Tyco MULTIMATIC F470H User manual

DELUGE VALVE,HORIZONTAL
MODEL F470H MULTIMATIC®— 4 and 6 INCH (100 and 150 mm)
GENERAL DESCRIPTION
The 4 and 6 inch (100 and 150 mm),
Model F470H Horizontal Multimatic
Deluge Valves are differential latch
type valves designed for fire protection
system service. They are used as
“automatic water control valves”in del-
uge, preaction, and foam-water fire
protection systems.The F470H Valves
alsoprovidefor actuationoffirealarms
upon system operation.
Operation of an F470H Valve is pro-
vided by an actuation (detection) sys-
tem that is separate from the normally
dry system piping. Trim configuration
options for automatic operation of the
F470H include wet pilot actuation, dry
pilot actuation, and electric actuation.
The various trim arrangements also
provide for local emergency (manual)
release of the F470H Valves.
APPROVALS AND STANDARDS
The 4 and 6 inch (100 and 150 mm),
Model F470H Horizontal Multimatic
Deluge Valves are listed by Underwrit-
ers Laboratories Inc. and Underwrit-
ers’ Laboratories of Canada. The
F470H Valves are also approved by
Factory Mutual Research Corporation.
The Model F470H Multimatic Deluge
ValvesareacceptedbytheCity ofNew
York under MEA 38-92-M.
WARNING
The Model F470H Horizontal Multi-
matic Deluge Valves described herein
must be installed and maintained in
compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation, in addition to the standards
of any other authorities having juris-
diction. Failure to do so may impair
the integrity of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. The installing contractor or
manufacturer should be contacted
relative to any questions.
Printed in U.S.A. 9-99 TD116H
Nominal Dimensions in Inches and (mm)
VALVE
SIZE
4
(100)
6
(150)
VALVE
SIZE
4
(100)
6
(150)
A
2"
NPT
2"
NPT
J
8.00
(203,2)
8.87
(225,3)
B
1/2"
NPT
1/2"
NPT
K
10.50
(266,7)
11.50
(292,1)
C
1/2"
NPT
1/2"
NPT
L
8.50
(215,9)
9.18
(233,2)
D
6.56
(166,6)
6.45
(163,8)
M
3.75
(95,3)
4.54
(115,3)
E
3.44
(87,4)
3.40
(86,4)
N
2.37
(60,2)
3.20
(81,3)
F
2.56
(65,0)
2.45
(62,2)
P
2.56
(65,0)
2.45
(62,2)
G
2.73
(69,3)
3.69
(93,7)
Q
1.72
(43,7)
1.82
(46,2)
H
5.25
(133,4)
6.63
(168,4)
R
13.25
(336,6)
14.25
(362,0)
6 INCH (150 mm)
VALVE ILLUSTRATED
FIGURE A
MODEL F470H HORIZONTAL MULTIMATIC DELUGE VALVES
— DIMENSIONS AND PORT LOCATIONS —
OBSOLETE

-2-
1 - Body
2 - Clapper
3 - Clapper Facing
4 - Clapper Facing
Retainer
5 - Clapper Bolt
6 - Seat Ring
7 - Clapper Latch
8 - O-Ring, # 3-908
9 - Clapper Latch Stop
10 - Diaphragm Cover
Bolt, (5 req’d)
1/2" - 13 UNC x 1"
11 - Diaphragm Retainer
12 - Flange & Push Rod
Assembly
13 - Diaphragm
14 - Diaphragm
Housing
15 - 1/2" Pipe Plug
(4 req’d)
16 - Bearing (4 req’d)
17 - Clapper Hinge Pin
18 - Latch Hinge Pin
19 - Handhole Cover
20 - Handhole Cover Gasket
21 - Handhole Cover Bolt,
(1/2" - 13 UNC x 1-1/2"
4 req’d for 4" valve)
(3/4" - 11 UNC x 1-1/2"
5 req’d for 6" valve)
Nominal Dimensions in Inches and (mm)
ANSI B16.1 (CLASS 125)
AS 2129 (TABLE E)
ISO 2084 (PN10)†
JIS B 2210 (10K)
4" (100 mm) Valve Size 6" (150 mm) Valve Size
ABAB
7.50 (190,5)
7.00 (178,0)
7.09 (180,0)
6.89 (175,0)
0.75 (19,0)
0.71 (18,0)
0.71 (18,0)
0.75 (19,0)
9.50 (241,3) 0.88 (22,2)
9.25 (235,0)
9.45 (240,0)
9.45 (240,0)
0.87 (22,0)
0.87 (22,0)
0.91 (23,0)
†Same drilling as for BS 4504 Section 3.2 (PN10) and DIN 2532 (PN10).
TABLE A
DIMENSIONAL SPECIFICATIONS FOR SELECTION OF FLANGE DRILLING
FIGURE B
MODEL F470H HORIZONTAL
MULTIMATIC DELUGE VALVE
— ASSEMBLY —
OBSOLETE

