Stanley Magic-Swing HDLE User manual

Stanley Access Technologies
Quick-Reference Guide
Magic-Swing
and Magic-Force
HDLE/FE
Microprocessor Control Box
Quick-Reference Guide
203959
Rev. F, 10/2/02
Prohibition on Copying
Any unauthorized reproduction, disclosure or distribution of copies by any person of any
portion of this work may be a violation of copyright law of the United States of America
and other countries, could result in the awarding of statutory damages of up to $250,000
(17 USC 504) for infringement, and may result in further civil and criminal penalties. All
rights reserved.

© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED. 203959
Rev. F, 10/2/02
1 of 23
Stanley Access Technologies
Quick-Reference Guide TABLE OF CONTENTS
1. PURPOSE ....................................................................................................................................................2
1.1 Discussion................................................................................................................................................2
1.2 Applicability ............................................................................................................................................2
1.3 Features and Functions ............................................................................................................................2
2. PRECAUTIONS ..........................................................................................................................................4
3. WIRING INSTRUCTIONS.........................................................................................................................4
3.1 Evaluating Power Requirements..............................................................................................................4
3.2 Connecting Main Power Wiring..............................................................................................................4
3.3 Connecting Breakout Status Signal Wiring (Magic-Swing Operators)...................................................5
3.4 Connecting Breakout Status Signal Wiring (Magic-Force Operators)....................................................7
3.5 Wiring the Operator Switch Module (Magic-Force Operators)...............................................................9
3.6 Wiring the Operator for Required Handing (Magic-Force Operators)..................................................10
3.7 Wiring the “ON/OFF/HOLD OPEN” Switch........................................................................................10
3.8 Wiring the Door Activation or Safety Device .......................................................................................11
3.9 Wiring Sentrex3......................................................................................................................................11
3.10 Wiring the Counter ................................................................................................................................11
4. TUNE-IN INSTRUCTIONS......................................................................................................................11
4.1 Initial Tune-In Settings..........................................................................................................................11
4.2 Final Tune-In Adjustments....................................................................................................................12
ATTACHMENTS
Attachment 1, Breakout Status Wiring...............................................................................................................14
Attachment 2, Magic-Force Operator Wiring—Dual Operators with Dual-Adjustment Closing Speed
Controls and Switch Modules........................................................................................................................15
Attachment 3, Magic-Force Operator Wiring—Dual Operators with Dual-Adjustment Closing Speed
Controls, Power Close Modules, and Switch Modules..................................................................................16
Attachment 4, Magic-Swing System Wiring—Main Power, Motor(s), and Encoder(s)....................................17
Attachment 5, Signal Wiring— HDLE/FE Control Box with Carpets, Pushplate, Operate Sensor,
or Safety Sensor ..............................................................................................................................................18
Attachment 6, Wiring Diagram— HDLE/FE Control Box with Bifold Doors ..................................................19
Attachment 7, Wiring Diagram—HDLE/FE Control Box with Sentrex3..........................................................20
Attachment 8, DIP Switch S2 Mode Settings.....................................................................................................21
Attachment 9, HDLE/FE Control Box................................................................................................................23

© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED. 203959
Rev. F, 10/2/02
2 of 23
1. PURPOSE
1.1 Discussion
This manual provides abbreviated descriptive information, wiring instructions, and tune-in
instructions for the microprocessor control box used with Magic-Swingand Magic-Force
operators. The manual is intended as a quick-reference guide.
1.2 Applicability
Two configurations of the microprocessor control box are currently in use, each with a distinct
decal on the control box cover. The newer (HDLE/FE) configuration is identified by a decal
with yellow text on a black background. The common name for this configuration is the black-
label box. The early model configuration is identified by a decal with black text on a yellow
background. The common name for this configuration is the yellow-label box. Black-label
control boxes can replace yellow-label boxes, but yellow-label boxes cannot replace black-label
boxes. This manual covers operation of HDLE/FE (black-label) control boxes only. For yellow-
label control box operating instructions, refer to Stanley Access Technologies document No.
203821, "Magic-SwingMicroprocessor Control Box."
Attachment 9 provides an overview of the HDLE/FE control box. Additional differences
between the yellow-label and black-label boxes include the following:
•The power switch has been deleted.
•A torque potentiometer has been added to accommodate adjusting from low to full
energy.
•A separate Magic-Touchtime delay rotary switch has been added. The time
delay settings are 2 to 20 seconds or 5 to 20 seconds, depending on the version of
the microprocessor installed.
•A Magic-Touch sensitivity adjustment has been added.
•Control box dual in-line package (DIP) switch configurations have changed. On
yellow-label control boxes, DIP switch S2 is a four-bank switch and DIP switch
S3 is a two-bank switch. On black-label control boxes, DIP switch S3 has been
eliminated and DIP switch S2 has been replaced with a larger seven-bank switch.
DIP switch S2 now also controls the features previously controlled by S3. On
black-label control boxes, rotary switch S4 has been added to control the Magic-
Touch time delay.
•A counter activation signal has been provided.
1.3 Features and Functions
1.3.1 Magic-Touch:A feature that allows the door to be actuated by a slight manual
movement of the door--without the need for an approach sensor. The microprocessor
control box provides a rotary switch that controls the Magic-Touch hold-open time
delay. The switch settings vary according to the version of microprocessor installed.
(The version is printed on the microprocessor.) Attachment 9 describes the hold-open
time delays for the two microprocessor versions. Magic-Touch can be used with press
plates or a radio control system, providing the system with two separate time delays.
Magic-Touch is not recommended for use with a dual door system using Sentrex.

© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED. 203959
Rev. F, 10/2/02
3 of 23
1.3.2 Learn Speed: When power is first turned on and an "open" signal is applied, the control
box opens the door in "learn speed," a slightly faster speed than open check. The
controller counts encoder pulses, learning the operator rotation from closed to open.
The calculated learn value is lost whenever power is lost.
1.3.3 Reverse On Obstruction: A one-second reverse-on-obstruction feature causes the door
to reverse motion if an obstruction is met during door opening or closing.
1.3.4 Safety Check: This feature monitors the safety signal activation on every open cycle. If
a safety carpet or overhead safety sensor fails "open" and can no longer detect a
pedestrian, the door stays open for 12 seconds to indicate that there is a problem.
1.3.5 Emergency Breakout: Disconnects power to the motor when the door is manually
pushed in the emergency-out direction. The operator then automatically resets and
power is resumed.
1.3.6 2S Logic: Used in trained-traffic applications and is not compatible with sensors.
Allows door to open when switch is pushed and door to close when next sequential
switch is pushed.
1.3.7 Automatic Open Check Calculation: Open check position—the area where the door
slows down before fully open—is calculated for approximately 80°in the opening
direction during "learn cycle."
1.3.8 Low- and High-Energy Operation: Allows selection of low-speed range (low-energy
applications) or high-speed range (full-energy and all dual-operator applications).
1.3.9 Bifold Safety Sensor Logic: Allows manual selection of bifold logic versus carpet or
timer logic via DIP switch. Used in bifold door systems, it eliminates the need for a
lockout relay for the overhead safety sensor.
1.3.10 Single- or Dual-Door Selection: Allows manual selection of single- or dual-door
operation via DIP switch.
1.3.11 Opening Speed Adjustment: Opening speed potentiometer permits adjustment of door
opening speed.
1.3.12 Closing Speed Adjustment: On Magic-Force operators, a dual-adjustment closing speed
control with two rheostats permits independent adjustment of door closing speed and
closing check speed. On Magic-Swing operators, provisions are provided for the
installation of an optional single-adjustment closing speed control.
1.3.13 Open Check Speed Adjustment: Open check speed potentiometer permits adjustment of
door open check speed.
1.3.14 Torque Adjustment: Allows adjustment of the door opening force.
1.3.15 Stall Logic: Used with a door-mounted sensor system to stop door motion when a
pedestrian or object is present.
1.3.16 One-Piece Switch Module: On Magic-Force operators, the individual breakout,
breakout status, close check, and auxiliary switches have been replaced with a single
one-piece switch module.

© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED. 203959
Rev. F, 10/2/02
4 of 23
2. PRECAUTIONS
2.1 If the Magic-Touch time delay is set to 2 seconds, a safety sensor must be installed to ensure
compliance with ANSI A156.19, “American National Standard for Power Assist and Low Energy
Power Operated Doors,” specifications.
3. WIRING INSTRUCTIONS
3.1 Evaluating Power Requirements
3.1.1 EVALUATE door system power requirements as follows:
•ENSURE power source is a dedicated 117 VAC, 50/60 Hz source with 20A
circuit rating per two-door system.
•ENSURE power source is not shared with other equipment, i.e., cash registers,
EAS systems, or other electromagnetic interference generators.
3.2 Connecting Main Power Wiring
WARNING
To prevent injury to personnel, incoming electrical power to header must be deenergized before
connecting control box electrical harness to electrical service.
3.2.1 DEENERGIZE incoming electrical power to header.
3.2.2 Refer to Attachment 4, and, using the wire nut provided, CONNECT ground wire
assembly (P/N 711527) to electrical service ground wire.
3.2.3 In a concealed location inside the header (not visible from the exterior of the header),
DRILL a hole for a No. 8 screw.
3.2.4 INSTALL ground wire ring terminal and star washer onto the No. 8 screw provided,
and FASTEN screw, star washer, and ground wire to header.
3.2.5 In a concealed location inside the header, DRILL a second hole for a No. 8 screw.
3.2.6 INSTALL main harness (J1) ring terminal and star washer onto the No. 8 screw
provided, and FASTEN screw, star washer, and ground wire to header.
3.2.7 Using the wire nuts provided, CONNECT power pigtail assembly (712846) to electrical
service as follows:
•CONNECT power pigtail assembly black wire to black (line) service wire.
•CONNECT power pigtail assembly white wire to white (neutral) service wire.
3.2.8 ENSURE power pigtail assembly is not connected to main harness connector J1.

© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED. 203959
Rev. F, 10/2/02
5 of 23
3.3 Connecting Breakout Status Signal Wiring (Magic-Swing Operators)
WARNING
To prevent injury to personnel and damage to equipment, control box power must be deenergized before
connecting breakout status signal wiring.
CAUTION
If the motor is running and the breakout status switch is not connected, arcing across the breakout switch
contacts can occur. This will result in damage to the breakout switch. To prevent damage from switch
contact arcing, the breakout status switch must always be connected.
3.3.1 DISCONNECT power pigtail assembly.
NOTE
1. The breakout status switch should be used in all applications where there is no positive door stop in
the breakout direction.
2. The auxiliary switch is the breakout status signal switch. The auxiliary switch was formerly the open
check switch on the operator switch plate (top cam).
3.3.2 Refer to Attachment 1, and CONNECT breakout status wiring.
3.3.3 REMOVE quick-connect terminal (brown wire) from the normally open terminal of the
auxiliary switch (formerly open check switch), and INSTALL onto normally closed
terminal.
3.3.4 CONNECT yellow jumper wires installed on the single/dual motor harness as follows:
a. REMOVE control box jumper wire from terminals 6 and 8.
b. INSTALL stripped end of first jumper wire (from position 3 of the 8-pin connector
on operator harness) into terminal 6 of control box connector TB1.
c. INSTALL stripped end of second jumper wire (from position 5 of the 8-pin
connector on operator harness) into terminal 8 of control box connector TB1.
3.3.5 SET the auxiliary cam for approximately 3°activation (toward breakout direction), and
ADJUST cam as necessary to trip the corresponding microswitch prior to activation of
the breakout switch.
NOTE
In a dual-door application, the breakout switches of each operator need to be wired in series to ensure that
the control box will not open the doors if either breakout status switch is activated.
3.3.6 IF application is a pair of doors, PERFORM the following:
a. REPEAT steps 3.3.4 and 3.3.5 for the second door operator.
b. CONNECT stripped end of one yellow jumper wire from each operator across
terminals 6 and 8 of control box connector TB1.
3.3.7 Using a wire nut, CONNECT remaining wire from first operator to remaining wire on
second operator.
3.3.8 VERIFY breakout status/breakout cam is properly set as follows:

© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED. 203959
Rev. F, 10/2/02
6 of 23
a. Refer to Figure 1, and visually INSPECT cams for proper setting.
b. UNPLUG TB1 from control box circuit board.
NOTE
When checking breakout status switch continuity, the switch is first checked with the door closed, then
again with the door in the breakout (negative 3°) position. In a dual-door application, both doors can be
tested at the same time in the closed position. However, the doors must be tested individually when
checking switch continuity with the doors in the breakout (negative 3°) position.
c. ENSURE door is in the closed position.
d. Using a multimeter, CHECK continuity between TB1 terminals 6 and 8, and
ENSURE there is continuity.
e. PUSH door in the breakout direction, and HOLD door at approximately the negative
3°position.
f. Using a multimeter, CHECK continuity between TB1 terminals 6 and 8, and
ENSURE there is an open circuit.
g. RELEASE door.
h. PLUG TB1 into control box circuit board.
Figure 1. Breakout Status/Breakout Cam Settings (Magic-Swing Operators)
EMERGENCY SWITCH
N.C.: RED
N.O.: YELLOW
COM.: BLACK
N. C.
N.O.
COM.
mcb002
OPEN CHECK SWITCH
N.O.: BROWN
COM.: ORANGE
CLOSE CHECK SWITCH
N.C.: WHITE
COM.: BLUE
COM
N.O.
N.C.
COM
N.O.
N.C.
N. C.
N.O.
COM.
TOP CAM = AUX SWITCH
CENTER CAM = EMERGENCY BREAKOUT SWITCH
BOTTOM CAM = CLOSE CHECK SWITCH
R. H. SHOWN L. H. SHOWN
TOP CAM = AUX SWITCH
CENTER CAM = EMERGENCY BREAKOUT SWITCH
BOTTOM CAM = CLOSE CHECK SWITCH

© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED. 203959
Rev. F, 10/2/02
7 of 23
3.4 Connecting Breakout Status Signal Wiring (Magic-Force Operators)
WARNING
To prevent injury to personnel and damage to equipment, control box power must be deenergized before
connecting breakout status signal wiring.
CAUTION
If the motor is running and the breakout status switch is not connected, arcing across the breakout switch
contacts can occur. This will result in damage to the breakout switch. To prevent damage from switch
contact arcing, the breakout status switch must always be connected.
3.4.1 DISCONNECT power pigtail assembly.
3.4.2 IF single-operator application, PERFORM the following:
•INSTALL one breakout status switch wire (yellow) to terminal 6 of control box
connector TB1.
•INSTALL second breakout status switch wire (yellow) to terminal 8 of control
box connector TB1.
3.4.3 IF dual-operator application, PERFORM the following:
•INSTALL one breakout status switch wire (yellow) from one operator to terminal
6 of control box connector TB1.
•INSTALL one breakout status switch wire (yellow) from second operator to
terminal 8 of control box connector TB1.
•CONNECT remaining two yellow breakout status switch wires together with a
wire nut.
3.4.4 VERIFY breakout status/breakout cams are properly set as follows:

© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED. 203959
Rev. F, 10/2/02
8 of 23
a. Refer to Figure 2, and visually INSPECT cams for proper setting.
Figure 2. Breakout Status/Breakout Cam Settings (Magic-Force Operators)
BREAKOUT CAM
BREAKOUT STATUS CAM
CLOSE CHECK CAM
AUXILIARY CAM
INCREASE
BREAKOUT
ANGLE
DECREASE
BREAKOUT
ANGLE
CAM ROTATION
INCREASE
CLOSE CHECK
ANGLE
DECREASE
CLOSE CHECK
ANGLE
CAM ROTATION
MF0026
SEE DETAIL A
DETAIL A: RIGHT HAND OPERATOR
CAM SETTINGS
AUXILIARY CAM
CLOSE CHECK CAM
DECREASE
CLOSE CHECK
ANGLE
INCREASE
CLOSE CHECK
ANGLE CAM ROTATION
BREAKOUT STATUS CAM
BREAKOUT CAM
DECREASE
BREAKOUT
ANGLE
INCREASE
BREAKOUT
ANGLE
CAM ROTATION
SEE DETAIL B
DETAIL B: LEFT HAND OPERATOR
CAM SETTINGS
INITIAL CAM SETTINGS (LOOKING DOWN AT OPERATOR SPINDLE)
ROTATE BREAKOUT CAMS COUNTERCLOCKWISE UNTIL RAISED PORTION OF
BREAKOUT STATUS CAM JUST CONTACTS SWITCH ROLLER.
ROTATE CLOSE CHECK CAM CLOCKWISE UNTIL RAISED PORTION OF CAM
ACTUATES SWITCH, THEN ROTATE CAM 10 DEGREES COUNTERCLOCKWISE.
ROTATE AUXILIARY CAM AS DESIRED.
INITIAL CAM SETTINGS (LOOKING DOWN AT OPERATOR SPINDLE)
ROTATE BREAKOUT CAMS CLOCKWISE UNTIL RAISED PORTION OF
BREAKOUT STATUS CAM JUST CONTACTS SWITCH ROLLER.
ROTATE CLOSE CHECK CAM COUNTERCLOCKWISE UNTIL RAISED PORTION OF CAM
ACTUATES SWITCH, THEN ROTATE CAM 10 DEGREES CLOCKWISE.
ROTATE AUXILIARY CAM AS DESIRED.
LEFT HAND OPERATOR
RIGHT HAND OPERATOR

© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED. 203959
Rev. F, 10/2/02
9 of 23
b. UNPLUG TB1 from control box circuit board.
NOTE
When checking breakout status switch continuity, the switch is checked twice; first with the door closed,
then with the door in the breakout (negative 3°) position. In a dual-door application, both doors can be
tested at the same time in the closed position. However, the doors must be tested individually when
checking switch continuity with the doors in the breakout (negative 3°) position.
c. ENSURE door is in the closed position.
d. Using a multimeter, CHECK continuity between TB1 terminals 6 and 8, and
ENSURE there is continuity.
e. PUSH door in the breakout direction, and HOLD door at approximately the negative
3°position.
f. Using a multimeter, CHECK continuity between TB1 terminals 6 and 8, and
ENSURE there is an open circuit.
g. RELEASE door.
h. PLUG TB1 into control box circuit board.
3.5 Wiring the Operator Switch Module (Magic-Force Operators)
3.5.1 Refer to Attachment 2 or 3 as applicable, and CONNECT switch module harness
413791 to dual-adjustment closing speed control connector J4.
3.5.2 IF auxiliary position switch will be used, refer to Figure 3, and PERFORM the
following:
a. LIFT switch module release lever up, and SLIDE switch module out of operator
housing.
b. CONNECT wiring to auxiliary position switch terminal block as shown.
c. SLIDE switch module into operator housing until switch module release lever snaps
into place.
Figure 3. Wiring the Auxiliary Position Switch (Magic-Force Operators)
SWITCH MODULE
MCB006
SWITCH MODULE RELEASE LEVER
(PRESS LEVER UP TO RELEASE SWITCH MODULE)
AUXILIARY POSITION SWITCH
TERMINAL BLOCK
NORMALLY CLOSED CONTACT
COMMON
NORMALLY OPEN CONTACT
OPERATOR HOUSING

© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED. 203959
Rev. F, 10/2/02
10 of 23
3.6 Wiring the Operator for Required Handing (Magic-Force Operators)
NOTE
Operator cams are factory-set for right hand operation.
3.6.1 Refer to Figure 4, and DETERMINE door handing.
3.6.2 CONFIGURE encoder for left or right hand operation as follows:
NOTE
There are two configurations of encoder wiring. Early model operators use a single encoder handing
harness, P/N 413767. Later model operators use a single-circuit connector in line with green and white
encoder wires.
a. IF operator must be configured for left hand operation, refer to Attachment 2 or 3 as
applicable, and PERFORM one of the following:
•IF operator is an early model configuration, INSTALL encoder handing
harness (part No. 413767), and CONNECT motor harness to dual-adjustment
closing speed control connector J1.
•IF operator is a later model configuration, CONNECT the white encoder
wire to the green encoder wire, the green encoder wire to the white encoder
wire, and CONNECT the motor harness to dual-adjustment closing speed
control connector J1.
b. IF operator must be configured for right hand operation, refer to Attachment 2 or 3
as applicable, and CONNECT motor harness into dual-adjustment closing speed
control connector J2.
3.7 Wiring the “ON/OFF/HOLD OPEN” Switch
3.7.1 Refer to Attachment 5, and CONNECT “ON/OFF/HOLD OPEN” switch wiring as
follows:
TB1 Terminal Connection Switch Wire Color
1 Common Yellow
2 Operate Orange
3 Sensors Violet
Figure 4. Door Handing
LEFT HAND RIGHT HAND
DOOR
OPENING
MOTION
MCB004

© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED. 203959
Rev. F, 10/2/02
11 of 23
3.8 Wiring the Door Activation or Safety Device
NOTE
Attachments 5 and 6 illustrate typical wiring for various devices. Though the specific device may not be
shown, this attachment can be used as a general guide. Specific wiring instructions from the manufacturer
must also be consulted.
3.8.1 Refer to Attachments 5 and 6 and applicable manufacturer's instructions, and
CONNECT door activation or safety device.
3.9 Wiring Sentrex3
3.9.1 Refer to Attachment 7, and CONNECT Sentrex3as follows:
TB2 Terminal Connection Sentrex3 Wire Color
1 VSX (+) Power for Sensor Head Red
2 Serial Communication Green
3 Serial Communication White
4 GND (-) Ground for Sensor Head Black
3.10 Wiring the Counter
3.10.1 Refer to Figure 5, and CONNECT wiring for counter.
4. TUNE-IN INSTRUCTIONS
4.1 Initial Tune-In Settings
4.1.1 DISCONNECT power pigtail assembly.
Figure 5. Counter Wiring
CNT
2
3
RED
BLACK
COUNTER
1
2
3
4
S/D TB3
MCB005

© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED. 203959
Rev. F, 10/2/02
12 of 23
WARNING
To prevent injury to personnel and damage to equipment, the following settings must be made before
applying power to control box.
4.1.2 SET potentiometers and switches to initial positions as follows:
a. SET stall speed potentiometer to full clockwise (maximum) position.
b. SET torque potentiometer to full clockwise (maximum) position.
c. SET high/low range DIP switch S1 as applicable:
WARNING
When changing from low range to high range, the door will move faster.
CAUTION
To ensure proper operation of door, DIP switch S1 must be set to "H" (high range) on all full-energy, dual
operator, Magic-Swing and bifold applications.
•IF single-operator full-energy application, dual-operator application, Magic-
Swing application, or bifold application, SET to "H" (high range).
•IF single-operator low-energy application, SET to "L" (low range).
d. SET open speed potentiometer as applicable:
•IF high/low range DIP switch S1 is set to ON (high-speed range), SET open
speed potentiometer to midrange position.
•IF high/low range DIP switch S1 is set to “OFF” (low-speed range), SET
open speed potentiometer to maximum (full clockwise) position.
e. SET open check speed potentiometer to 3/4of full clockwise position.
f. SET time delay potentiometer to full counterclockwise (minimum) position.
g. SET Magic-Touchtime delay rotary switch S4 to 0 (5 seconds).
h. SET "CLS" (close speed) rheostat to midrange position.
i. IF application is a Magic-Force installation, SET “CK” (close check speed) rheostat
to full counterclockwise position.
4.1.3 Refer to Attachment 8, and PERFORM tune-in as applicable.
4.2 Final Tune-In Adjustments
4.2.1 ENSURE door-opening path is clear of all wires and obstructions.
4.2.2 SET “ON/OFF/HOLD OPEN” switch to “OFF.”
4.2.3 CONNECT power pigtail assembly.
4.2.4 Refer to ANSI A156.10, "American National Standard for Power Operated Doors" or
ANSI 156.19, “American National Standard for Power Assist and Low Energy Power
Operated Doors,” and DETERMINE ANSI door operating requirements.
4.2.5 CYCLE and RECYCLE door several times to verify proper speeds and forces, and
PERFORM adjustments in the following order:
a. ADJUST close check cam.
b. ADJUST open speed potentiometer.

© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED. 203959
Rev. F, 10/2/02
13 of 23
c. ADJUST open check speed potentiometer.
d. ADJUST "CLS" (close speed) rheostat.
e. ADJUST "CK" (close check speed) rheostat.
NOTE
Adjustments to the “CK” (close check) rheostat also affect closing speed. Closing speed must always be
checked after adjusting close check speed.
f. ADJUST "CLS" (close speed) rheostat.
CAUTION
To prevent motor overheating and premature motor failure, stall speed potentiometer must not be set too
high.
g. ADJUST stall speed potentiometer.
h. ADJUST torque potentiometer.
i. ADJUST time delay potentiometer.
WARNING
If the Magic-Touch time delay is set to 2 seconds, a safety sensor must be installed to ensure compliance
with ANSI A156.19, “American National Standard for Power Assist and Low Energy Power Operated
Doors,” specifications.
j. ADJUST Magic-Touchtime delay rotary switch. IF the Magic-Touch time delay
is set to 2 seconds, INSTALL and ADJUST safety sensor.
k. ADJUST breakout and breakout status cams.

203959
Rev. F, 10/2/02
Page 14 of 23
© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED.
Attachment 1
Breakout Status Wiring
(Sheet 1 of 1)
1
2
3
4
5
6
7
8
COMMON
OPERATE
SENSOR OPERATE
12 VAC
FOR SENSOR
AUX INPUT
SAFETY/STALL
SENSOR COMMON
N.C.
RED
GREEN
WHITE
1
2
3
4
5
6
7
8
WIRE HARNESS (CONNECTOR
SEEN FROM WIRES SIDE)
TWO-WIRE HARNESS TERMINATED BY TWO
COMM. MATE-N-LOCK RECEPTACLE CONTACTS
COM. N.O.
TB1
AUX. SWITCH
1
2
3
4
5
6
7
8
COMMON
OPERATE
SENSOR OPERATE
12 VAC
FOR SENSOR
AUX INPUT
SAFETY/STALL
SENSOR COMMON
N.C.
COM. N.O.
TB1
AUX. SWITCH
BREAKOUT STATUS WIRING--SINGLE DOOR BREAKOUT STATUS WIRING--DUAL DOOR
N.C.
COM. N.O.
AUX. SWITCH
OPERATOR NO. 1
OPERATOR NO. 2
3
5
5
3
MCBA017
NOTE:
REMOVE CONTROL BOX JUMPER WIRE
FROM TERMINALS 6 AND 8.

203959
Rev. F, 10/2/02
Page 15 of 23
© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED.
Attachment 2
Magic-Force Operator Wiring—Dual Operators with Dual-Adjustment Closing Speed Controls and Switch Modules
(Sheet 1 of 1)
LEFT HAND OPERATOR
S/D
CNT
4 AMP FUSE
RIGHT HAND OPERATOR
OPERATOR HARNESS
BREAKOUT
BREAKOUT
BREAKOUT STATUS
BREAKOUT STATUS
CLOSE CHECK
CLOSE CHECK
AUXILIARY
AUXILIARY
BREAKOUT STATUS
WIRE NUT
SINGLE P/N 515735
DUAL P/N 515736
2
3
RED
HDLE/FE CONTROL BOX
BLACK
P/N 110277
1234567
CLOSING SPEED CONTROL HARNESS P/N 413791
CLOSING SPEED CONTROL HARNESS P/N 413791
ENCODER
ENCODER
MOTOR
MOTOR
COUNTER P/N 413787
ENCODER
#1
TB3
LED4LED5LED2LED3 LED1
1
TB1
1
J1
1
RN3
TB2
1
2
3
4
5
6
7
8
1
2
3
4
E1
E2
WD
M/SWING
SENTREX 3
GRN
WHT
BLK
1
2
3
4
redN
MCBA20
J1
J4
J2
J3
J1
J4
J2
J3
DUAL-ADJUSTMENT CLOSING
SPEED CONTROL P/N 516660
DUAL-ADJUSTMENT CLOSING
SPEED CONTROL P/N 516660
S2
S4
S1
S3
BO
BOS
AUX
CCK
1
S2
S4
S1
S3
BO
BOS
AUX
CCK
AUXILIARY POSITION
SWITCH TERMINAL BLOCK
SWITCH MODULE
P/N 516671
BREAKOUT STATUS
SWITCH MODULE
P/N 516671
AUXILIARY POSITION
SWITCH TERMINAL BLOCK
ENCODER
HANDING
HARNESS
P/N 413767
ENCODER
#1
DETAIL A
(SEE NOTE)
GREEN
GREEN WHITE
WHITE
SEE DETAIL A
CONFIGURATION ON EARLY
MODEL OPERATOR ASSEMBLIES.
NOTE
ENCODER
#2
GREEN
GREEN
WHITE
WHITE
SEE DETAIL B
ENCODER
#2
DETAIL B
(SEE NOTE)

