manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco
  6. •
  7. Industrial Equipment
  8. •
  9. Tyco A User manual

Tyco A User manual

Model A
Pipe Line Strainer
Page 1 of 4 MAY 2021 TFP1640
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
Technical
Data
Approvals
UL Listed
ULC Listed
FM Approved
Sizes
3, 4, 6, 8 & 10 Inch
(DN80, DN100, DN150, DN200 & DN250)
Maximum Working Pressure
175 psi (12,1 bar)
Friction Loss and Equivalent
Lengths of Pipe
Refer to Graph A
Finish
Galvanized
Physical Characteristics
Body � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � Steel
Inlet Connection � � � � � � � � � � � � � � � � � � Cast Iron
Outlet Connection� � � � � � � � � � � � � � � � � Cast Iron
Flushing Connection Cast Iron
End Closure� � � � � � � � � � � � � � � � � � � � � � Cast Iron
Nuts and Bolts ����� Zinc Plated, Carbon Steel
Ring Gaskets� � � � � � � � � � � � � � � � � � SBR Rubber
Basket Assembly ���Stainless Steel or MONEL
Strainer Basket Screen
Strainer basket screen is perforated by
1/8 inch (3,2 mm) diameter holes spaced
to provide 40 percent open area�
Design
Criteria
Install TYCO Model A Pipe Line Strain-
ers horizontally with the flushing con-
nection oriented down (Ref� Figure 1)�
A saddle support accommodating the
body nominal pipe size (Ref� Figure 1)
must be located beneath the strainer
on center with the outlet� If outlet Angle
"J" is other than 180°, additional pro-
visions must be made for separate
support of the outlet piping�
General
Description
TYCO Model A Pipe Line Strainers are
designed for installation in the water
supply connection to automatic sprin-
kler, water spray deluge, foam-water
deluge, or standpipe fire protection
systems� The strainers are used where
it is necessary to protect spray nozzles,
sprinklers, or other type discharge
outlets from obstruction by debris that
may be present in the water supply�
The Model A Pipe Line Strainer is a
redesignation of the Gem Model A�
NOTICE
The Model A Pipe Line Strainers
described herein must be installed
and maintained in compliance with this
document, as well as with the applica-
ble standards of the NATIONAL FIRE
PROTECTION ASSOCIATION (NFPA),
in addition to the standards of any other
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
The strainer must be located with ade-
quate clearance to allow complete
removal of the basket assembly for
cleaning and maintenance (Ref� Figure
1)�
When planning installation, consider-
ation must be given to disposal of the
large quantities of water that may be
required to ensure thorough clean-
ing of the basket assembly during
flushing� Typically, the flushing con-
nection is fitted with an appropriately
sized, normally closed, valve and hose
connection�
Installation
The TYCO Model A Pipe Line Strainer
is shipped as an assembly� Threaded
inlet and flanged outlet and flushing
connections (Ref� Figure 1 and Table
A) are to be made in accordance with
accepted piping practices� Provisions
for the pipe saddle, basket removal
clearance, and strainer flushing must
be made in accordance with the
requirements described in the Design
Criteria section�
TFP1640
Page 2 of 4
Strainer
Figure
Number
Inlet
Connection
Nominal
Thread Size
Inches NPT
Outlet
Nominal
Pipe Size
ANSI
Inches
DN
Flushing
Nominal
Pipe Size
ANSI
Inches
DN
Dimensions in Inches (mm)
Inlet
Take-Out A B C D E
1260 -1
3 NPT
2-1/2
DN65 2-1/2
DN62
9/16
(14,3)
25-3/8
(644,5)
11-15/16
(303,2)
6-5/8
(168,3)
26
(660,4)
7
(177, 8 )
1260-2 3
DN80
7-1/2
(190,5)
1260-3
4 NPT
4
DN100 2-1/2
DN62
11/16
(17,5)
29-7/8
(758,8)
15-15/16
(404,8)
7-7/8
(200,0) 30
(762,0)
9
(228.6)
1260-4 6
DN150
8-3/8
(212,7)
11
(279,4)
1260-5 6 NPT 6
DN150
2-1/2
DN62
3/4
(19,1)
44-7/8
(113 9, 8)
24-5/16
(633,4)
9-7/16
(239,7)
45
(1143,0)
11
(279,4)
1260-6 8 NPT 8
DN200
4
DN100
13/16
(20,8)
65-1/4
(16 57,4)
43-5/16
(1100,1)
10 -15/16
(277,8)
66
(1676,4)
13-1/2
(342,9)
1260-7 10 NPT 10
DN250
4
DN100
3/8
(9,5)
83-7/8
(2130,4)
53-15/16
(1370,0)
13-1/4
(336,6)
84
(2133,6)
16
(406,4)
Strainer
Figure
Number
Inlet
Connection
Nominal
Thread Size
Inches NPT
Outlet
Nominal
Pipe Size
ANSI
Inches
DN
Dimensions in Inches (mm) Inlet and End
Closure Flange
Bolt and Nut
Inches
UNC x Length
Body
Nominal
Pipe Size**
ANSI
Inches Sch.
