  9. SMC Networks 56-EX500-GPR1A Series User manual

SMC Networks 56-EX500-GPR1A Series User manual

56-EX500-TF2Z330EN
Page 1 of 2
Instruction Manual
Gateway unit – PROFIBUS-DP compatible
Series 56-EX500-GPR1A
II 3G Ex ec IIC T4 Gc 5
o
C
≤
Ta
≤
45
o
C
II 3D Ex tc IIIC T57oC Dc IP65
The intended use of the Gateway unit is for connection to SI units and
input devices for the control of pneumatic valves.
1 Safety Instructions
These safety instructions are intended to prevent hazardous situations
and/or equipment damage. These instructions indicate the level of
potential hazard with the labels of “Caution,” “Warning” or “Danger.”
They are all important notes for safety and must be followed in addition
to International Standards (ISO/IEC)*1), and other safety regulations.
*1) ISO 4414: Pneumatic fluid power - General rules relating to systems.
ISO 4413: Hydraulic fluid power - General rules relating to systems.
IEC 60204-1: Safety of machinery - Electrical equipment of machines.
(Part 1: General requirements)
ISO 10218-1: Manipulating industrial robots -Safety. etc.
•Refer to product catalogue, Operation Manual and Handling
Precautions for SMC Products for additional information.
•Keep this manual in a safe place for future reference.
Caution
Caution indicates a hazard with a low level of risk which, if
not avoided, could result in minor or moderate injury.
Warning
Warning indicates a hazard with a medium level of risk
which, if not avoided, could result in death or serious injury.
Danger
Danger indicates a hazard with a high level of risk which, if
not avoided, will result in death or serious injury.
Warning
•Always ensure compliance with relevant safety laws and
standards.
•All work must be carried out in a safe manner by a qualified person in
compliance with applicable national regulations.
ATEX Marking Description
II 3G Ex ec IIC T4 Gc 5oC
≤
Ta
≤
45oC
II 3D Ex tc IIIC T57oC Dc IP65
Equipment Group II
Category 3
Gas (G) and Dust (D) environment
Ex - European standards apply
ec – Increased safety
IIC - for all types of gas
T4 - Temperature classification
tc - protected by enclosure
lllC - for all types of dust
T57oC - Max. surface temperature
Gc/Dc - Equipment Protection Level
Ta - ambient temperature
IP65 - Protection structure
Based on the conformity assessment carried out by SMC Corporation.
Certificate Number:
SMC 20.0004 X
If the Certificate number includes an X, special conditions for safe use
apply as follows:-
•Protect the product from sources of heat which can generate surface
temperatures greater than the temperature classification.
•Protect the product and cable connections against all impact or
mechanical damage using a suitable ATEX compliant enclosure.
1 Safety Instructions (continued)
•Protect the product from direct sunlight or UV light using a suitable
protective cover.
•Do not disconnect the M12 connectors before first switching OFF the
power supply.
•Use only ATEX approved connectors and use shielded cable to
provide grounding.
•Use only a damp cloth to clean the product to avoid an electrostatic
charge.
2 Specifications
General specifications
Item
Specifications
Ambient temperature
5 to 45
o
C
Ambient humidity
35 to 85% RH (no condensate)
Ambient storage temperature
-
25 to +70
o
C
Withstand voltage
1000 VAC applied for 1 minute
Insulation resistance
500 VDC, 2 MΩor more
Weight
470 g
Electrical specifications
3 Name and function of Individual parts
No
Part
Description
1
Fieldbus connector
Connection to PROFIBUS-DP
2
Power supply connector
Connection for power supply.
3
Connector (COM A)
Connection to SI units (manifold valve)
or input units using a branch cable.
4
Connector (COM B)
5
Connector (COM C)
6
Connector (COM D)
7
LED Display
Displays the unit status.
8
Switch cover
Setting switches under the cover.
9
Ground terminal
Functional Earth (FE)
4 Installation
4.1 Direct mounting
Secure in position using 4 x M5 screws, 15 mm minimum thread length.
4.2 Wiring connections
•Communication Connector
Select the appropriate cables to mate with the connectors on the SI
unit. The PROFIBUS-DP connection has 2 ports, BUS IN and BUS
OUT, and both ports can be used for connection.
M12 5-pin Plug / Socket (B-coded)
Connector
Pin No. Signal name
BUS IN
BUS OUT
1
N.C.
2
RxD/TxD-N
3
N.C.
4
RxD/TxD-P
Plug
Socket
5
Shield
•Power Supply Connector
Connect the power supply to the power supply connector on the
Gateway unit. With this cable, power is supplied to the output devices
(such as solenoid valve) and the input devices and for control.
The M12 connector cable for fieldbus and power supply connections
has two types, Standard M12 and SPEEDCON compatible. If both
plug and socket have SPEEDCON connectors, the cable can be
inserted and connected by turning it a 1/2 rotation.
A standard connector can be connected to a SPEEDCON connector.
•Both single and two power supply systems can be adopted, however
the wiring should be made separately (for solenoid valves / outputs
and for input and control) for either system.
•Branch Connector
Connect SI units (solenoid valves) and input devices to the
communication connectors (COM A - D) using an M12 (8 pin)
connector cable.
As each cable contains power supply wiring, there is no need to
supply power to the SI unit (solenoid valves) or input devices
separately.
Warning
•Be sure to fit a seal cap (EX9-AWTS) on any unused connectors.
Proper use of the seal cap enables the enclosure to maintain IP65
specification. Tightening torque: 0.1 N•m.
4.3 Ground Connection
•Connect the ground terminal (FE) to ground.
•Individual grounding should be provided close to the product with a
