Siemens Cerberus PACE Compact User manual

Cerberus PACE Compact
Public Address and Controlled Evacuation
Operation Manual
A6V11899865_en--_b
Smart Infrastructure
2021-03-12

Imprint
2 | 54
A6V11899865_en--_b
Imprint
Technical specifications and availability subject to change without notice.
Transmittal, reproduction, dissemination and/or editing of this document as well as
utilization of its contents and communication thereof to others without express
authorization are prohibited. Offenders will be held liable for payment of damages.
All rights created by patent grant or registration of a utility model or design patent
are reserved.
Issued by:
Siemens Switzerland Ltd.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 724-2424
www.siemens.com/buildingtechnologies
Edition: 2021-03-12
Document ID: A6V11899865_en--_b
© Siemens Switzerland Ltd, 2020

A6V11899865_en--_b
3 | 54
Table of contents
1 About this document ....................................................................................5
1.1 Applicable documents.....................................................................................8
1.2 Technical terms and abbreviations .................................................................9
1.3 Revision history...............................................................................................9
2 Safety............................................................................................................10
2.1 Safety notes ..................................................................................................10
2.2 Safety regulations for the method of operation.............................................11
2.3 System owner................................................................................................13
2.4 Function test / system acceptance / maintenance........................................13
2.5 Standards and directives complied with........................................................14
2.5.1 Multimedia equipment....................................................................14
2.6 Cyber security disclaimer..............................................................................15
3 Operating conditions..................................................................................16
3.1 Operating condition indicators.......................................................................16
4 Operating elements in the system.............................................................17
4.1 Operating and call stations............................................................................17
4.2 Call stations...................................................................................................19
5 Access levels...............................................................................................22
6 Operating and call station PT1002-A1.......................................................23
6.1 Operating functions PT1002-A1....................................................................24
6.2 Operation PT1002-A1 ...................................................................................25
7 Fire brigade call station PT2002-A1 and PT2003-A1 ...............................27
7.1 Operating functions PT2002-A1 and PT2003-A1 .........................................28
7.2 Operation PT2002-A1 and PT2003-A1.........................................................28
8 Desk call station (19 buttons) PT2001-A1.................................................30
8.1 Operating functions PT2001-A1....................................................................30
8.2 Operation PT2001-A1 ...................................................................................31
8.3 Indicator PT2001-A1 .....................................................................................33
8.4 Display information PT2001-A1 ....................................................................34
9 Key switch for desk call station PTO2002/3-A1 .......................................35
9.1 Operating functions PTO2002/3-A1..............................................................35
9.2 Operation PTO2002/3-A1 .............................................................................35
10 Desk call station (RS485, 8+1) PT2009-A1 and Call station extension
(RS485, 8) PTO2006-A1...............................................................................36
10.1 Operating functions PT2009-A1....................................................................36
10.2 Operation PT2009-A1 ...................................................................................37
10.3 Indicator PT2009-A1 .....................................................................................38
11 Desk call station (analog, 3+1) PT2008-A1...............................................39
11.1 Operating functions PT2008-A1....................................................................39
11.2 Operation PT2008-A1 ...................................................................................40
11.3 Indicator PT2008-A1 .....................................................................................41
12 System operating unit PT1001-A1.............................................................42

4 | 54
A6V11899865_en--_b
12.1 Operating functions PT1001..........................................................................42
12.2 Operation PT1001-A1 ...................................................................................43
13 Remote control panel PT2006-A1..............................................................44
13.1 Operating functions PT2006-A1....................................................................44
13.2 Operation PT2006-A1 ...................................................................................45
14 Power supply in PC1002.............................................................................46
15 System acceptance on site ........................................................................47
16 Commissioning and maintenance.............................................................48
17 Appendix......................................................................................................50
17.1 Error list for power supply in PC1002............................................................50
Glossary .................................................................................................................52
Index ......................................................................................................................53