DN
Nominal
Weight
lb
(kg)
F G H I
1260 -1
3 NPT
2-1/2
DN65 11
(279,4)
7
(177, 8 )
6-1/4
(158,8)
8-1/2
(215,9) 3/4 x 3-1/2 6 Sch. 40
DN150
163
(73,9)
1260-2 3
DN80
1260-3
4 NPT
4
DN100 13-1/2
(342,9)
7
(177, 8 )
6
(152,4)
8-1/2
(215,9) 3/4 x 3-1/2 8 Sch. 30
DN200
250
(113 ,3)
1260-4 6
DN150
1260-5 6 NPT 6
DN150
16
(406,4)
7
(177, 8 )
8
(203,2)
11-1/8
(282,6) 7/8 x 3-3/4 10 Sch. 30
DN250
404
(183,2)
1260-6 8 NPT 8
DN200
19
(482,6)
9
(228,6)
8-5/8
(219,1)
12
(304,8) 7/8 x 3-3/4 12 Sch. 30
DN300
751
(340,6)
1260-7 10 NPT 10
DN250
23-1/2
(596,9)
9
(228,6)
12
(304,8)
12
(304,8) 1 x 5 16 Sch. 30
DN400
1200
(544,3)
*
*
*
A
B
F
CONNECTION
INLET
HANDLE
NUT
HANDLE
ROD
CONNECTION
**
OUTLET
D
ANGLE "J"
90° to 270°
(180° IS
STANDARD)
CLOSURE
END
OUTLET
CONNECTION
INLET
TAKE-OUT
END
CLOSURE
NUT
BOLT AND
CONNECTION
FLUSHING
(MINIMUM
FOR BASKET
REMOVAL)
C
ISCREEN
RING
E
RING GASKET
H G
BODY
SUPPORT FIXTURE
(10" STRAINER
ONLY)
FIGURE 1
MODEL A PIPE LINE STRAINERS
ASSEM B LY
* Flange drilling per ANSI B16.5 (Class 150), refer to Table A
** Support saddle accomodating body nominal pipe size required
TFP1640
Page 3 of 4
Hazen and Williams
Coefficient
Strainer Figure Number
Equivalent Length of Outlet Pipe, Feet (m)
1260-1 1260-2 1260-3 1260-4 1260-5 1260-6 1260-7
C = 100 6
(1,8)
13
(4,0)
18
(5,5)
91
( 27, 7 )
29
(8,8)
45
(13,7)
53
(16,2)
C = 120 8
(2,4)
17
(5,2)
24
( 7, 3)
133
(40,5)
41
(12,5)
61
(18,6)
75
(22,9)
Note: The approximate friction losses are based on the Hazen and Williams formula and expressed in equivalent
length of Schedule 40 pipe, calculated on the basis of ow rates typically used with each size strainer.
Dim.
