GB.TBLZ481.160408
Specifications are subject to alteration without notice.
Installation equipment cabinet for smoke funct. TBLZ-1-48-1
GOLD/COMPACT
www.swegon.com 1
1. General
Equipment cubicle for smoke function consists of a con-
trol unit installed in a box with transparent cover.
There are necessary terminals for external connection.
The equipment cubicle is equipped with knockout grom-
mets.
2. Range of Application
The equipment cubicle is used together with smoke detec-
tors TBLZ-2-49-a. In the event of an error indication the
unit is designed to control dampers and stop the unit and
give an alarm. Connected damper actuators must be suit-
able for a 230 V supply.
3. Function control unit smoke
The control unit is designed to meet the requirements set
to provide reliable fire protection together with our smoke
detectors. Equipped with relay contactors for controlling
dampers and fans. Besides smoke alarms, the control unit
is equipped with a service alarm and error alarm relays.
In the event of a smoke alarm, a red LED lights and the
alarm relays trip at the same time.
In the event of a service alarm on the smoke detector,
the LED for the service alarm flashes quickly for 1 minute.
Then the service alarm relay is active and the LED lights
continuously. If the service alarm on the detector resets,
the relay trips and the LED starts to flash slowly: Alarm
memory.
Short-circuits and open-circuits cause fault relays and
alarm relays to activate at the same time as the respective
LED lights (open-circuit, approx. 10 seconds delay). If a
short-circuit or open-circuit recurs, the relays trip and the
respective LED starts to flash slowly: Alarm memory.
Exercising the relays: keep the reset button depressed for
5 seconds.
4. Installation
Use the four screws to mount the equipment cabinet on
the wall, unit or similar.
5. Technical Data
Supply voltage 230VAC, 50-60Hz
Power consumption
(control unit)
1.8VA
Degree of protection IP 65
Ambient temperature 0-50°C
Dimensions (WxHxD) 175 x 125 x 100mm
Weight 740g