TECHNICAL DATA
Deluge Valve:
The 4 and 6 inch (100 and 150 mm),
Model F470H Horizontal Multimatic
Deluge Valves are rated for use at a
maximum service pressure of 175 psi
(12,1 bar). The Valve dimensions are
shown in Figure A, and all of the ports
are NPT threaded per ANSI Standard
B1.20.1. Flanged inlet and outlet con-
nections are available drilled per the
ANSI, AS, ISO, and JIS specification
options indicated in Table A.When the
flange drilling is provided to AS, ISO,
or JIS specifications, the label located
on the Handhole Cover indicates the
specification to which the flange drill-
ing has been provided.
TheF470HValveistobeinstalledhori-
zontally, as shown in Figure A.Exterior
surfaces of the F470H Valve are
painted red, and the year of manufac-
ture is indicated on the Handhole
Cover.
Components of the F470H Valve are
shown in Figure B. The Body, Hand-
hole Cover, and Diaphragm Cover are
ductile iron per ASTM A536 (UNS
F33100). The Handhole Cover Gasket
is neoprene, and the Clapper Facing,
Diaphragm, and O-Rings are EPDM.
The Seat Ring, Clapper, Diaphragm
Retainer, and the Flange of the Flange
& Push Rod Assembly are bronze per
ASTM B62 (UNS C83600).The Clap-
per Latch is aluminum bronze per
ASTM B148 (UNS C956200), the
Clapper Latch Stop is brass per ASTM
B16 (UNS C36000), and the Bearings
are bronze per ASTM B438, Grade 1,
Type II. The Clapper Facing Retainer,
ClapperBolt,ClapperHingePin,Latch
Hinge Pin, and the Push Rod of the
Flange & Push Rod Assembly are fab-
ricated from austenitic stainless steel.
TheHandholeCover Bolts,Diaphragm
Cover Bolts, and Pipe Plugs are carb-
on steel.
The nominal pressure losses versus
flow are shown in Graphs A-1 and A-2.
Theapproximatefrictionlosses,based
on the Hazen and Williams formula
and expressed in equivalent length of
Schedule 40 pipe with C = 120, is 12
feet for the 4 inch (100 mm) valve size
and 30 feet for the 6 inch (150 mm)
valve size. The equivalent length of
pipe has been calculated on the basis
of the flow rates typically used with
each size valve.
Valve Trim:
The Wet Pilot Actuation Trim, Dry Pilot
Actuation Trim, or Electric Actuation
Trim illustrated in Figure D form a part
of the laboratory listings and approval
of the F470H Valves and are neces-
sary for their proper operation. Each
package of trim includes the following
items:
•Water Supply Pressure Gauge
•Diaphragm Chamber
Pressure Gauge
•DiaphragmChamberConnections
•Actuation Devices (as applicable)
•Main Drain Valve
•Alarm Test Valve
•Alarm Control Valve
•Automatic Drain Valve
•Dry Pilot Line Pressure Gauge
(as applicable)
Wet Pilot Actuation
(Figure D, Items 1 through 38)
The Wet Pilot Actuation Trim provides
for connection of a detection system
consisting of wet pilot sprinklers (heat
detectors) and manual control stations
-3
GRAPHS A-1 and A-2
NOMINAL PRESSURE LOSS VERSUS FLOW
GRAPH A-1 GRAPH A-2
OBSOLETE

interconnected with minimum 1/2 inch
(15 mm) Schedule 40 steel pipe. The
pilot line is connected to the “Wet Pilot
Detection”connection shown in Figure
D. Minimum clearance dimensions for
the Wet Pilot Actuation Trim are shown
in Figure C.
Wet pilot sprinklers are to be minimum
1/2 inch (15 mm) orifice listed or ap-
proved automatic sprinklers. Manual
Control Stations are to be either the
ModelF180orF184describedinTech-
nical Data Sheet TD121.
The maximum height of a wet pilot line
above the F470H Valve must not ex-
ceed the limitations given in Graph B
as a function of the minimum water
supply pressure to the F470H Valve
and the length of the pilot line to the
most remote pilot sprinkler.
Provision must be made for installing
a 1/2 inch (15mm) orifice, Inspector’s
Test Connection at the most hydrauli-
cally demanding location of a wet pilot
line (usually adjacent to the highest
and most remote wet pilot sprinkler or
manual control station).
To determine the most hydraulically
demanding location of a wet pilot line,
when the choice between two or more
locations is not readily apparent, de-
termine for each location the elevation
above the F470H Valve and the
equivalent length of fittings plus hori-
zontal pipe from the F470H Valve to
the location.Then, using Graph B, de-
termine the minimum system supply
pressurerequired for theelevationand
equivalent length of pipe at each loca-
tion. Interpolate between the equiva-
lent length plots as necessary. The lo-
cation requiring the highest system
supply pressure is the most hydrauli-
cally demanding location for the wet
pilot line. (Reference: In no case
should the required system supply
pressure exceed the minimum ex-
pected system supply pressure.)
Operation of a pilot sprinkler or open-
ing of a manual control station results
in a rapid pressure drop in the Dia-
phragm Chamber of the F470H Valve,
and the force differential applied
through the Clapper Latch which holds
the Clapper down in the set position is
reduced to below the valve trip point.
NOTES
WetPilotLinesmustbemaintainedat
a minmum temperature of 40°F/4°C.
Itisrecommendedthatinternallygal-
vanized pipe and cast iron fittings be
used for wet pilot lines.
Dry Pilot Actuation
(Figure D, Items 1 through 38 plus
Items D1 through D15)
The Dry Pilot Actuation Trim provides
for installation of a detection system
consisting of dry pilot sprinklers (heat
detectors) and manual control stations
interconnected with minimum 1/2 inch
(15 mm) steel pipe. The pilot line,
which is to be pressurized with air or
nitrogen, is connected to the “Dry Pilot
Detection”connection shown in Figure
D. Provision must be made for a 1/2
inch (15 mm) orifice, Inspector’s Test
Connection at the most remote loca-
tion from the F470H Valve. Minimum
clearance dimensions for Dry Pilot Ac-
tuationTrimareshowninFigureC.
The Dry Pilot Actuation Trim is pro-
videdwith a listedandapproved Model
B-1 Dry Pilot Actuator, which is de-
scribed in Technical Data Sheet
TD117W.The Actuator is rated for use
at a maximum pilot service pressure of
50 psi (3,4 bar) and a maximum water
supply service pressure of 175 psi
(12,1 bar).
Operation of a pilot sprinkler or open-
ing of a manual control station, re-
leases pneumatic pressure from the
pilot line.In turn, the Dry Pilot Actuator
opens resulting in a rapid pressure
drop in the Diaphragm Chamber of the
F470H Valve, and the force differential
applied through the Clapper Latch
-4-
GRAPH B
WET PILOT LINE DESIGN CRITERIA
OBSOLETE