short cable to assure the safety and noise resistance of the system.
•Resistance to ground should be 100 Ω or less.
4 Installation (continued)
4.4 Environment Warning
•Do not use in an environment where corrosive gases, chemicals, salt
water or steam are present.
•Do not install in a location subject to vibration or impact in excess of
the product’s specifications.
•Do not mount in a location exposed to radiant heat that would result
in temperatures in excess of the product’s specifications.
5 Setting
5.1 Switch setting
•The switches should only be set with the power supply turned OFF.
•Open the switch protection cover and set the switches with a small
flat blade screwdriver.
•Be sure to set the switches before use.
•After setting the switches close the protective cover and tighten the
screws with the specified tightening torque of 0.6 N•m.
•The node address can be set in the range 0 – 125.
•The number of available nodes is up to 32 stations per branch, or 126
stations with a repeater.
•Bus terminator switch (SW4)
Set the switch to select the bus terminator.
5.2 Configuration
An applicable GSD file is required to configure the Gateway unit for the
PROFIBUS-DP network. Download the latest GSD file from the SMC
website (URL: https://www.smcworld.com).
Product number
GSD files
56-EX500-GPR1A
Smc_1405.gsd
Technical documentation giving detailed configuration information can
be found on the SMC website (URL: https://www.smcworld.com).
ORIGINAL INSTRUCTIONS
Item Specifications
Power supply for control and
input
24.0 VDC ±10%, 3.0 A
Power supply for solenoid
valves
24.0 VDC +10%/-5%, 3.0 A
Current consumption
Input device and SI unit control: 2.8 A
Gateway internal circuit: 0.2 A
No. of Inputs / Outputs 32 Inputs / 64 Outputs
Communication specifications
Item
Specifications
Protocol
PROFIBUS-DP (EN 50170)
Device type
Slave
Communication speed
9.6 / 19.2 / 45.45 / 93.75 / 187.5 / 500 kbps
1.5 / 3.0 / 6.0 / 12 Mbps
Occupied area
64 inputs / 64 outputs max.
Configuration file
GSD file
ID number
1405h (Hex)
Low level bus specifications
Item
Specifications
No. of branches for inputs
4 branches for input (8 per branch)
No. of branches for outputs
4 branches for output (16 per branch)
Communication method
Dedicated protocol for SMC, 750 kbps
Branch current for inputs
0.7 A max. per branch
Branch current for outputs
0.65 A max. per branch (for EX500-S#01)
0.75 A max. per branch (for EX500-Q#01)
Branch cable length
5 m max. per branch (10 m total max.)
M12 5-pin Socket (A-coded)
Connector
Pin No.
Signal name
1
0 V (solenoid valves)
2
24 V (solenoid valves)
3
0 V (control and input)
4
24 V (control and input)
5
FE
•Address setting
SW3 (x100)
SW2
SW1
Node Address
1
2
x10
x1
N.C.
0
0
0
0 (default)
0
1
1
0
2
2
:
:
:
9
8
98
9
9
99
1
0
0
100
0
1
101
:
:
:
2
5
125
56-EX500-TF2Z330EN
Page 2 of 2
6 LED Display
7 Outline Dimensions (mm)
Refer to the operation manual on the SMC website (URL:
https://www.smcworld.com) for outline dimensions.
8 How to Order
Refer to the operation manual on the SMC website (URL:
https://www.smcworld.com) for How to order information.
9 Maintenance
9.1 General Maintenance Caution
•Not following proper maintenance procedures could cause the
product to malfunction and lead to equipment damage.
•If handled improperly, compressed air can be dangerous.
•Maintenance of pneumatic systems should be performed only by
qualified personnel.
•Before performing maintenance, turn off the power supply and be
sure to cut off the supply pressure. Confirm that the air is released to
atmosphere.
•After installation and maintenance, apply operating pressure and
power to the equipment and perform appropriate functional and
leakage tests to make sure the equipment is installed correctly.
•If any electrical connections are disturbed during maintenance,
ensure they are reconnected correctly and safety checks are carried
out as required to ensure continued compliance with applicable
national regulations.
•Do not make any modification to the product.
•Do not disassemble the product, unless required by installation or
maintenance instructions
•Stop operation if the product does not function correctly.
10 Limitations of Use
10.1 Limited warranty and Disclaimer/Compliance Requirements
Refer to Handling Precautions for SMC Products.
11 Product Disposal
This product shall not be disposed of as municipal waste. Check your
local regulations and guidelines to dispose of this product correctly, in
order to reduce the impact on human health and the environment.
12 Contacts
Refer to www.smcworld.com or www.smc.eu for your local distributor /
importer.
URL: https://www.smcworld.com (Global) https://www.smc.eu (Europe)
SMC Corporation, 4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021, Japan
Specifications are subject to change without prior notice from the manufacturer.
© 2021 SMC Corporation All Rights Reserved.
Template DKP50047-F-085M
•Gateway unit status
LED Description
RUN
Green ON
Power for control and input is ON.
OFF
Power for control and input is not supplied.
SOL
Green ON
Power for SI units (solenoid valves) is ON.
OFF
Power is not supplied to SI units (solenoid
valves), or voltage < 20 V.
BF
Red ON
PROFIBUS-DP communication is abnormal.
OFF
PROFIBUS-DP communication is normal.
DIA
Red ON
DIA is abnormal.
OFF
DIA is normal.
COM A
Green ON
COM A is receiving data.
OFF
COM A is not receiving data.
COM B
Green ON
COM B is receiving data.
OFF
COM B is not receiving data.
COM C
Green ON
COM C is receiving data.
OFF
COM C is not receiving data.
COM D
Green ON
COM D is receiving data.
OFF
COM D is not receiving data.

