Siemens FDM243H User manual

FDM243H
Manual call point
Technical Manual
A6V10374021_f_en_-- Smart Infrastructure
2020-09-04

Imprint
Technical specifications and availability subject to change without notice.
Transmittal, reproduction, dissemination and/or editing of this document as well as
utilization of its contents and communication thereof to others without express
authorization are prohibited. Offenders will be held liable for payment of damages.
All rights created by patent grant or registration of a utility model or design patent
are reserved.
Issued by:
Siemens Switzerland Ltd.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 724-2424
www.siemens.com/buildingtechnologies
Edition: 2020-09-04
Document ID: A6V10374021_f_en_--
© Siemens Switzerland Ltd, 2013
Imprint
2 | 38 A6V10374021_f_en_--

A6V10374021_f_en_-- 3 | 38
Table of contents
1 About this document................................................................................. 5
1.1 Applicable documents .............................................................................. 6
1.2 Technical terms ........................................................................................ 7
1.3 History of changes.................................................................................... 7
2 Safety ....................................................................................................... 8
2.1 Safety notes.............................................................................................. 8
2.2 Safety regulations for the method of operation......................................... 9
2.3 Standards and directives complied with ................................................... 11
2.4 Release Notes .......................................................................................... 11
3 Structure and function .............................................................................. 12
3.1 Overview................................................................................................... 12
3.1.1 Details for ordering ..................................................................... 12
3.1.2 Product version ........................................................................... 13
3.2 Setup ........................................................................................................ 14
3.2.1 Manual call point ......................................................................... 14
3.2.2 Connections ................................................................................ 15
3.2.3 Indication elements..................................................................... 15
3.3 Function.................................................................................................... 16
3.3.1 Danger levels .............................................................................. 16
3.3.2 Internal alarm indicator ............................................................... 16
3.3.3 Line separator............................................................................. 16
3.3.4 Test mode on the manual call point............................................ 16
3.3.5 Diagnosis levels .......................................................................... 17
3.3.6 Behavior in degraded mode........................................................ 17
3.4 Accessories .............................................................................................. 19
3.4.1 Glass insert FDMG298 ............................................................... 19
3.4.2 Key FDMK294 ............................................................................ 19
3.4.3 M20x1.5 metal cable gland....................................................... 19
4 Planning.................................................................................................... 20
4.1 Compatibility ............................................................................................. 20
4.2 Fields of application.................................................................................. 20
4.3 Mounting site ............................................................................................ 20
4.4 Environmental influences ......................................................................... 20
5 Mounting/Installation................................................................................. 21
5.1 Preparation ............................................................................................... 21
5.2 Installation ................................................................................................ 22
5.3 Installation ................................................................................................ 23
6 Commissioning ......................................................................................... 26
6.1 Localization and device testing................................................................. 26
6.2 Checking function ..................................................................................... 27
7 Maintenance/Repair ............................................................................... 30
7.1 Resetting after an alarm ........................................................................... 30
7.2 Status query ............................................................................................. 31
7.3 Performance check................................................................................... 31

4 | 38 A6V10374021_f_en_--
7.4 Replacing the glass insert ........................................................................ 31
8 Specification ............................................................................................. 34
8.1 Technical data .......................................................................................... 34
8.2 Dimensions............................................................................................... 35
8.3 Master gauge for recesses ....................................................................... 36
8.4 Environmental compatibility and disposal................................................. 36
Index................................................................................................................... 37