which holds the Clapper down in the
set position is reduced to below the
valvetrippoint.
Dry pilot sprinklers are to be minimum
1/2 inch (15 mm) orifice listed or ap-
proved automatic sprinklers. Manual
Control Stations are to be either the
ModelF180orF184describedinTech-
nical Data Sheet TD121.
Graph C shows the “minimum pilotline
service pressure” as a function of the
watersupplypressure.Thepressurein
the dry pilot actuation system must be
automatically maintained using one of
the following maintenance devices, as
appropriate.
•Model F324 Air Maintenance De-
vice (pressure reducing type), re-
fer to Technical Data Sheet
TD111.
•Model F326 Air Maintenance De-
vice(compressorcontroltype), re-
fer to Technical Data Sheet
TD112.
•Model F328 Nitrogen Mainte-
nance Device (high pressure re-
ducing type), refer to Technical
Data Sheet TD113.
NOTES
The dewpoint of thepilot line air pres-
sure must be maintained below the
lowest ambient temperature to which
the dry pilot actuation system will be
exposed.Accumulation of water in the
pilot line connection to the Actuator
will lower the air pressure at which
the Actuator will open and possibly
prevent proper operation. Also, intro-
ductionof moistureinto thepilotlines
exposed to freezing temperatures can
createan icebuildupwhichcouldpre-
vent proper operation of the Actuator.
An air dryer must be installed where
the moisture content of the air supply
is not properly controlled at less than
therequiredvalue.Thedesiccantdryer
with mounting accessories described
inTechnicalDataSheetTD135issuit-
able for use with a maximum inlet
pressure of 150 psi (10,3 bar) and for
drying system air down to a dewpoint
of less than -20°F/-29°C at a pressure
of 45 psi (3,1 bar).
It is recommended that an F328 Ni-
trogenMaintenanceDevicebeutilized
in dry pilot actuation system applica-
tions where the dewpoint must be
maintained below -20°F/-29°C. See
Technical Data Sheet TD113.
Itisrecommendedthatinternallygal-
vanized pipe and cast iron fittings be
used for dry pilot lines.
Supervision of the pressure in the dry
pilot actuation system and/or alarm
which separately indicates operation
of the detection system is recom-
mended and may be required by the
authority having jurisdiction. A dual
setting low pressure alarm switch,
such as the unit described in Technical
Data Sheet TD210, is suitable for the
service. The recommended pressure
settings are as follows:
• Low pressure alarm setting at
approximately 6 psi (0,4 bar)
below the minimum pilot line
service pressure requirement
shown in Graph C.
• Fire alarm setting at approxi-
mately 15 psi (1,0 bar) below
the minimum pilot line service
pressure requirement shown
in Graph C.
The Pressure Relief Valve (Ref. Item
D5 - Fig. D) is factory set to relieve at
apressureofapproximately45psi(3,1
bar); however, it may be field adjusted
to a lower pressure, if required.
Electric Actuation Trim
(Figure D, Items 1 through 38 plus
Items E1 through E5)
The Electric Actuation Trim is required
for electric operation of the F470H
Valve by a detection system consisting
of electrical devices such as heat sen-
sitive thermostats, smoke detectors,
and/or electric manual pull stations.
Information on the various types of So-
lenoid Valves that may be used with
this trim package is given in Technical
Data Sheet TD119. A listed and ap-
proved, 24VDC Solenoid Valve for
non-hazardous locations is supplied
as standard. Minimum clearance di-
mensions for the Electric Actuation
Trim are shown in Figure C.
NOTE
ApprovalbyFactoryMutualiscontin-
gent on the use of an FM Approved
24VDC Solenoid Valve. FM only ap-
proves solenoid valves for use in non-
hazardous locations.
The Electric Actuation Trim is only to
be used in conjunction with an electric
deluge valve releasing panel (auto-
matic control unit) that is listed or ap-
proved (as appropriate) for fire protec-
tion system releasing service. In
addition, the deluge valve releasing
panel is only to be operated by listed
or approved (as approriate) fire detec-
tors.
Operation of an electrical device such
as a heat sensitive thermostat, smoke
detector, or electrical manual control
stationsignalsthedelugevalvereleas-
ing panel to energize the Solenoid
Valve. In turn, the energized Solenoid
Valve opens resulting in a rapid pres-
sure drop in the Diaphragm Chamber
of the F470H Valve, and the force dif-
ferential applied through the Clapper
Latch which holds the Clapper downin
theset positionisreduced tobelowthe
valvetrippoint.
NOTE
Consult with the Authority Having
Jurisdiction regarding installation
criteria pertaining to electric actua-
tion circuitry.
-5-
GRAPH C
DRY PILOT LINE PRESSURE REQUIREMENTS
OBSOLETE

-6-
FIGURE C
MINIMUM CLEARANCE DIMENSIONS FOR
WET PILOT, DRY PILOT, OR ELECTRIC ACTUATION TRIM
Minimum Clearance Dimensions in Inches and (mm)
VALVE
SIZE
4
(100)
6
(150)
A
17-1/2
(445)
18-1/2
(470)
B
13
(325)
14
(350)
C
9
(225)
10-1/2
(270)
D
13.25
(336,6)
14.25
(362,0)
E
10
(250) 36
(900)
F
12
(300)
12
(300)
G
36
(900)
10
(250)
4 INCH (100 mm)
VALVE ILLUSTRATED
OBSOLETE