About this document
Applicable documents
1
A6V11899865_en--_b
5 | 54
1 About this document
Retention and availability
NOTICE
Missing information
Damage due to misuse
●This document must be available in a usable format throughout the entire life
cycle of the product. Keep the document for reference and ensure that it can
be accessed by target groups.
Should you require another copy of this document, please contact the Customer
Support Center, phone +49 89 9221-8000.
Goal and purpose
This document describes the operation of a ↑Cerberus PACE Compact voice
alarm and announcement system on the ↑voice alarm control and indicating
equipment (VACIE) and the additional operating elements of the voice alarm
system.
The reader should learn about and understand the operating elements and the key
functions in the system as a whole. This knowledge will mean that they can
respond adequately in an emergency and will be able to operate other system
functions correctly.
Scope
The information contained in this document is valid for Cerberus PACE Compact.
WARNING
The 'Cerberus PACE Compact' system is a Class A product. Operation of this
equipment in a residential environment could cause radio interference. If so, the
user must be required to take adequate measures.

About this document
Applicable documents
1
6 | 54
A6V11899865_en--_b
Target groups
The information in this document is intended for the following target groups:
Target group
Activity
Qualification
System owner
●According to EN 50110-1,
'nominated person with the overall
responsibility to ensure the safe
operation of the electrical
installation by setting rules and
organisation or framework.'
●'This person can be the owner,
employer, proprietor or a delegated
person.'
●'Some of these duties can be
delegated to others as required. For
large or complex electrical
installations or networks, the duties
can be delegated for parts of the
installations or the network.'
IT security officers
●Support companies when it comes
to assessing the security of
products, solutions, and services,
and defining and implementing
improvements.
●Are technical experts in all aspects
of IT security.
Commissioning personnel
●Configures the product at the place
of installation according to
customer-specific requirements.
●Checks the product operability and
releases the product for use by the
operator.
●Searches for and corrects
malfunctions.
●Has obtained suitable specialist
training for the function and for the
products.
●Has attended the training courses
for commissioning personnel.
Operating personnel
●Carries out procedures to correctly
operate the product.
●No particular basic training is
needed.
●Has been instructed by the
commissioning personnel.
Maintenance personnel
●Carries out all maintenance work.
●Checks that the products are in
perfect working order.
●Searches for and corrects
malfunctions.
●Has obtained suitable specialist
training for the function and for the
products.

About this document
Applicable documents
1
A6V11899865_en--_b
7 | 54
Source language and reference document
●The source/original language of this document is German (de).
●The reference version of this document is the international version in English.
The international version is not localized.
Document identification
The document ID is structured as follows:
ID code
Examples
ID_languageCOUNTRY_ modification index
-- = multilingual or international
A6V10215123_deDE_a
A6V10215123_en--_a
A6V10315123_----_a
Date format
The date format in the document corresponds to the recommendation of
international standard ISO 8601 (format YYYY-MM-DD).
Presentation conventions
Text markups
Special text markups are used as follows in this document:
⊳
Prerequisite for an instruction telling you what to do
1.
2.
Instruction with at least two steps
◈
Instruction with one step
–
Variant, option, or detailed information on an instruction
⇒
Interim result of an instruction
⇒
Final result of an instruction
●
Lists
[➙X]
Reference to a page number
'Text'
Quote, exact match
<Button>
Identification of buttons
>
Indicates a link and identifies steps in a sequence, e.g., 'Menu bar' >
'Help' > 'Help topics'
↑Text
Identifies a glossary entry
Additional information and tips
The 'i' symbol identifies additional information and tips to simplify the procedure.