1 About this document
Goal and purpose
This document contains all information on the manual call point FDM243H.
Following the instructions consistently will ensure that the product can be used
safely and without any problems.
Target groups
The information in this document is intended for the following target groups:
Target group Activity Qualification
Product Manager ● Is responsible for information
passing between the manufacturer
and regional company.
● Coordinates the flow of information
between the individual groups of
people involved in a project.
● Has obtained suitable specialist
training for the function and for the
products.
● Has attended the training courses
for Product Managers.
Project Manager ● Coordinates the deployment of all
persons and resources involved in
the project according to schedule.
● Provides the information required to
run the project.
● Has obtained suitable specialist
training for the function and for the
products.
● Has attended the training courses
for Project Managers.
Project engineer ● Sets parameters for product
depending on specific national and/
or customer requirements.
● Checks operability and approves
the product for commissioning at
the place of installation.
● Is responsible for troubleshooting.
● Has obtained suitable specialist
training for the function and for the
products.
● Has attended the training courses
for Product Engineer.
Installation personnel ● Assembles and installs the product
components at the place of
installation.
● Carries out a performance check
following installation.
● Has received specialist training in
the area of building installation
technology or electrical installations.
Maintenance personnel ● Carries out all maintenance work.
● Checks that the products are in
perfect working order.
● Searches for and corrects
malfunctions.
● Has obtained suitable specialist
training for the function and for the
products.
Document identification
The document ID is structured as follows:
ID code Examples
ID_ModificationIndex_Language_COUNTRY
-- = multilingual or international
A6V10215123_a_de_DE
A6V10215123_a_en_--
A6V10315123_a_--_--
Date format
The date format in the document corresponds to the recommendation of
international standard ISO8601 (format YYYY-MM-DD).
Conventions for text marking
Markups
About this document 1
A6V10374021_f_en_-- 5 | 38

Special markups are shown in this document as follows:
wRequirement for a behavior instruction
1.
2.
Behavior instruction with at least two operation sequences
◈Behavior instruction with one operation sequence
– Version, option, or detailed information for a behavior instruction
aIntermediate result of a behavior instruction
aEnd result of a behavior instruction
● Lists
[➙ X] Reference to a page number
'Text' Quotation, reproduced identically
<Key> Identification of keys
> Relation sign and for identification between steps in a sequence,
e.g., 'Menu bar' > 'Help' > 'Help topics'
↑Text Identification of a glossary entry
Supplementary information and tips
The 'i' symbol identifies supplementary information and tips for an easier way of
working.
1.1 Applicable documents
Document ID Title
008250 Technical Manual Line tester FDUL221
008331 List of compatibility (for 'Sinteso™' product line)
008838 Operation Manual Fire control panel / Fire terminal FC20xx / FT2040
009052 FS20 Fire detection system - Commissioning, Maintenance,
Troubleshooting
A6V10210416 FS720 Fire detection system - Commissioning, Maintenance,
Troubleshooting
A6V10211076 Operation Manual Fire control panel / Fire terminal FC72x / FT724
A6V10229261 List of compatibility (for 'Cerberus™ PRO' product line)
A6V10356927 Data sheet Manual call point FDM243H
A6V10374023 Installation Manual call point FDM243H
About this document
Applicable documents
1
6 | 38 A6V10374021_f_en_--

1.2 Technical terms
Term Explanation
FDnet/C-NET Addressed detector line
LED Light-emitting diode
1.3 History of changes
The reference document's version applies to all languages into which the reference
document is translated.
The first edition of a language version or a country variant may, for example, be
version 'd' instead of 'a' if the reference document is already this version.
The table below shows this document's history of changes:
Version Edition date Brief description
f 2020-09-04 'Installation [➙22]' chapter Torque 1.5Nm added
e 2018-04-03 New address inserted
d 2017-01-26 Characteristic data changed to 1.5 A, 2 A, and 0.4 Ω in 'Line separator' section in
'Technical data' chapter
c 2014-07-01 Installation height changed from 1.3…1.6m to 0.9…1.6m
V-pins removed from accessories
Details for ordering added
b 2013-09-18 Approvals supplemented
Key for FDMK294 modified
a 2013-02-01 First edition
About this document
Technical terms 1
A6V10374021_f_en_-- 7 | 38