OPERATING PRINCIPLES
The Model F470H Horizontal Multi-
matic Deluge Valve is a differential
latch type valve which depends upon
water pressure in the Diaphragm
Chamber to hold the Clapper closed
againstthewatersupplypressure.The
nominal trip ratio is 2.5 to 1, i.e., the
F470H Valve operates (opens) when
the pressure in the Diaphragm Cham-
ber is reduced to approximately 40
percent of the water supply pressure.
When the F470H Valve is set for serv-
ice, the Diaphragm Chamber is pres-
surized through the trim connections
from the inlet side of the system’s main
control valve, for example an O.S.&Y.
gate valve or butterfly valve (Ref. Fig-
ureC).Openingofanactuationdevice,
for example the solenoid valve in the
Electric Actuation Trim (Ref. Fig. D),
releases water from the Diaphragm
Chamber faster than it can be replen-
ished through the 1/8 inch (3,2mm)
Restriction in the Diaphragm Chamber
Supply Connection. This results in a
rapid pressure drop in the Diaphragm
Chamber and the force differential ap-
pliedthroughthe ClapperLatchtohold
the Clapper down in the set position is
reduced to below the valve trip point.
The water supply pressure then forces
the Clapper open permitting water to
flow into the system piping, as well as
through the Alarm Port to actuate the
system alarms.
When the system main control valve is
closed to stop waterflow into the sys-
tem, the Clapper, by design, remains
open until it is manually reset.
INSTALLATION
NOTES
Proper operation of the Model F470H
Horizontal Multimatic Deluge Valves
depends upon their trim being in-
stalled in accordance with the in-
structions given in this Technical
Data Sheet. Failure to follow the ap-
propriate trim diagram may prevent
the F470H Valve from functioning
properly,aswellasvoidlistings,ap-
provals, and the manufacturer’s war-
ranties.
The F470H Valve must be installed in
a readily visible and accessible loca-
tion.
The F470H Valve, associated trim,
and wet pilot lines must be main-
tained at a minimum temperature of
40°F/4°C.
Heat tracing of the F470H Valve or its
associated trim is not permitted.Heat
tracing can result in the formation of
hardened mineral deposits which are
capable of preventing proper opera-
tion.
The Model F470H Horizontal Multi-
maticDelugeValveistobeinstalledin
accordance with the following criteria:
1a. Flange mounting fasteners are to be
tightened uniformly using a cross-
draw sequence. Fastener specifica-
tions are to be as required by the
authority having jurisdiction. Tight-
eningtorquesaretobeasindicated
below.
Valve Fastener Torque
Size Size Ft. Lbs. (Nm)
4" 5/8" (M16) 40-50 (54-68)
6" 3/4" (M20) 50-65 (68-81)
1b. Allnipples,fittings,anddevicesmust
be clean and free of scale and burrs
before installation. Use pipe thread
sealant sparingly on male pipe
threads only.
NOTE
It is recommended that internally
galvanized pipe and cast iron fit-
tingsbeusedforwetordrypilot
lines.
2. The F470H Valve must be trimmed
in accordance with Figure D.
3. Care must be taken to make sure
that check valves, strainers, globe
valves,etc.areinstalledwiththeflow
arrows in the proper direction.
4. Drain tubing to the drip funnel must
be installed with smooth bends that
will not restrict flow.
5. The main drain and drip funnel drain
may be interconnected provided a
check valve is located at least 12
inches (300 mm) below the drip fun-
nel.
6. Suitable provision must be made for
disposal of drain water. Drainage
water must be directed such that it
will not cause accidental damage to
property or danger to persons.
7. Connect the Diaphragm Chamber
Supply Control Valveto the inletside
of the system’s main control valve in
order to facilitate setting of the
F470H Valve (Ref. Figure C).
8. An Inspector’s Test Connection, as
described in the Technical Data sec-
tion,must beprovided for Wetor Dry
Pilot Actuation systems.
9. An Air Maintenance Device, as de-
scribed in the Technical Data Sec-
tion, must be provided for Dry Pilot
Actuation.
10. Adesiccantdryer,whenspecifiedfor
Dry Pilot Actuation, is to be installed
between a drip leg and the Air Main-
tenance Device.
11. The Low Pressure Alarm Switch for
DryPilotActuationistobeadjusted
as follows:
• Low pressure alarm setting at
approximately 6 psi (0,4 bar)
below the minimum pilot line
service pressure requirement
shown in Graph C.
• Fire alarm setting at approxi-
mately 15 psi (1,0 bar) below
the minimum pilot line service
pressure requirement shown
in Graph C.
12. Unused pressure alarm switch con-
nections must be plugged.
13. The Pressure Relief Valve provided
with the Dry Pilot Actuation Trim is
factory set to relieveat a pressure of
approximately 45 psi (3,1 bar),
which can typically be used for a
maximum normal dry pilot actuation
system pressure of 40 psi (2,8 bar).
The Pressure Relief Valve may be
reset;however, itmust be beresetto
relieve at a pressure which is in ac-
cordance with the requirements of
the authority having jurisdiction.
To reset the Pressure Relief Valve,
first loosen the jam nut and then
adjust the cap accordingly — clock-
wise for a higher pressure setting or
counterclockwise for a lower pres-
sure setting. After verifying the de-
sired pressure setting, tighten the
jam nut.
14. Conduit and electrical connections
are to be made in accordance with
the requirements of the authority
having jurisdiction and/or the Na-
tional Electric Code.
VALVE SETTING PROCEDURE
Steps 1 through 14 are to be per-
formed when initially setting the Model
F470H Horizontal Multimatic Deluge
Valve; after an operational test of the
fire protection system;or, after system
operation due to a fire.
1. ClosetheDiaphragmChamberSup-
ply Control Valve.
2. Close the Main Control Valve, and if
thesystemisequippedwithDryPilot
Actuation, close the Air Supply Con-
trol Valve (Ref. Figure D).
3. Open the Main Drain Valve and all
-7-
OBSOLETE

-8-
FIGURE D
EXPLODED VIEW OF VALVE TRIM
NOTES:
1. Refer to Page 9 for the corresponding bills of materials.
2. Alternate pressure alarm switch location.
3. 3/4" NPT connection for water motor alarm.
OBSOLETE