About this document
Applicable documents
1
8 | 54
A6V11899865_en--_b
1.1 Applicable documents
You will find more information on the Cerberus PACE Compact system and its
components in the following documents:
Title
Document ID
IT security policies
Cerberus PACE Compact –IT security policies
A6V11439692
System documentation
Cerberus PACE Compact –planning
A6V11899877
'PACE-Design' –configuration
A6V10429097
Cerberus PACE Compact –mounting / installation
A6V11899867
Cerberus PACE Compact –operation
A6V11899865
Data sheets
System data sheet
A6V11868429
Voice alarm panel Compact 400
A6V11940263
Voice alarm panel Compact 1000
A6V11940268
Network components
A6V11940273
Operating and call stations
A6V11940274
Power supply and batteries
A6V11940272
Accessories and options
A6V11940275
Loop isolator (100V)
Loop isolator (100V) - technical manual
A6V11571319
Environmental declaration
Cerberus PACE –environmental declaration
A6V11948779
Cerberus PACE Compact –environmental
declaration
A6V12161830
Download center
Related documents such as environmental declarations, CE declarations, etc., can
also be downloaded at the following Internet address:
http://siemens.com/bt/download

About this document
Technical terms and abbreviations
1
A6V11899865_en--_b
9 | 54
1.2 Technical terms and abbreviations
You will find details of technical terms and abbreviations in the 'Glossary' chapter.
1.3 Revision history
The reference document's version applies to all languages into which the reference
document is translated.
The first edition of a language version or a country variant may, for example, be
version 'd' instead of 'a' if the reference document is already this version.
The table below shows this document's revision history:
Version
Edition date
Brief description
b
2021-03-12
Updated:
Operating and call stations [➙17]; Call stations [➙19]; Operation PT1002-A1
[➙25]; Operation PT1001-A1 [➙43]; Power supply in PC1002 [➙46];
a
2020-12-30
First edition

Safety
Safety notes
2
10 | 54
A6V11899865_en--_b
2 Safety
2.1 Safety notes
Comply with the following safety notes to protect life, limb, and property.
The safety notes in the document include the following elements:
●Symbol for hazard
●Signal word
●Type and source of hazard
●Consequences in the event the hazard occurs
●Measures or prohibitions to prevent the hazard
Symbol for hazard
This is the symbol for hazard. It warns you of Risks of injury.
Comply with all measures designated by this symbol to prevent injury or
death.
Additional hazard symbols
These symbols indicate general hazards, type of hazard, possible consequences,
measures and prohibitions, a sample of which is displayed in the following table:
General hazard
Potentially explosive
atmospheres
Voltage/electrical shock
Laser light
Battery
Heat
Signal word
The signal word classifies the hazard as defined in the following table:
Signal word
Danger level
DANGER
'DANGER' identifies a dangerous situation, that results directly in death or
serious injuries, if you do not avoid this situation.
WARNING
'WARNING' identifies a dangerous situation, that can result in death or serious
injuries, if you do not avoid this situation.
CAUTION
'CAUTION' identifies a dangerous situation, that can result in minor or
moderate injuries, if you do not avoid this situation.
Note
'NOTE' identifies a possible situation that may cause damage if not observed.
'NOTE' does not reference possible injury.
Depiction of risk of injury
Notes on risk of injury is depicted as follows:

Safety
Safety regulations for the method of operation
2
A6V11899865_en--_b
11 | 54
WARNING
Type and source of hazard
Consequences in the event the hazard occurs
●Measures/prohibitions to prevent the hazard
DEPICTION for possible damage to property
Notes on possible damage to property is depicted as follows:
NOTICE
Type and source of hazard
Consequences in the event the hazard occurs
●Measures/prohibitions to prevent the hazard
2.2 Safety regulations for the method of operation
National standards, regulations and legislation
Siemens products are developed and produced in compliance with the relevant
European and international safety standards. Should additional national or local
safety standards or legislation concerning the planning, mounting, installation,
operation or disposal of the product apply at the place of operation, then these
must also be taken into account together with the safety regulations in the product
documentation.
Electrical installations
WARNING
Electrical voltage
Electric shock
●Work on electrical installations may only be carried out by qualified
electricians or by instructed persons working under the guidance and
supervision of a qualified electrician, in accordance with the electrotechnical
regulations.
●Wherever possible disconnect products from the power supply when carrying
out commissioning, maintenance or repair work on them.
●Lock volt-free areas to prevent them being switched back on again by mistake.
●Label the connection terminals with external voltage using a
'DANGER External voltage' sign.
●Route mains connections to products separately and fuse them with their own,
clearly marked fuse.
●Fit an easily accessible disconnecting device in accordance with EN 62368-1
outside the installation.
●Produce earthing as stated in local safety regulations.