2 Safety
2.1 Safety notes
Comply with the following safety notes to protect life, limb, and property.
The safety notes in the document include the following elements:
● Symbol for hazard
● Signal word
● Type and source of hazard
● Consequences in the event the hazard occurs
● Measures or prohibitions to prevent the hazard
Symbol for hazard
This is the symbol for hazard. It warns you of Risks of injury.
Comply with all measures designated by this symbol to prevent injury or
death.
Additional hazard symbols
These symbols indicate general hazards, type of hazard, possible consequences,
measures and prohibitions, a sample of which is displayed in the following table:
General hazard Potentially explosive
atmospheres
Voltage/electrical shock Laser light
Battery Heat
Signal word
The signal word classifies the hazard as defined in the following table:
Signal word Danger level
DANGER 'DANGER' identifies a dangerous situation, that results directly in death or serious
injuries, if you do not avoid this situation.
WARNING 'WARNING' identifies a dangerous situation, that can result in death or serious
injuries, if you do not avoid this situation.
CAUTION 'CAUTION' identifies a dangerous situation, that can result in minor or moderate
injuries, if you do not avoid this situation.
Note
'
NOTE
' identifies a possible situation that may cause damage if not observed.
'
NOTE
' does not reference possible injury.
Depiction of risk of injury
Notes on risk of injury is depicted as follows:
WARNING
Type and source of hazard
Consequences in the event the hazard occurs
● Measures/prohibitions to prevent the hazard
Safety
Safety notes
2
8 | 38 A6V10374021_f_en_--

DEPICTION for possible damage to property
Notes on possible damage to property is depicted as follows:
NOTICE
Type and source of hazard
Consequences in the event the hazard occurs
● Measures/prohibitions to prevent the hazard
2.2 Safety regulations for the method of operation
National standards, regulations and legislation
Siemens products are developed and produced in compliance with the relevant
European and international safety standards. Should additional national or local
safety standards or legislation concerning the planning, mounting, installation,
operation or disposal of the product apply at the place of operation, then these
must also be taken into account together with the safety regulations in the product
documentation.
Electrical installations
WARNING
Electrical voltage
Electric shock
● Work on electrical installations may only be carried out by qualified
electricians or by instructed persons working under the guidance and
supervision of a qualified electrician, in accordance with the electrotechnical
regulations.
● Wherever possible disconnect products from the power supply when carrying
out commissioning, maintenance or repair work on them.
● Lock volt-free areas to prevent them being switched back on again by mistake.
● Label the connection terminals with external voltage using a
'DANGERExternal voltage' sign.
● Route mains connections to products separately and fuse them with their own,
clearly marked fuse.
● Fit an easily accessible disconnecting device in accordance with IEC60950‑1
outside the installation.
● Produce earthing as stated in local safety regulations.
CAUTION
Noncompliance with the following safety regulations
Risk of injury to persons and damage to property
● Compliance with the following regulations is required.
● Specialist electrical engineering knowledge is required for installation.
● Only an expert is permitted to carry out installation work.
Incorrect installation can take safety devices out of operation unbeknown to a
layperson.
Safety
Safety regulations for the method of operation 2
A6V10374021_f_en_-- 9 | 38