auxiliary drains in the system.Close
the auxiliary drain valves after water
ceases todischarge.Leave theMain
Drain Valve open.
4. Depress the plunger of the Automat-
ic Drain Valve to verify that it is open
and that the F470H Valve, as well as
the horizontal main, is completely
drained.
5. Remove the Handhole Cover and
thoroughly clean all interior parts of
the F470H Valve. Make certain that
the two 1/8 inch (3,2mm) diameter
pressure equalizing ventsinthesys-
tem side of the Clapper are open.
TesttheClapper,ClapperLatch, and
Flange and Push Rod for freedom of
movement.Inspect the Clapper Fac-
ing for any sign of deterioration due
to age or chemicals in the water.
Replacewornordamagedparts,ac-
cordingly.
6. Raise the Clapper and pivot the
Clapper latch to allow the Clapper to
be reseated. After reseating the
Clapper, release the Latch so that it
reseats on the Clapper.
7. Clean theStrainer in theDiaphragm
Chamber Supply connection by re-
moving the clean-out plug and
strainer basket.The Strainer may be
flushed out by momentarily opening
the Diaphragm Chamber Supply
Control Valve.
8. Open the Alarm Control Valve (Fig.
D), if it was closed to silence local
alarms.
It is recommended that the Alarm
Control Valve be wire sealed in the
open position with a No. 16 twisted
wire, the ends of which are secured
by a lead seal.The wire seal should
be looped through the hole in the
handleandtightlytwistedaroundthe
pipe nipple adjacent to the handle.
9. Reset the actuation system.
Manual Actuation — Push the oper-
ating lever up; however, do not close
the hinged cover at this time.
Wet Pilot Actuation — Replace op-
erated pilot sprinklers and/or reset
the manual control stations.
Dry Pilot Actuation — Replace oper-
ated pilot sprinklers and/or reset the
manual control stations. Re-estab-
lish dry pilot pneumatic pressure.
Electric Actuation — Reset the elec-
tric detection system in accordance
with the manufacturer’s instructions
to de-energize the solenoid valve.
NOTE
If the system is being set after a
fire and in order to prevent the
possibility of a subsequent opera-
tion of an overheated solder type
pilot sprinkler, any solder type pi-
lot sprinklers which were possibly
exposed to a temperature greater
than their maximum rated ambi-
ent must be replaced.
10. Open theDiaphragm ChamberSup-
ply Control Valve and allow time for
full pressure to build up in the Dia-
phragm Chamber.
11. Operate (open) the Manual Control
Station to vent trapped air from the
Diaphragm Chamber. If necessary,
first open the hinged cover, and then
fullypulldownontheoperatinglever.
SLOWLY close the operating lever,
by pushing it up, after aerated water
ceases to discharge from the Man-
ual Control Station drain tubing.
Close the hinged cover and insert a
new break rod in the small hole
through the top of the enclosing
box.
If wet pilot actuation is being used,
crackopen theInspector’sTest Con-
nection and any other vent valves, to
relieve trapped air. After the dis-
charge of air has stopped, close the
vent valves and the Inspector’s Test
Connection.
12. Inspect drain connections from the
Manual Control Station, Solenoid
Valve, Dry Pilot Actuator, and Alarm
Devices, as applicable. Any leaks
must be corrected before proceed-
ing to the next step.
13. Replace the Handhole Cover and
Gasket. Tighten all Handhole Cover
Bolts uniformly using a cross-draw
sequence.
14. Slowly open the Main Control Valve.
Close the Main Drain Valve as soon
as water discharges from the drain
connection. Observe the Automatic
Drain Valve for leaks. If there are
leaks, determine/correct the cause
of the leakage problem. If there are
no leaks, the F470H Valve is ready
to be placed in service and the Main
Control Valve must then be fully
opened.
NOTE
After setting a fire protection system,
notify the proper authorities and ad-
vise those responsible for monitoring
proprietary and/or central station
alarms.
-9-
VALVE TRIM
BILLS OF MATERIALS
NOTES:
1. WetPilotActuationTrimconsistsof
Items 1 through 38.
2. Dry PilotActuationTrim consistsof
Items 1 through 38 plus Items D1
through D15.
3. Electric Actuation Trim consists of
Items 1 through 38 plus Items E1
through E5.
4. The nipples utilized in the trim ar-
rangements are Schedule 40 steel
per ASTM A53 or A135 and they are
threaded per ANSI B1.20.1 The fit-
tings are either malleable iron per
ANSI B16.3 or cast iron per ANSI
B16.4.
“Standard order” trim is provided
with black nipples and fittings: how-
ever, galvanized nipples and fittings
are available on “special order”.
1 - 300 lb. Water
Pressure
Gauge (2 req’d)
2 - 1/4" Gauge
Test Valve
3 - Model F180
Manual Control
Station
4 - 2" Angle Valve
5 - 1/2" Ball Valve
(2 req’d)
6 - 1/2" Swing
Check Valve
7 - 1/2" Spring
Loaded Check
Valve
8 - Priming Supply
Restriction
9 - 1/2" Y-Strainer
10 - Model F793
Automatic
Drain Valve
11 - Drip Funnel
Support Plug
12 - Drip Funnel
Support
13 - Drip Funnel
14 - 3/32" Vent
Fitting
15 - 1/2" Angle
Valve
16 - 1/4" Tube,
30" long
17 - 1/2" Tube,
Connector
18 - 1/2" Tube,
24" long
19 - 1/4" Plug
20 - 1/2" Plug
21 - 3/4" Plug
22 - 1/2" Union
(5 req’d)
23 - 1/2" 90° Elbow
(3 req’d)
24 - 1/2" Tee (4 req’d)
25 - 1/2" x 1/4" x 1/2"
Tee (2 req’d)
26 - 1/2" x 1/2" x 3/4"
Tee
27 - 1/2" Cross
28 - 1/2" x 1/4"
Bushing
29 - 2" 90° Elbow
30 - 1/2" x 1-1/2"
Nipple
(16 req’d)
31 - 1/2" x 2"
Nipple
32 - 1/2" x 3" Nipple
33 - 1/2" x 5" Nipple
34 -1/2" x 7-1/2"
35 - 1/2" x 10-1/2"
Nipple for
4" valve,
1/2" x 12"
Nipple for
6" valve
36 - 1/4" x 4" Nipple
37 - 2 x 3" Nipple
38 - 2 x 4" Nipple
D1 - Model B-1
Dry Pilot
Actuator
D2 - 250 lb. Air
Pressure Gauge
D3 - 1/4" Gauge
Test Valve
D4 - 1/2" Globe
Valve
D5 - 1/4" Pressure
Relief Valve
D6 - 1/4" Plug
D7 - 1/2" Tube
Connector
D8 - 1/2" Tube,
30" long
D9 - 1/2" 90° Elbow
(2 req’d)
D10 - 1/2" x 1/2" x 1/4"
Tee (2 req’d)
D11 - 1/2" Tee (2 req’d)
D12 - 1/4" x 2" Nipple
D13 - 1/2" x close
Nipple (2 req’d)
D14 - 1/2" x 1-1/2"
Nipple (4 req’d)
D15 - 1/2" x 2"
Nipple (2 req’d)
E1 - 1/2" 90° Elbow
E2 - 1/2" Tube
Connector
E3 - 1/2" Tube,
30" long
E4 - 1/2" x 1-1/2"
Nipple
(2 req’d)
E5 - 24VDC Solenoid
Valve
OBSOLETE