Safety
Safety regulations for the method of operation
2
12 | 54
A6V11899865_en--_b
CAUTION
Noncompliance with the following safety regulations
Risk of injury to persons and damage to property
●Compliance with the following regulations is required.
●Specialist electrical engineering knowledge is required for installation.
●Only an expert is permitted to carry out installation work.
Incorrect installation can take safety devices out of operation unbeknown to a
layperson.
Mounting, installation, commissioning and maintenance
●If you require tools such as a ladder, these must be safe and intended for the
work in question.
●When starting the voice alarm system, make sure that no unstable states can
occur.
●Make sure that all points described in the 'Testing and checking the
functionality of the products' section below are observed.
●You may only put controls into normal operation once work to test and check
the functionality of the products has been completed and the site has been
handed over to the customer.
Testing and checking the functionality of the products
●Prevent incorrect triggering of the remote transmission.
●When you test building equipment or activate devices from third-party
companies, you must liaise with the people responsible for these.
●No one must be injured and no damage to the building equipment must occur
when voice alarm controls are activated for test purposes. The following
instructions must be observed:
–Use the correct potential for the activation; as a rule, this will be the
potential of the building equipment.
–Only check controls up to the interface (relay with blocking option).
–Make sure that only the controls to be tested are activated.
●Inform people before testing alarm devices and determine any potential panic
reactions.
●Inform people of any noise or smoke emission which may occur.
●Inform the corresponding alarm and fault receiving centers before performing a
test remote transmission.
Modifications to the system design and the products
Modifications to the system and to individual products may lead to faults,
malfunctioning and safety risks. Written confirmation must be obtained from
Siemens and the corresponding safety bodies for modifications or additions.
Modules and spare parts
●Components and spare parts must comply with the technical specifications
defined by Siemens. Only use products specified or recommended by Siemens.
●Only use fuses with the specified fuse characteristics.
●Wrong battery types and improper battery changing lead to a risk of explosion.
Only use the same battery type or an equivalent battery type recommended by
Siemens.
●Batteries must be disposed of in an environmentally friendly manner. Observe
national guidelines and regulations.

Safety
System owner
2
A6V11899865_en--_b
13 | 54
Disregard of the safety regulations
Before they are delivered, Siemens products are tested to ensure they function
correctly when used properly. Siemens disclaims all liability for damage or injuries
caused by the incorrect application of the instructions or the disregard of danger
warnings contained in the documentation. This applies in particular to the following
damage:
●Personal injuries or damage to property caused by improper use and incorrect
application
●Personal injuries or damage to property caused by disregarding safety
instructions in the documentation or on the product
●Personal injury or damage to property caused by poor maintenance or lack of
maintenance
2.3 System owner
According to EN 50110-1, the system owner must also ensure that the
commissioning personnel and the operating personnel –see 'Target groups [➙6]'
–have the necessary knowledge relating to the position of operating terminals and
call stations of a Cerberus PACE Compact system.
WARNING
Lack of orientation in the event of an alarm
Delayed measures to prevent damage
●As the system owner, you must ensure that the members of the operating
personnel are aware of the position of all operating terminals and call stations
of the Cerberus PACE Compact system.
2.4 Function test / system acceptance /
maintenance
WARNING
Failure to follow instructions and recommendations
Restricted alarms or no alarms, and personal injury in the case of evacuation.
●Read and follow the instructions and recommendations provided in the
chapters referred to below.
Failure to follow the instructions and recommendations found in the chapters
'System acceptance on site [➙47]' and 'Commissioning and maintenance
[➙48]' may result in the system not being able to help protect the lives and
wellbeing of people at all or to its full potential, especially in the event that an
evacuation is required.