Mounting, installation, commissioning and maintenance
● If you require tools such as a ladder, these must be safe and must be intended
for the work in hand.
● When starting the fire control panel ensure that unstable conditions cannot
arise.
● Ensure that all points listed in the 'Testing the product operability' section below
are observed.
● You may only set controls to normal function when the product operability has
been completely tested and the system has been handed over to the customer.
Testing the product operability
● Prevent the remote transmission from triggering erroneously.
● If testing building installations or activating devices from third-party companies,
you must collaborate with the people appointed.
● The activation of fire control installations for test purposes must not cause
injury to anyone or damage to the building installations. The following
instructions must be observed:
– Use the correct potential for activation; this is generally the potential of the
building installation.
– Only check controls up to the interface (relay with blocking option).
– Make sure that only the controls to be tested are activated.
● Inform people before testing the alarm devices and allow for possible panic
responses.
● Inform people about any noise or mist which may be produced.
● Before testing the remote transmission, inform the corresponding alarm and
fault signal receiving stations.
Modifications to the system design and the products
Modifications to the system and to individual products may lead to faults,
malfunctioning and safety risks. Written confirmation must be obtained from
Siemens and the corresponding safety bodies for modifications or additions.
Modules and spare parts
● Components and spare parts must comply with the technical specifications
defined by Siemens. Only use products specified or recommended by
Siemens.
● Only use fuses with the specified fuse characteristics.
● Wrong battery types and improper battery changing lead to a risk of explosion.
Only use the same battery type or an equivalent battery type recommended by
Siemens.
● Batteries must be disposed of in an environmentally friendly manner. Observe
national guidelines and regulations.
Disregard of the safety regulations
Before they are delivered, Siemens products are tested to ensure they function
correctly when used properly. Siemens disclaims all liability for damage or injuries
caused by the incorrect application of the instructions or the disregard of danger
warnings contained in the documentation. This applies in particular to the following
damage:
● Personal injuries or damage to property caused by improper use and incorrect
application
● Personal injuries or damage to property caused by disregarding safety
instructions in the documentation or on the product
● Personal injury or damage to property caused by poor maintenance or lack of
maintenance
Safety
Safety regulations for the method of operation
2
10 | 38 A6V10374021_f_en_--

2.3 Standards and directives complied with
A list of the standards and directives complied with is available from your Siemens
contact.
2.4 Release Notes
Limitations to the configuration or use of devices in a fire detection installation with
a particular firmware version are possible.
WARNING
Limited or non-existent fire detection
Personal injury and damage to property in the event of a fire.
● Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
● Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.
NOTICE
Incorrect planning and/or configuration
Important standards and specifications are not satisfied.
Fire detection installation is not accepted for commissioning.
Additional expense resulting from necessary new planning and/or configuration.
● Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
● Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.
Safety
Standards and directives complied with 2
A6V10374021_f_en_-- 11 | 38

3 Structure and function
3.1 Overview
The manual call points are intended for use in places where a fire can be detected
by people who can manually trigger an alarm.
The manual call point consists of a housing and a switching unit. It has the
following features:
● Indirect activation
● Door contact connected with magnet
● Two-wire installation for all cable types
● Cable entry from below for two surface-mounted feed lines
● Individual detector addressing
● Indication of the condition (Alarm, localization or test) by means of a
dichromatic LED
● Integrated line separation function
● Communication via FDnet/C-NET
● Sturdy housing for use outdoors and in humid areas
Manual call point FDM243H
3.1.1 Details for ordering
Manual call point FDM243H:
Type Order no. Designation
FDM243H S54311-F8-A1 Manual call point
Scope of delivery:
● Red housing with glass insert and switching unit
● 1key
● 1V-pinM20x1.5
● 2screws
● 2pins
See also
2Accessories [➙ 19]
Structure and function
Overview
3
12 | 38 A6V10374021_f_en_--

3.1.2 Product version
The product version is a two-digit code which denotes the technical release of a
device’s software and hardware.
The product version is quoted on the product label/type plate after the order
number.
Product version on product label
Système de
Sécurité Incendie
NF 508 (SSI)
www.marque-nf.com
ID-Nr. 5C7E802
FDOOT241-A
S54310-F13-A1
Country of Origin: Switzerland
ID-Nr. 5C7E802
61
51L P100 M
Figure 1: Example product label
Product version on packaging label
FDOOT241-A
Country of Origin: SwitzerlandSiemens Switzerland Ltd, CH-6300 Zug
Neural fire detector, ASA
Technical documentation see: www.siemens.com/bt/download
1P S54310-F13-A1
16D 20191217
2PFS 61
16D 20191
2PFS 61
Figure 2: Example packaging label
Depending on the product and various approvals, the product labels may differ in
terms of the type of information provided and its layout.
Up until 2019, some product labels included the abbreviation “ES” before the two-
digit code denoting the product version.
Structure and function
Overview 3
A6V10374021_f_en_-- 13 | 38