CARE AND MAINTENANCE
The following procedures and inspec-
tions should be performed as indi-
cated, in addition to any specific re-
quirements of the NFPA, and any
impairment must be immediately cor-
rected.It isalsorecommendedthatfire
protection systems be inspected by a
qualified Inspection Service.
NOTES
The operational test procedure, water-
flow pressure alarm test procedure,
and low pressure alarm test proce-
dure will result in operation of the
associated alarms. Consequently, no-
tification must first be given to the
owner and the fire department, cen-
tral station, or other signal station to
which the alarms are connected.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
which it controls, permission to shut
down the effected fire protection sys-
tems must first be obtained from the
proper authorities and all personnel
who may be affected by this decision
must be notified.
Annual Operation Test Procedure
Proper operation of the F470H Valve
(i.e., opening of the F470H Valve as
during a fire condition) should be veri-
fied at least once a year as follows:
1. Ifwatermustbepreventedfromflow-
ing beyond the riser, perform the fol-
lowing steps.
a. Close the Main Control Valve.
b. Open the Main Drain Valve.
c. Open the Main Control Valve
oneturn beyond theposition at
which water just begins to flow
from the Main Drain Valve.
d. Close the Main Drain Valve.
2. Determine the type of actuation/de-
tection system, and operate the
F470H Valve accordingly.
NOTE
Be prepared to quickly perform
Steps3,4,and5,ifwatermustbe
prevented from flowing beyond
the riser.
Wet Pilot Actuation — Open the
Inspector’s Test Connection.
Dry Pilot Actuation — Open the
Inspector’s Test Connection.
Electric Actuation — Test the del-
uge releasing panel (automatic con-
trol unit) in accordance with the
manufacturer’s instructions to ener-
gize the solenoid valve.
3. Verify that the F470H Valve has
tripped, as indicated by the flow of
water into the system.
4. ClosetheDiaphragmChamberSup-
ply Control Valve.
5. Close the system’s Main Control
Valve.
6. Reset the F470H Deluge Valve in
accordance with the Valve Setting
Procedure.
Five Year Internal Valve Inspection
Once every five years during the an-
nual operational test procedure and
prior to the F470H Valve being reset,
the Diaphragm should be inspected
and replaced if there are any signs of
deterioration due to age or chemicals
in the water.
NOTE
If the water supply contains chemi-
cals which tend to attack an EPDM
type rubber, the frequency of the Dia-
phragm inspection should be in-
creased as appropriate.
Worn or damaged parts must be re-
placed and the F470H Valve must be
reassembled in accordance with Fig-
ure B. The Cap Screws securing the
Diaphragm and Handhole Covers
should be uniformly tightened using a
cross-draw sequence.
Quarterly Solenoid Valve Test Pro-
cedure For Electric Actuation
Proper operation of the Solenoid Valve
for electric actuation should beverified
at least quarterly as follows:
1. Close the Main Control Valve.
2. Open the Main Drain Valve.
3. Test the automatic control unit (del-
uge releasing panel) in accordance
with the manufacturer’s instructions
to energize the solenoid valve.
4. Verify that the flow of water from the
Solenoid Valve drain connection in-
creases to a full flow.
5. Verify that the Diaphragm Chamber
pressure has decreased to below
25% of the water supply pressure.
6. Reset the electric detection system
in accordance with the manufac-
turer’s instructions to de-energize
the solenoid valve. Check the Sole-
noid Valve drain for leaks.Any leaks
must be corrected before proceed-
ing to the next step.
7. Slowly open the Main Control Valve.
Close the Main Drain Valve as soon
as water discharges from the drain
connection. Observe the Automatic
Drain Valve for leaks. If there are
leaks, determine/correct the cause
of the leakage problem. If there are
no leaks, the F470H Valve is ready
to be placed in service and the Main
Control Valve must then be fully
opened.
Quarterly Dry Pilot Actuator Test
Procedure For Dry Pilot Actuation
Proper operation of the Dry Pilot Ac-
tuator for dry pilot actuation should be
verified at least quarterly as follows:
1. Close the Main Control Valve.
2. Open the Main Drain Valve.
3. Open the Inspector’s Test Connec-
tion on the Dry Pilot Line.
4. Verify that the flow of water from the
Dry Pilot Actuator drain connection
increases to a full flow.
5. Verify that the Diaphragm Chamber
pressure has decreased to below
25% of the water supply pressure.
6. Close the Inspector’s Test Connec-
tion and allow the dry pilot line pres-
sure to re-establish. Check the Dry
Pilot Actuator drain for leaks. Any
leaks must be corrected before pro-
ceeding to the next step.
7. Slowly open the Main Control Valve.
Close the Main Drain Valve as soon
as water discharges from the drain
connection. Observe the Automatic
Drain Valve for leaks. If there are
leaks, determine/correct the cause
of the leakage problem. If there are
no leaks, the F470H Valve is ready
to be placed in service and the Main
Control Valve must then be fully
opened.
Quarterly Waterflow Alarm Test
Procedure
Testingof thesystemwaterflowalarms
should be performed quarterly. To test
the waterflow alarm, open the Alarm
Test Valve, which will allow a flow of
water to the Pressure Alarm Switch
and/or Water Motor Alarm.Uponsatis-
factory completion of the test, close
the Alarm Test Valve.
Quarterly Low Pressure Alarm Test
Procedure And Condensate Drain
Procedure For Dry Pilot Actuation
For Dry Pilot Actuation, testing of the
-10-
OBSOLETE