Other SMC Networks Gateway manuals

SMC Networks SMCWTVG User manual

SMC Networks

SMC Networks SMCWTVG User manual

SMC Networks FieldServer FS-QS-2X10 User guide

SMC Networks

SMC Networks FieldServer FS-QS-2X10 User guide

SMC Networks LEC-GEN1 User manual

SMC Networks

SMC Networks LEC-GEN1 User manual

SMC Networks SMCD3USG User manual

SMC Networks

SMC Networks SMCD3USG User manual

SMC Networks EliteConnect SMCWHSG14-G User manual

SMC Networks

SMC Networks EliteConnect SMCWHSG14-G User manual

SMC Networks SMC8004CM User manual

SMC Networks

SMC Networks SMC8004CM User manual

SMC Networks EtherNet/IP EX500-GEN1 User manual

SMC Networks

SMC Networks EtherNet/IP EX500-GEN1 User manual

SMC Networks EX500-GPR1A-X20 Series User manual

SMC Networks

SMC Networks EX500-GPR1A-X20 Series User manual

SMC Networks BARRICADE SMC7901WBRA2 B1 User manual

SMC Networks

SMC Networks BARRICADE SMC7901WBRA2 B1 User manual

SMC Networks EZ Connect 2.4GHz 54Mbps Wireless Cable Modem Gateway... User manual