Safety
Standards and directives complied with
2
14 | 54
A6V11899865_en--_b
2.5 Standards and directives complied with
A list of the standards and directives complied with is available from your Siemens
contact.
2.5.1 Multimedia equipment
In the DIN EN 55032 standard (VDE 0878-32):2016-02; EN 55032:2015
'Electromagnetic compatibility of multimedia equipment –Emission Requirements',
the following information is provided on multimedia equipment in section 4:
---- Start EN 55032 section 4 ----
4 Classification of equipment
This standard defines Class A equipment and Class B equipment associated with
two types of end-use environment.
Class A equipment is equipment which meets the requirements given in Table A.2,
Table A.3, Table A.9, and Table A.11, using the limitations defined in Table A.1
and Table A.8.
Class B equipment is equipment which meets the requirements given in Table A.4,
Table A.5, Table A.6, Table A.7, Table A.10, Table A.12 and Table A.13, using the
limitations defined in Table A.1 and Table A.8.
The Class B requirements for equipment are intended to offer adequate protection
to broadcast services within the residential environment.
Equipment intended primarily for use in a residential environment shall meet the
Class B limits. All other equipment shall comply with the Class A limits.
Broadcast receiver equipment is class B equipment.
NOTE Equipment meeting Class A requirements may not offer adequate protection
to broadcast services within a residential environment.
---- End EN 55032 section 4 ----
WARNING
The 'Cerberus PACE Compact' system is a Class A product. Operation of this
equipment in a residential environment could cause radio interference. If so, the
user must be required to take adequate measures.
WARNING
Failure of external devices to comply with the permitted EMC classes
Personal injury and damage to property in an emergency due to a fault with the
system and complete failure of the alarm.
●Check the categorization of external devices in the same room or building that
may have an impact on the 'Cerberus PACE Compact' system, following
DIN EN 55032, section 4, 'Classification of equipment'.

Safety
Cyber security disclaimer
2
A6V11899865_en--_b
15 | 54
2.6 Cyber security disclaimer
Siemens provides a portfolio of products, solutions, systems and services that
includes security functions that support the secure operation of plants, systems,
machines and networks. In the field of Building Technologies, this includes building
automation and control, fire safety, security management as well as physical
security systems. In order to protect plants, systems, machines and networks
against cyber threats, it is necessary to implement –and continuously maintain –a
holistic, state-of-the-art security concept. Siemens’ portfolio only forms one element
of such a concept.
You are responsible for preventing unauthorized access to your plants, systems,
machines and networks which should only be connected to an enterprise network
or the internet if and to the extent such a connection is necessary and only when
appropriate security measures (e.g. firewalls and/or network segmentation) are in
place. Additionally, Siemens’ guidance on appropriate security measures should be
taken into account. For additional information, please contact your Siemens sales
representative or visit https://www.siemens.com/global/en/home/company/topic-
areas/future-of-manufacturing/industrial-security.html.
Siemens’ portfolio undergoes continuous development to make it more secure.
Siemens strongly recommends that updates are applied as soon as they are
available and that the latest versions are used. Use of versions that are no longer
supported, and failure to apply the latest updates may increase your exposure to
cyber threats. Siemens strongly recommends to comply with security advisories on
the latest security threats, patches and other related measures, published, among
others, under https://www.siemens.com/cert/en/cert-security-advisories.htm.

Operating conditions
Operating condition indicators
3
16 | 54
A6V11899865_en--_b
3 Operating conditions
The ↑voice alarm control and indicating equipment (VACIE) or voice alarm
system has the following operating conditions:
●Quiescent condition
●Voice alarm condition
●Fault warning condition
3.1 Operating condition indicators
Indicating element colors
The light-emitting indicating elements display the operating conditions as follows:
Color
↑Operating condition
Red
↑Voice alarm condition
Yellow
↑Fault warning condition
Green
↑Quiescent condition
VACIE is supplied with energy
Evacuation messages and alert messages
Automatic voice messages for evacuation messages and alert messages are
indicated as follows:
Color
Operating condition
Red
Evacuation messages
Green
Alert messages or standard messages
Fault warning condition and RSL
Causes of a fault being displayed are defined in the ↑'RSL when the system is
configured with 'PACE-Design'.

