettingstillittrips.Setthe
relayataslightlyhighervaluethanthissetting.
Overloadrelaycharacteristics(Referservicemanual
A5E50797230A)canbeusedtoestimatetheaverage
trippingtimeatdifferentmultiplesofsetcurrent.
– Allowaresettimeofapprox.4min.beforepressing
theblueknobontherelaytoresetit.
– Restartthemotoraftersometime.Iftherelaydoes
nottripthenconsiderittobeproperlyset.Ifthe
relaytrips,setatalittlehighervaluethanbeforeand
recheck.
• Closethefrontdoor.
Caution:
• During commissioning or maintenance always ensure
that the main supply is disconnected by switching off
the main switch & Rocker switch.
• InthecaseofFASDcontrollersunderno
circumstances should the relay be set higher than the
phase current i.e. 0.58 times the rated current on the
motor name plate.
• Iftherelaytripsevenwhensetatratedmotorcurrent
thesuitabilityofthecontroller/relayfortheparticular
applicationshouldbecheckedwiththenearestSiemens
office.
Procedure for connecting WLC sensors & terminations:
• ThesesensorsneedtoberoutedfromleftsideofBaseplatethroughcablegland(Pleaseensureduecaretoavoid
damagetothesensors.)
Mode For Single Tank application
(Delivery or Suction mode)
For Dual Tank application
(Dual tank mode) For by passing WLC
ConnectionProcedure ConnectsensorsP1,P2&P3
toTerminalX1,X2,X3of
TerminalblockTB5
ConnectsensorsP1,P2&
P3toTerminalX1,X2,X3of
TerminalblockTB5&sensors
P4,P5&P6toTerminalX4,
X5,X6ofTerminalblockTB5
Removeconnectionbetween
X7-X8ofTerminalblockTB5.
RemoveconnectionfromX11
ofTB5&ConnectittoX12of
TB5.
2
Fig. 3 Timer Adjustment
Dial