203959
Rev. F, 10/2/02
Page 16 of 23
© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED.
Attachment 3
Magic-Force Operator Wiring—Dual Operators with Dual-Adjustment Closing Speed Controls,
Power-Close Modules, and Switch Modules
(Sheet 1 of 1)
POWER CLOSE MODULE P/N 516116
MCBA21
CLOSING SPEED CONTROL HARNESS
P/N 413799
1
1
1
2
3
4
5
6
7
8
1
2
3
4
E1
E2
WD
M/SWING SENTREX 3
4 AMP FUSE
1
2
3
4
RIGHT HAND OPERATOR
LEFT HAND OPERATOR
OPERATOR HARNESS
BREAKOUT
BREAKOUT
BREAKOUT STATUS
BREAKOUT STATUS
CLOSE CHECK
CLOSE CHECK
AUXILIARY
AUXILIARY
BREAKOUT STATUS
WIRE NUT
BREAKOUT STATUS
SINGLE P/N 515735
DUAL P/N 515736
POWER CLOSE MODULE P/N 516116
MOTOR
2
3
RED
HDLE/FE CONTROL BOX
BLACK
P/N 110277
1234567
COUNTER P/N 413787
CLOSING SPEED CONTROL HARNESS
P/N 413799
MOTOR
ENCODER
ENCODER
D1
D2
R1 R2
RH1 RH2
D1
D2
R1 R2
RH1 RH2
J1
J4
J2
J3
J1
J4
J2
J3
DUAL-ADJUSTMENT CLOSING
SPEED CONTROL P/N 516660
DUAL-ADJUSTMENT CLOSING
SPEED CONTROL P/N 516660
S2
S4
S1
S3
BO
BOS
AUX
CCK
S2
S4
S1
S3
BO
BOS
AUX
CCK
SWITCH MODULE P/N 516671
SWITCH MODULE
P/N 516671
AUXILIARY POSITION
SWITCH TERMINAL BLOCK
AUXILIARY POSITION
SWITCH TERMINAL BLOCK
MOTOR
HANDING
HARNESS
P/N 413768
CONFIGURATION ON EARLY MODEL
OPERATOR ASSEMBLIES.
NOTE
ENCODER
#1
GREEN
WHITE
WHITE
SEE DETAIL A
GREEN
ENCODER
#2
GREENGREEN
WHITEWHITE
SEE DETAIL B
ENCODER
#2
DETAIL B
(SEE NOTE)
ENCODER
HANDING
HARNESS
P/N 413767
ENCODER
#1
DETAIL A
(SEE NOTE)

203959
Rev. F, 10/2/02
Page 17 of 23
© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED.
Attachment 4
Magic-Swing System Wiring—Main Power, Motor(s), and Encoder(s)
(Sheet 1 of 1)
18
17
16
15
14
13
12
11
10
8
7
6
5
4
3
2
1
HARNESS CONNECTOR
CONNECT TO
MAGIC-SWING
CONTROL BOX
AT J1.
POSITION #9 -
NO CONNECTION
BLACK
WHITE
GREEN
WHITE
RED
GREEN
WHITE
RED
RED
GREEN
WHITE
BLACK
RED
GREEN
WHITE
BLACK
1
2
1
2
1
CONNECT POWER
PIGTAIL (712846)
FASTEN TO HEADER WITH
#8 SCREW (P/N 322731960)
AND #8 STARWASHER PROVIDED.
GREEN-GROUND
BLACK-HOT
WHITE-NEUTRAL
HEADER-MAIN POWER
TERMINATE GROUND
WIRE TO HEADER
117 VAC
MAIN
POWER-IN
16 7167
OPERATOR CABLE(S)
(TO OPERATOR
SWITCH PLATE)
ON SINGLE HARNESS, MOTOR &
ENCODER #2 WIRES NOT INSTALLED
ENCODER NO. 2
BLACK
GREEN
WHITE
RED ENCODER
1 GREEN
2 BLACK
3 WHITE MOTOR
MAGIC-SWING SWITCH PLATE WIRING ON OPERATOR
GROUND WIRE
PROVIDED
(P/N 711527)
GREEN
2
34
56
78
12
34
56
784321
4321
4321
ENCODER NO. 1
CR-20 CR-21
GREEN 1
BLACK 2
WHITE 3
SW-2, OPEN CHECK
(STACKED ON TOP)
NC
NO
COM
OPEN CHECK
SWITCH NOT USED
FOR MAGIC-SWING
MICROPROCESSOR
CONTROL BOX
SW-3, CLOSE CHECK
(STACKED ON BOTTOM)
NC
NO
COM
NC
NO
COM
R-50
SW-1, BREAKOUT
WHITE
BLUE
RED
YELLOW
BLACK
GREEN
ORANGE
BROWN
RED
BLUE
WHITE
BLACK
12
34
56
78
9
MCBA002
R-20 (FOR LIGHT
SPRING OPERATORS)
Motor 1
Motor 2