Low Pressure Alarm Switch and drain-
age of the pilot line condensate should
be performed quarterly as follows.
1. ClosetheDiaphragmChamberSup-
ply Control Valve.
2. Close the Main Control Valve.
3. Open the Main Drain Valve.
4. Drain the dry pilot line condensate
as follows.
a. Close the Gauge Test Valve lo-
cated below the Dry Pilot Line
Pressure Gauge.
b. Remove the 1/4" Plug from the
Gauge Test Valve.
c. Crack Open the Gauge Test
Valve and allow all conden-
sate, if any, to drain out.
d. Close the Gauge Test Valve,
replace the Plug, and then
open the Gauge Test Valve.
5. Open the Inspector’s Test Connec-
tion, and slowly relieve pneumatic
pressure. Verify that the Low pres-
sureAlarmSwitchisoperationaland
that the low pressure set points are
as follows:
• Low pressure alarm setting at
approximately 6 psi (0,4 bar)
below the minimum pilot line
service pressure requirement
shown in Graph C.
• Fire alarm setting at approxi-
mately 15 psi (1,0 bar) below
the minimum pilot line service
pressure requirement shown
in Graph C.
6. Close the Inspector’s Test Connec-
tion, and allow the Dry Pilot Line to
automatically repressurize.
7. Open the Diaphragm ChamberSup-
ply Control Valve.
8. Slowly open the Main Control Valve.
Close the Main Drain Valve as soon
as water discharges from the drain
connection. Observe the Automatic
Drain Valve for leaks. If there are
leaks, determine/correct the cause
of the leakage problem. If there are
no leaks, fully open the Main Control
Valve.
WARRANTY
Seller warrants for a period of oneyear
from the date of shipment (warranty
period) that the products furnished
hereunder will be free from defects in
material and workmanship.
For further details on Warranty, see
Price List.
ORDERING PROCEDURE
All orders for Model F470H Multimatic
Deluge Valves, trim, accessories, and
replacement parts must include the
description and Product Symbol
Number (PSN), where applicable.
Valves:
Unlessotherwise specified, theF470H
Valves will be provided with ANSI
flange drilling.
Specify: (specify size) Model F470H
Horizontal Multimatic Deluge Valve
with (specify abbreviation — refer to
Table A, Page 2) flange drilling, PSN
(specify).
ANSI
4" (100 mm) . . . . . . . . . . . . . . PSN 52-471-1-013
6" (150 mm) . . . . . . . . . . . . . . PSN 52-471-1-015
ISO
4" (100 mm) . . . . . . . . . . . . . . PSN 52-471-4-113
6" (150 mm) . . . . . . . . . . . . . . PSN 52-471-4-115
AS
4" (100 mm) . . . . . . . . . . . . . . PSN 52-471-4-313
6" (150 mm) . . . . . . . . . . . . . . PSN 52-471-4-315
JIS
4" (100 mm) . . . . . . . . . . . . . . PSN 52-471-4-713
6" (150 mm) . . . . . . . . . . . . . . PSN 52-471-4-715
“Standard Order” Black Trim:
Specify: Black (specify type trim) for
use with the Model F470H Horizontal
Multimatic Deluge Valve, PSN (spec-
ify).
Wet Pilot Actuation
Trim . . . . . . . . . . . . . . . . . . PSN 52-471-1-201
Dry Pilot Actuation
Trim . . . . . . . . . . . . . . . . . . PSN 52-471-1-202
Electric Actuation
Trim With 24VDC
Solenoid Valve. . . . . . . . . . PSN 52-471-1-203
“Special Order” Galvanized Trim:
Specify:Galvanized (specify type trim)
for use with the Model F470H Horizon-
tal Multimatic Deluge Valve, PSN
(specify).
Wet Pilot Actuation
Trim...................PSN52-471-2-201
Dry Pilot Actuation
Trim...................PSN52-471-2-202
Electric Actuation
Trim With 24VDC
Solenoid Valve . . . . . . . ...PSN52-471-2-203
“Special Order” Electric Actuation
Trim With Separately Ordered Sole-
noid Valve:
Specify: (Specify black or galvanized)
Electric Actuation Trim With Sepa-
rately Ordered Solenoid Valve for use
with the Model F470H Horizontal Mul-
timatic Deluge Valve.
Whenordering“Electric ActuationTrim
With Separately Ordered Solenoid
Valve”, refer to Technical Data Sheet
TD119 for information on separately
ordered, UL Listed Solenoid Valves
that may be suitable for use in hazard-
ous locations or that have voltage rat-
ings other than 24VDC.
NOTE
Factory Mutual Approval for electric
actuation of the F470H Valve is con-
tingent on the use of the FM Approved
24VDC Solenoid Valve provided with
the “Standard Order” Electric Actua-
tion Trim, PSN 52-470-1-103 or PSN
52-470-2-103.
Accessories:
Refer to the following Technical Data
Sheets (TD), as applicable.
PressureAlarmSwitch ........ TD213
Low Pressure Alarm Switch. . . . . TD210
Model F324 Air Maintenance
Device................... TD111
Model F326 Air Maintenance
Device................... TD112
Model F328 Nitrogen Maintenance
Device................... TD113
DesiccantDryer.............. TD135
Model F180 or F184
Manual Control Stations. . . . . . TD121
Valve Replacement Parts Kit:
The Valve Replacement Parts Kit con-
tains a Clapper Facing, Diaphragm,
and Handhole Cover Gasket.It is rec-
ommended to have these parts readily
available when servicing the Model
F470H Horizontal Multimatic Deluge
Valve.
Specify: Valve Replacement Parts Kit
for use with (specify size) inch Model
F470H Horizontal Multimatic Deluge
Valve.
4"(100mm) ..............PSN92-470-1-101
6"(150mm) ..............PSN92-470-1-102
-11-
OBSOLETE