SMC Networks

SMC Networks EZ Connect 2.4GHz 54Mbps Wireless Cable Modem Gateway... User manual

SMC Networks LEC-GDN1 Series User manual

SMC Networks

SMC Networks LEC-GDN1 Series User manual

SMC Networks ProtoAir FPA-W34 User guide

SMC Networks

SMC Networks ProtoAir FPA-W34 User guide

SMC Networks SMCD3GN2 User manual

SMC Networks

SMC Networks SMCD3GN2 User manual

SMC Networks EX500-GPR1A User manual

SMC Networks

SMC Networks EX500-GPR1A User manual

SMC Networks EtherNet/IP EX500-GEN1 User manual

SMC Networks

SMC Networks EtherNet/IP EX500-GEN1 User manual

SMC Networks EliteConnect SMCWHSG14-G User manual

SMC Networks

SMC Networks EliteConnect SMCWHSG14-G User manual

SMC Networks SMC8014WN Use and care manual

SMC Networks

SMC Networks SMC8014WN Use and care manual

SMC Networks ProtoAir FPA-W44 User guide

SMC Networks

SMC Networks ProtoAir FPA-W44 User guide

SMC Networks EZ Networking SMC8013WG User manual

SMC Networks

SMC Networks EZ Networking SMC8013WG User manual

SMC Networks SMCD3GNV User manual

SMC Networks

SMC Networks SMCD3GNV User manual

SMC Networks EZ Connect SMC8014WG-SI User manual

SMC Networks

SMC Networks EZ Connect SMC8014WG-SI User manual

SMC Networks SMCD3GN User manual

SMC Networks

SMC Networks SMCD3GN User manual

SMC Networks EX500-GEN2 Series User manual

SMC Networks

SMC Networks EX500-GEN2 Series User manual

SMC Networks FieldServer QuickServer FS-QS-12 0 Series User guide

SMC Networks

SMC Networks FieldServer QuickServer FS-QS-12 0 Series User guide

Popular Gateway manuals by other brands

Softing echocollect How-to

Softing

Softing echocollect How-to

Sub-1GHz P-900 Operation manual

Sub-1GHz

Sub-1GHz P-900 Operation manual

ICP DAS USA GRP-530M user manual

ICP DAS USA

ICP DAS USA GRP-530M user manual

Sollae SIG-5441 user manual

Sollae

Sollae SIG-5441 user manual

Advantech Vlinx BB-MESR90 Series user manual

Advantech

Advantech Vlinx BB-MESR90 Series user manual

ZyXEL Communications P-2302HW-P1 Series quick start guide

ZyXEL Communications

ZyXEL Communications P-2302HW-P1 Series quick start guide

SST Automation GT200-HT-EI user manual

SST Automation

SST Automation GT200-HT-EI user manual

Samsara CBL-AG-BPWR install guide

Samsara

Samsara CBL-AG-BPWR install guide

Gree GRJW05-J owner's manual

Gree

Gree GRJW05-J owner's manual

Arris Touchstone DG3260 user guide

Arris

Arris Touchstone DG3260 user guide

AudioCodes Gateway & Session Border Controller Series Hardware installation manual

AudioCodes

AudioCodes Gateway & Session Border Controller Series Hardware installation manual

Billion BiGuard S100N quick start guide

Billion

Billion BiGuard S100N quick start guide

Lantronix EDS-MD Series Command reference

Lantronix

Lantronix EDS-MD Series Command reference

THOMSON SpeedTouch 510 Setup and user guide

THOMSON

THOMSON SpeedTouch 510 Setup and user guide

AVT Yeastar TG100 quick guide

AVT

AVT Yeastar TG100 quick guide

Endress+Hauser Fieldgate FXA520 operating instructions

Endress+Hauser

Endress+Hauser Fieldgate FXA520 operating instructions

Intergas LAN2RF installation manual

Intergas

Intergas LAN2RF installation manual

Valcom IP Solutions PagePro VIP-204 user guide

Valcom

Valcom IP Solutions PagePro VIP-204 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.