203959
Rev. F, 10/2/02
Page 18 of 23
© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED.
Attachment 5
Signal Wiring—HDLE/FE Control Box With Carpets, Pushplate, Operate Sensor, or Safety Sensor
(Sheet 1 of 1)
1
2
3
4
5
6
7
8
COMMON
OPERATE
SENSOR OPERATE
12 VAC
FOR SENSOR
AUX INPUT
SAFETY/STALL
SENSOR COMMON
TB1
HOLD OPEN
OFF
AUTO
YELLOW
ORANGE
VIOLET
OPERATE CARPET
OR PUSH PLATE
HDLE/FE CONTROL BOX
L1
S4
C10
1J3
P1P6P5P2
P4
1
TB1
1
T
U6
LED1
LED3LED2
LED5LED4
XTL
U2
REL
Q1
D2
1
J1
VR1
VR2
J2
S1
1
TB2
CX2
S2
1
2
3
4
5
6
7
8
1
2
3
4
E1
E2
WD
M/SWING
1
1
SENTREX 3
RED
GRN
WHT
BLK
TQ
OCK
OPEN
STALL
TIME17
ON
H
L
CONNECT YELLOW WIRES FROM PINS 3 AND 5
ON MOTOR / ENCODER HARNESS ACROSS
TB1, TERMINALS 6 AND 8. REMOVE CONTROL BOX
JUMPER WIRE FROM TERMINALS 6 AND 8.
IF DUAL OPERATORS, CONNECT YELLOW OPERATOR
WIRES IN SERIES BEFORE CONNECTING TO TERMINALS 6 AND 8.
YELLOW
YELLOW
SET DIP SWITCH S2 POSITION
1 TO ON FOR CARPET MODE.
(SEE DIP SWITCH S2 MODE
SETTINGS ATTACHMENT.)
MCBA018
SAFETY CARPET
OPERATE SENSOR
SAFETY SENSOR
F1
4 AMP FUSE
CNT
2
3
RED
BLACK
1234567
COUNTER P/N 413787
TB3
1
2
3
4
S/D

203959
Rev. F, 10/2/02
Page 19 of 23
© 2002, THE STANLEY WORKS. ALL RIGHTS RESERVED.
Attachment 6
Wiring Diagram—HDLE/FE Control Box with Bifold Doors
(Sheet 1 of 1)
WHITE
WHITE
GREEN
WHITE
RED
BLACK
GREEN
SIGNAL
POWER
SIGNAL
POWER
SIGNAL
POWER
AC
AC
AC
AC
NO
C
AC
AC
AC
AC
1
2
3
41
21
2
1
21
2
BLACK
BLACK
BLACK
INSIDE
SENSOR
SENSOR
OUTSIDE
SENSOR
BREAKOUT
SWITCHES
TB1
1
1
2
2
3
3
4
4
5
6
7
8
SEE NOTE 1
NOTES:
IF A TWO-PANEL BIFOLD IS USED, INSTALL TWO-POSITION JUMPER 713410 IN PLACE OF SECOND MAGNETIC SWITCH.
SEE NOTE 2
2. OPTIONAL CLOSING SPEED AND POWER CLOSE MODULES MAY BE ADDED BETWEEN THE MAGIC-SWING
CONTROL BOX AND THE MAGIC-SWING OPERATOR.
3. OPTIONAL ENCODER EXTENSION HARNESS, P/N 412449-1.
4. OPTIONAL MOTOR EXTENSION HARNESS, P/N 413411-1.
WHITE
GREEN
WHITE
GREEN
RED
WHITE
GREEN
COMMON
OPERATE
12VAC
12VAC
VIOLET
ORANGE
YELLOW
HARNESS, BREAKOUT
P/N 413448-1
TB2
BLACK OR BROWN
RED OR YELLOW
BLACK OR BROWN
RED OR YELLOW
SAFETY
SAFETY GRAY
GRAY
YELLOW
WHITE
5. ALL SENSOR SIGNAL OUTPUTS ARE DEFINED WITH THE POWER ON.
6. SEE ATTACHMENT 2 FOR STANDARD OPERATOR WIRING. SEE ATTACHMENT 3 FOR POWER CLOSE OPERATOR
WIRING. WIRE BREAKOUT STATUS AS SHOWN.
1. SCHEMATIC SHOWS BREAKOUT SWITCHES FOR A 4-PANEL BIFOLD.
GREEN
132
AUTO/OFF/HOLD OPEN
SWITCH
STANGUARD
SIGNAL
POWER
RED
RED
BLACK
WHITE
OPTEX OA601
TB1
TB2
HDLE/FECONTROL BOX
COMMON
BREAKOUT
120 VAC
LINE
EARTH
GROUND GROUND SCREW
IN HEADER
ON OFF
BLACK
312 POWER SWITCH
BLACK
WHITE
GREEN
HARNESS ON/OFF HOLD OPEN &
POWER P/N 413446-1
RED
WHITE 1
12
2
LINE
NEUTRAL
BLACK
MCBA011A
SEE NOTE 6
This manual suits for next models
3
Table of contents
Other Stanley Controllers manuals

Stanley
Stanley MC521 Pro User manual

Stanley
Stanley EX5500 User manual

Stanley
Stanley PAC 520 User manual

Stanley
Stanley DE-MC521 User manual

Stanley
Stanley JUMPiT J309E User manual

Stanley
Stanley PSI-C Product manual

Stanley
Stanley Theta Controller User manual

Stanley
Stanley 204143 User manual

Stanley
Stanley QB Expert User manual

Stanley
Stanley JUMP iT J5C09D User manual