Operating elements in the system
Operating and call stations
4
A6V11899865_en--_b
17 | 54
4 Operating elements in the system
The operating elements in a Cerberus PACE Compact voice alarm system are the
call stations and operating terminals with which you can make live announcements
and play emergency tones and recorded messages in a targeted manner.
In addition, you can carry out key system functions, read off the system state, and
also play music using these operating elements.
4.1 Operating and call stations
PT1001-A1
'System operating unit'
●EN 54-16-compliant indicator panel for visual and acoustic status messages
and controlling voice alarms
●For installation in a Cerberus PACE Compact cabinet door
●Lockable viewing front door
●Insertable labels for custom button identification
●Insertable labels in English, German and Netherlands are enclosed
●Display of system status
●Control of voice alarms
●Fault warning with acoustic warning signal
●Color-coded visual indicators: operation, fault, and alarm
–Operation: green
–Fault: yellow
–Voice Alarm: red
●Color-coded control buttons: control of voice alarms, acknowledges
–<Start Voice Alarm>: red LED indicator button
–<Reset Voice Alarm>: black button
–<Silence Voice Alarm>: green LED indicator button
–<Reset Fault>: black button (acknowledge faults)
–<Silence Buzzer / LED Test>: black button (acknowledge acoustic
warning and LED test)
●8 predefined visual fault indicators: yellow
–Power fault
–Fuse fault
–Earth fault
–Network fault
–Bus (RS485) fault
–Amplifier fault
–Microphone fault
–Speaker circuit fault
●8 user-configurable visual state indicators: yellow
●'PACE-Bus' (RS485) data transmission
●Addressable via a 4-way SIP (Single Inline Package) switch for 'PACE-Bus'
connection
●Supplied with an installation frame
●Supplied with a pre-assembled cable to facilitate the wiring to the cabinet door

Operating elements in the system
Operating and call stations
4
18 | 54
A6V11899865_en--_b
PT1002-A1
'System operating unit and call station'
●EN 54-16-compliant indicator panel for visual and acoustic status messages
and controlling voice alarms
●Call station with 8 configurable and illuminated zone buttons
●For installation in a Cerberus PACE Compact cabinet door
●Lockable viewing front door
●Insertable labels for custom button identification
●Insertable labels in English, German and Netherlands are enclosed
●Removable hand-held microphone with talk button
●Microphone and line monitoring
●Symmetrical audio transmission, analog
●Audio output 0 dB (line volume)
●Integrated speaker
●Display of system status
●Control of voice alarms
●Fault warning with acoustic warning signal
●Color-coded visual indicators: operation, fault, and alarm
–Operation: green
–Fault: yellow
–Voice Alarm: red
●Color-coded control buttons: control of voice alarms, acknowledges
–<Start Voice Alarm>: red LED indicator button
–<Reset Voice Alarm>: black button
–<Silence Voice Alarm>: green LED indicator button
–<Reset Fault>: black button (acknowledge faults)
–<Silence Buzzer / LED Test>: black button (acknowledge acoustic
warning and LED test)
●8 predefined visual fault indicators: yellow
–Power fault
–Fuse fault
–Earth fault
–Network fault
–Bus (RS485) fault
–Amplifier fault
–Microphone fault
–Speaker circuit fault
●8 user-configurable visual state indicators: yellow
●'PACE-Bus' (RS485) data transmission
●Addressable via 4-way SIP (Single Inline Package) switch for 'PACE-Bus'
connection
●Supplied with installation frame
●Supplied with an adapter module PTO2008-A1 and pre-assembled cables to
facilitate the wiring to the cabinet door