3.2 Setup
3.2.1 Manual call point
The manual call point FDM243H triggers an alarm when the glass insert is pushed
in and the alarm button is pressed (indirect activation). The alarm is immediately
transmitted to the control panel.
When the alarm is activated, the switching unit must be reset and a new glass
insert installed.
234
567
1
8
9
10
11
Figure 3: Manual call point FDM243H with open door
1 Housing 7 Switching magnet for door contact
2 Switching unit 8 Retainer for glass insert
3 Alarm button 9 Guide for the glass insert
4 Internal alarm indicator 10 Stopping lever for resetting
5 Door 11 Screwed cable gland
6 Glass insert
Structure and function
Setup
3
14 | 38 A6V10374021_f_en_--

3.2.2 Connections
The manual call point has eight spring clips on the rear of the switching unit; these
are for the detector line and for connecting external alarm indicators.
Figure 4: Spring clips on the rear of the switching unit
3.2.3 Indication elements
An LED is built into the switching unit as an internal alarm indicator.
Figure 5: Internal alarm indicator
Structure and function
Setup 3
A6V10374021_f_en_-- 15 | 38

3.3 Function
3.3.1 Danger levels
The manual call point can transmit the following danger levels to the control panel:
Danger level Meaning
0 Normal state, no danger
3 Alarm
Door status
Danger level Meaning
0 Door closed
2 Door open
The evaluation of the danger level and the resulting measures (e.g.activation of
remote transmission) are configured on the control panel.
3.3.2 Internal alarm indicator
The LED indicator of the alarm indicator has the following meanings:
LED indication Meaning
Off ● Normal condition
Green
Flashes once per second
● Test mode is active
Red
Flashes once per second
● Localization is active
o r
● Alarm is triggered
Red and green alternating
Flashes twice per second
● Alarm is triggered/localization is active
a n d
● Test mode is active
3.3.3 Line separator
All FDnet/C-NET devices are equipped with a line separator.
The FDnet/C-NET device is equipped with electronic switches which isolate the
defective part in case of a short-circuit on the FDnet/C-NET detector line. The rest
of the detector line remains serviceable. On a loop line, all FDnet/C-NET devices
remain fully functional after a single short-circuit.
3.3.4 Test mode on the manual call point
You can activate test mode in the fire control panel by opening the door, and
deactivate it by closing the door again. The test mode is only active for a short time
and is indicated by the green LED. Therefore, you should work quickly to complete
the steps between opening the door and closing it again. Make sure you do not
unintentionally activate an alarm. See the chapter 'Checking function [➙27]'.
Structure and function
Function
3
16 | 38 A6V10374021_f_en_--

Please observe the documentation for your fire control panel.
Not every fire control panel allows test mode to be activated automatically. For
some fire control panels, this function must be set explicitly. This setting may be
automatically deactivated under certain circumstances. So that test mode can
also be used from the manual call point with an FC20xx/FC72x fire control panel,
MC link communication, for example, must be active.
Enabling on FC20xx fire control panels
You will find more information for FC20xx fire control panels in 'Enabling detector
exchanger and tester communication' in document number 008838.
Enabling on FC72x fire control panels
1. In the main menu, select the 'Functions' menu item.
aThe 'Functions' window is open.
2. Select 'Maintenance' and confirm with <ok>.
aA list of all element categories on which a command of the 'Maintenance'
command group can be executed is indicated.
3. Select the 'Element category' 'Station'.
aThe 'Enter address' window is open.
4. Enter the number of the 'Station' on which you want to enable communication
with the detector exchanger and tester and confirm with <ok>.
aThe 'Select command' window is open.
5. Select the 'Enable MC link' command and confirm with <ok>.
aCommunication is now enabled.
Automatic deactivation of test mode, e.g. for FC20xx/FC72x:
● Once a specified time has elapsed, deactivation occurs after 60seconds.
● Deactivation occurs immediately when a customer text, for example, is
downloaded.
● Deactivation occurs immediately when the double CPU is changed over.
3.3.5 Diagnosis levels
The manual call point monitors its operation largely autonomously.
The following diagnosis levels are derived from the different control measurements:
● Normal, no fault is present
● Replacement necessary
● Fault present
When an error occurs which impairs the correct functionality of the device, a fault
message is reported to the control panel.
3.3.6 Behavior in degraded mode
Applicable for the FDnet/C-NET:
When the main processor of the fire control panel fails, the control panel works in
degraded mode operation. Depending on the control panel type, the fire control
panel can continue to perform the most important alarming and signaling functions
in degraded mode operation.
Structure and function
Function 3
A6V10374021_f_en_-- 17 | 38