Replacement Valve Parts (Fig. B):
Specify: (description) for use with
(specify size) Model F470H Horizontal
Multimatic Deluge Valve, PSN (spec-
ify).
4 inch (100 mm) Valve
2 - Clapper . . . . . . . . . . . . . . . PSN 92-470-1-006
3 - Clapper Facing . . . . . . . . . PSN 92-470-1-009
4 - Clapper Facing
Retainer . . . . . . . . . . . . . PSN 92-470-1-004
5 - Clapper Bolt. . . . . . . . . . . . PSN 62-634-1-112
7 - Clapper Latch . . . . . . . . . . PSN 92-470-1-005
8 - O-Ring . . . . . . . . . . . . . . . . PSN 62-578-1-306
9 - Clapper Latch
Stop . . . . . . . . . . . . . . . . PSN 92-470-1-054
10 - Diaphragm
Cover Bolt . . . . . . . . . . . PSN 62-039-1-207
11 - Diaphragm
Retainer . . . . . . . . . . . . . PSN 92-470-1-049
12 - Flange & Push
Rod Assembly . . . . . . . . PSN 92-470-1-040
13 - Diaphragm. . . . . . . . . . . . PSN 92-470-1-031
14 - Diaphragm
Cover . . . . . . . . . . . . . . . PSN 92-470-1-029
15 - Clapper Hinge
Pin . . . . . . . . . . . . . . . . . PSN 92-470-1-038
16 - Latch Hinge Pin. . . . . . . . PSN 92-470-1-023
17 - Handhole Cover . . . . . . . PSN 92-470-1-002
18 - Handhole
Cover Gasket. . . . . . . . . PSN 92-470-1-008
19 - Handhole
Cover Bolt . . . . . . . . . . . PSN 62-039-1-208
- Flurosilicone
Grease
1.5 grams. . . . . . . . . . . . PSN 92-302-1-641
57 grams . . . . . . . . . . . . PSN 92-302-1-642
6 inch (150 mm) Valve
2 - Clapper . . . . . . . . . . . . . . . PSN 92-470-1-025
3 - Clapper Facing . . . . . . . . . PSN 92-470-1-032
4 - Clapper Facing
Retainer . . . . . . . . . . . . . PSN 92-470-1-026
5 - Clapper Bolt. . . . . . . . . . . . PSN 62-634-1-113
7 - Clapper Latch . . . . . . . . . . PSN 92-470-1-030
8 - O-Ring . . . . . . . . . . . . . . . . PSN 62-578-1-306
9 - Clapper Latch
Stop . . . . . . . . . . . . . . . . PSN 92-470-1-054
10 - Diaphragm
Cover Bolt . . . . . . . . . . . PSN 62-039-1-207
11 - Diaphragm
Retainer . . . . . . . . . . . . . PSN 92-470-1-049
12 - Flange & Push
Rod Assembly . . . . . . . . PSN 92-470-1-040
13 - Diaphragm. . . . . . . . . . . . PSN 92-470-1-031
14 - Diaphragm
Cover . . . . . . . . . . . . . . . PSN 92-470-1-029
15 - Clapper Hinge
Pin . . . . . . . . . . . . . . . . . PSN 92-470-1-039
16 - Latch Hinge Pin. . . . . . . . PSN 92-470-1-023
17 - Handhole Cover . . . . . . . PSN 92-470-1-021
18 - Handhole
Cover Gasket. . . . . . . . . PSN 92-470-1-033
19 - Handhole
Cover Bolt . . . . . . . . . . . PSN 62-634-1-407
Replacement Trim Parts (Fig. D):
Specify: (description) for use with
Model F470H Horizontal Multimatic
Deluge Valve, PSN (specify).
1 - 300 lb. Water
Pressure
Gauge . . . . . . . . . . . . . . PSN 92-343-1-005
2 - 1/4" Gauge Test
Valve . . . . . . . . . . . . . . . PSN 46-005-1-002
3 - F180 Manual
Control Station . . . . . . . PSN 52-289-1-001
4 - 2" Angle Valve . . . . . . . . . PSN 46-048-1-009
5 - 1/2" Ball Valve . . . . . . . . . PSN 46-050-1-004
6 - 1/2" Swing
Check Valve . . . . . . . . . PSN 46-049-1-004
7 - 1/2" Spring
Loaded Check
Valve . . . . . . . . . . . . . . . PSN 92-322-1-002
8 - Priming Supply
Restriction. . . . . . . . . . . PSN 92-020-1-009
9 - 1/2" Y-Strainer . . . . . . . . . PSN 52-353-1-005
10 - F793 Automat-
ic Drain Valve . . . . . . . . PSN 52-793-1-004
11 - Drip Funnel
Support Plug. . . . . . . . . PSN 92-211-1-005
12 - Drip Funnel
Support . . . . . . . . . . . . . PSN 92-211-1-003
13 - Drip Funnel . . . . . . . . . . . PSN 92-343-1-007
14 - 3/32" Vent
Fitting . . . . . . . . . . . . . . PSN 92-032-1-002
15 - 1/2" Angle
Valve . . . . . . . . . . . . . . . PSN 46-048-1-004
D1 - B-1 Dry Pilot
Actuator. . . . . . . . . . . . . PSN 52-280-1-001
D2 - 250 lb. Air
Pressure
Gauge . . . . . . . . . . . . . . PSN 92-343-1-012
D3 - 1/4" Gauge
Test Valve. . . . . . . . . . . PSN 46-005-1-002
D4 - 1/2" Globe
Valve . . . . . . . . . . . . . . . PSN 46-047-1-004
D5 - 1/4" Pressure
Relief Valve. . . . . . . . . . PSN 92-343-1-020
E5 - 24VDC Sole-
noid Valve . . . . . . . . . . . PSN 52-287-1-024
WEIGHTS
The following are the nominal weights for
the valves and trim:
4" Model F470H Multimatic
DelugeValve............. 77lbs.(35kg)
6" Model F470H Multimatic
DelugeValve............. 111lbs.(49kg)
WetPilotActuationTrim....... 28lbs.(13kg)
DryPilotActuationTrim....... 41lbs.(18kg)
Electric Actuation Trim
With 24VDC Solenoid Valve. . 33 lbs. (15 kg)
® Reg.trademark of GRINNELL CORPORATION, 3 TYCO PARK, EXETER, NH 03833
OBSOLETE
Table of contents
Other Tyco Control Unit manuals
Popular Control Unit manuals by other brands

tau
tau 800LL quick start guide

Flowserve
Flowserve Valtek ShearStream SIL Safety Manual

National Instruments
National Instruments FBUS-HSE/H1 LD installation guide

Captron
Captron CHT4 Series Original operating instructions

Schmalz
Schmalz MATCH ABB IRB 1100 operating instructions

Texas Instruments
Texas Instruments LMK05318EVM user guide