Operating elements in the system
Call stations
4
A6V11899865_en--_b
19 | 54
4.2 Call stations
PT2002-A1
'Fire brigade call station (AT)'
●Alarm call station with standard-compliant housing and control panel
●Full network participant in a Cerberus PACE Compact system
●7 standardized and configurable buttons
●3 standardized and preconfigured displays
●Removable hand-held microphone with talk button
●Microphone and line monitoring
●Integrated audio amplifier (1 watt) and speaker
●Real-time audio transmission with constant latency: 4.6 ms analog-in/analog-
out
●Integrated industrial micro SD card reader/writer with max. 2 GB card capacity
for alarm messages
●Recording capacity: 256 files with a total duration of approx. 3 hours
●Provision of alarm announcements and alarm tones
●2x Ethernet LAN interfaces for connection to 'PACE-Net'
●One additional audio input (line) and one additional audio output
●Adapter module PTO2009-A1 for redundant connection to the control panel
PT2003-A1
'Fire brigade call station (485, AT)'
●Alarm call station with standard-compliant housing and control panel
●7 standardized and configurable buttons
●3 standardized and preconfigured displays
●Removable hand-held microphone with talk button
●Microphone and line monitoring
●Symmetrical audio transmission, analog
●Audio output 0 dB (line volume)
●'PACE-Bus' (RS485) data transmission
●Connection to control panel via CAT5 cable (max. 500 m)
●Connection to control panel with RJ45 or screw terminal connector
●Adapter module PTO2008-A1 for connection to the control panel
●Addressable via 4-way SIP (Single Inline Package) switch in device

Operating elements in the system
Call stations
4
20 | 54
A6V11899865_en--_b
PT2001-A1
'Desk call station (19 buttons)'
●Call station with electret condenser microphone and gooseneck
●Full network participant in a Cerberus PACE Compact system
●2-line text display
●Buttons and status indicators to control and monitor the Cerberus PACE
Compact system by users. The buttons are basically freely operable
●Insertable labels for custom button identification
●Monitored microphone
●Integrated audio amplifier (1 watt) and speaker
●1x additional audio input (line/mic) and 1x additional audio output
●4x digital inputs, 4x digital outputs, and 6x analog control inputs
●Live speech / real-time audio transmission and integrated real-time recorder
for delayed announcements
●Integrated micro SD card reader/writer with max. 2 GB card capacity for alarm
messages
●Recording capacity: 256 files with a total duration of approx. 3 hours
●Provision of alarm announcements and alarm tones
●2x Ethernet LAN interfaces for connection to 'PACE-Net'
●Up to four extension modules PTO2001-A1 per desk call station PT2001-A1
to a maximum of 115 buttons
●Can be extended with key switch module PTO2002-A1 or PTO2003-A1 to
enable buttons to be released or locked
●Adapter module PTO2009-A1 for redundant connection to the control panel
PTO2001-A1
'Desk call station extension (24 buttons)'
●Optional button extension for the desk call station PT2001-A1
●24 freely configurable buttons
●Up to 4x button extensions per desk call station PT2001-A1, offering a total of
115 buttons
●Insertable labels for custom button identification
PTO2002-A1
'Desk call station extension (Kaba)'
●Call station extension for PT2001-A1 with key switch (Kaba)
●Enables call station operation
PTO2003-A1
'Desk call station extension (Nordic)'
●Call station extension for PT2001-A1 with key switch (Nordic)
●Enables call station operation
Other manuals for Cerberus PACE Compact
1
Table of contents
Other Siemens Safety Equipment manuals

Siemens
Siemens SIRIUS 3SB3801-2EA30 Series User manual

Siemens
Siemens FDM1101-Rx User manual

Siemens
Siemens LFS1 Series User manual

Siemens
Siemens SIRIUS 8WD42 User manual

Siemens
Siemens LME71 Operator's manual

Siemens
Siemens FS-MSM Assembly instructions

Siemens
Siemens SIRIUS 3TK2821 User manual

Siemens
Siemens SIRIUS 3RK3 Technical Document

Siemens
Siemens 3RB30 Installation and operation manual

Siemens
Siemens FDM243H User manual