Behavior of control panels that support degraded mode operation:
● Alarming is still ensured in degraded mode operation. However, in degraded
mode only collective alarming is possible. This means that in the event of an
alarm, it is possible to identify the FDnet/C-NET detector line but not the exact
location of the detector triggering the alarm.
Degraded mode operation on the FDnet/C-NET is not supported in the same way
by all control panels. The information in the 'List of compatibility' and in the
corresponding control panel documentation must be taken into account during
project planning.
Structure and function
Function
3
18 | 38 A6V10374021_f_en_--

3.4 Accessories
3.4.1 Glass insert FDMG298
● For alarm activation and protection against soiling
● Compatible with:
– Manual call point FDM243H
● Order no.: S54311-B8-A1
3.4.2 Key FDMK294
● Plastic key
● For opening doors on manual call points
● To help with resetting the alarm button
● Compatible with:
– Manual call point FDM233
– Manual call point FDM234
– Manual call point FDM243H
● Order number: S24217-G34-A1
3.4.3 M20x1.5 metal cable gland
● For introducing a cable into a housing
● For cable diameters of 3.5…5.5mm
● Temperature range: -40…+100°C
● Allows for increased IP protection
● Compatible with:
– M20x1.5 metal counter nut
– Housing FDMH231-S-R
– Housing FDMH292-x
– Housing FDMH293-x
– Housing FDMH297-R
– Housing FDCH221
– Manual call point FDM243H
– Air sampling smoke detection kit FDBZ290
– Base deep (wall mounting) FDB227‑x
● Order number: A5Q00004478
Structure and function
Accessories 3
A6V10374021_f_en_-- 19 | 38

4 Planning
4.1 Compatibility
Compatible with control panels that support the FDnet/C-NET detector line.
Detector line Control panel
FC20xx FC72x SIGMASYS AlgoRex
FDnet X – – –
C-NET – X – –
X = compatible
– = not compatible
You will find detailed information in the 'List of compatibility'.
4.2 Fields of application
The manual call points are intended for use in places where a fire can be detected
by people who can manually trigger an alarm.
4.3 Mounting site
The manual call points must be installed in easily accessible places at a height of
0.9...1.6m on an even surface.
Observe the country-specific regulations for the exact mounting height!
4.4 Environmental influences
If the devices are used in industrial applications, consultation with the project
manager is required, since plastics do not withstand certain environmental
conditions.
The following factors must be taken into consideration:
● Chemicals
● Temperature
● Moisture
Planning
Compatibility
4
20 | 38 A6V10374021_f_en_--
Other manuals for FDM243H
2
Table of contents
Other Siemens Safety Equipment manuals

Siemens
Siemens Cerberus PACE Compact User manual

Siemens
Siemens SIRIUS 3RK3 Technical Document

Siemens
Siemens SIRIUS 3TK2821 User manual

Siemens
Siemens LFS1 Series User manual

Siemens
Siemens LME71 Operator's manual

Siemens
Siemens SIRIUS 8WD42 User manual

Siemens
Siemens 3TK2853 User manual

Siemens
Siemens 3RB30 Installation and operation manual

Siemens
Siemens SIRIUS 3SB3801-2EA30 Series User manual

Siemens
Siemens SIRIUS 3RK1105-1AE04-0CA0 User manual