5
Setting test mode detection area with remote control
•The detector goes directly into test mode when the test
mode is set via the remote control:
□Every movement is indicated by the LED.
□When movement occurs the light and presence switch
contacts close.
□When no one is present the light switch contact opens after
10 seconds.
□Brightness measurement deactivates, detector does not
react to brightness.
□Teach-in cannot be activated in test mode.
•Test mode ends automatically after 10 mins. The detector
performs a new start (see switch-on behaviour).
10. Technical data
Operating voltage 230 V AC +- 10 %
Frequency 50 Hz
Upstream protection device: 13 A
Power consumption approx. 0.5 W
Type of installation Ceiling installation
Recommended installation height 2.0 – 4.0 m
Minimum height > 1.7 m
Detection area horizontal
vertical
360°
120°
Maximum range Ø 4 m (Mh. 3 m) / 13 m2radially
moving
Ø 8 m (Mh. 3 m) / 50 m2tan-
gentially moving
Setting range brightness switching value 30 – 3000 Lux
Lighting time delay A light 10 s – 60 min / Pulse
Presence time delay 10 s – 120 min
Channel A light Relay 230 V /10 A, µ-contact
Max. switching capacity cos j1 resistive 2300 W
Max. switching capacity cos j 0.5 1150 VA
Max. switching capacity LED
Guide values
see manufacturer concerning
cos j
< 2 W : 25 W / > 2 W : 70 W
Guidance value max. inrush current level 400 A / 200 µs
Maximum number EBs T5/T8 10 x 54/58 W, 16 x 35/36 W
5 x 2 x 54/58 W
8x 2x 35/36 W
Channel H, presence Floating relay
Maximum voltage 220 V DC / 250 V AC
Maximum switching capacity 50 W / 50 VA (max. 2 A)
Recommended minimum load 0.5 mV / 10 mA
Connection type Screwless terminals
Max. cable cross-section max. 2.5 mm²
Protection rating: theMova S360-101 DE
Protection rating: theMova S360-101 AP
IP 20
IP 40 in installed state
IP 54
Ambient temperature -15 °C to +50 °C
CE Declaration of Conformity This device conforms to the
safety regulations of the EMC
directive 2004/108/EC and of
NSR 2006/95/EC.
Product overview
Type of
installation
Channel Operating
voltage
Colour Type Item No.
Ceiling
installation
Light |
HVAC
230 V AC White theMova
S360 -101
DE WH
1030565
Ceiling
installation
Light |
HVAC
230 V AC Grey theMova
S360 -101
DE GR
1030566
Ceiling
installation
Light |
HVAC
230 V AC Special colour
in accordance
with customer
information
theMova
S360 -101
DE SF
1030568
Ceiling
installation
Light |
HVAC
230 V AC White theMova
S360 -101
AP WH
1030555
Ceiling
installation
Light |
HVAC
230 V AC Grey theMova
S360 -101
AP GR
1030556
Ceiling
installation
Light |
HVAC
230 V AC Special colour
in accordance
with customer
information
theMova
S360 -101
AP SF
1030558
Troubleshooting
Fault Cause
Light does not switch
on if presence is
detected and in
darkness
Lux value is set too low; light was switched off
via theSenda S; person not within detection area;
obstruction(s) interrupting detection; time delay
set too short
Light does not switch
off and/or light
switches on spontane-
ously when no one is
present
Wait for time delay;
Thermal sources of interference in the detection
area: fan heaters, incandescent lamps/halogen
spotlights, moving objects (e.g. curtains hanging in
an open windows);
Load (EBs, relays) not cleared
Error ashing
(4 x per second)
Error in self-test;
Device not properly functional!
LED display
LED Description
Blinking in 1
second cycle
The motion detector is in the start-up phase.
Flickering
for 2 s
The command sent from the remote control via infrared was
accepted by the motion detector.
Lights up
briey
The command sent from the remote control via infrared
was rejected by the motion detector. The command is not
valid. Check the detector type or parameter selected in the
"SendoPro".
Fast
blinking
Error blinking; The motion detector has found an error.
Lights or
ickers
irregularly
The motion detector is in detection area test mode or "LED
display movement" is activated. The LED displays detection
of movement.
Guarantee
ThebenHTS motion detectors are manufactured with the
utmost care and using state-of-the-art technology and are
quality-tested. ThebenHTS AG therefore guarantees perfect
operation when used correctly. Should a fault occur, however,
ThebenHTS AG will full the guarantee within the scope of the
general terms and conditions.
Please note in particular:
•that the guarantee period lasts 24 months from the date
of manufacture.
•that the guarantee is invalidated if you, or a third party,
make changes or undertake repairs to the devices.