Flange Connection Size
Nominal Dimensions*, Inches (mm)
2-1/2 Inch
(DN65)
3 Inch
(DN80)
4 Inch
(DN100)
6 Inch
(DN150)
8 Inch
(DN200)
10 Inch
(DN250)
A5.50
(139,7)
6.00
(152,4)
7.50
(190,5)
9.50
(241,3)
11.75
(298,5)
14.25
(362,0)
B0.75
(19,0)
0.75
(19,0)
0.75
(19,0)
0.88
(22,2)
0.88
(22,2)
1.00
(25,4)
Qty. N 4488812
• Flange drilling per ANSI B16.5 (Class 150)
200 400 1000 40002000600150
0,08
0,04
0,06
0,05
0,07
0,10
0,09
0,20
0,30
0,40
0,50
0,60
50002000 3000 1000070001000600 20000
6000
0.6
0.5
1.0
0.9
0.8
0.7
2.0
3.0
4.0
8.0
7.0
5.0
6.0
10.0
9.0
(1 GPM = 3,785 LPM)
FLOW RATE IN LITERS PER MINUTE (LPM)
FLOW RATE IN GALLONS PER MINUTE (GPM)
(1 PSI = 0,06895 BAR)
NOMINAL PRESSURE DROP IN BAR
NOMINAL PRESSURE DROP IN POUNDS PER SQUARE INCH (PSI)
1260-1
1260-2
1260-3
1260-4
1260-5
1260-6
1260-7
Dim. A
Bolt Circle
Diameter
Dim. B
Bolt Hole
Diameter
Qty. N
Number of
Bolt Holes
GRAPH A
MODEL A PIPE LINE STRAINERS
NOMINAL PRESSURE LOSS VS. FLOW AND EQUIVALENT LENGTH OF PIPE
TABLE A
MODEL A PIPE LINE STRAINERS
OUTLET AND FLUSHING CONNECTION FLANGE DRILLING DIMENSIONS
TFP1640
Page 4 of 4
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
MONEL is a registered trademark of Special Metals Corporation
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2021 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Care and
Maintenance
The following procedure and inspec-
tions must be performed as indicated,
in addition to any specific requirements
of the NFPA� Any impairment must be
immediately corrected�
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this action�
The owner is responsible for the inspec-
tion, testing, and maintenance of their
fire protection system and devices in
compliance with this document, as well
as with the applicable standards of the
NATIONAL FIRE PROTECTION ASSO-
CIATION (e�g�, NFPA 25), in addition to
the standards of any other authorities
having jurisdiction� Contact the install-
ing contractor or product manufacturer
with any questions�
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualified Inspection Service in accor-
dance with local requirements and/or
national code�
Maintenance Procedure
It is recommended that Model A strain-
ers be flushed at least annually� More
frequent flushing may be necessary
where water supplies are non-potable
and/or contain debris which could clog
1/3 or more of the basket open area�
Note: Never disassemble or remove
any strainer component without veri-
fying that the system is depressurized
and drained.
Strainers should be thoroughly flushed
clean after each system operation or
flow test and during routine inspections
as follows:
Step 1. Open flushing connection
valve (Ref� Design Criteria) allowing
flow until drain water runs clear� Close
valve�
Note: If heavy sediment in drain water
persists or there are indications that
all debris such as large stones may
not have been removed, basket must
be removed for cleaning; Proceed to
Step 2.
Step 2. Shut down and drain system�
Step 3. Remove end closure nuts and
bolts, flange and ring gasket�
Step 4. Withdraw basket in slow, hori-
zontal motion to minimize possibility of
debris falling from open inlet end into
body�
Step 5. Empty debris from basket and
clean body interior�
Step 6. Insert basket into body until
open inlet end is fully seated against
inlet connection flange�
Step 7. Install end closure gasket,
flange, and nuts and bolts� Gradually
tighten all nuts and bolts in cross-draw
sequence to apply uniform load around
flange�
Step 8. Ensure flushing connection
valve is closed�
Limited
Warranty
For warranty terms and conditions, visit
www�tyco-fire�com�
Ordering
Procedure
Contact your local distributor for avail-
ability� When placing an order, indi-
cate the full product name, including
description and part number (P/N)�
Standard Order Strainers
Specify: Standard Model A Pipe Line
Strainer, (specify) Inlet Size, Figure No�
(specify), P/N (specify):
1260-2 ����������������������52-270-1-011
1260-3 ����������������������52-270-1-013
1260-5 ����������������������52-270-1-015
1260-6 ����������������������52-270-1-016
1260-7 ����������������������52-270-1-017
Note: Standard order strainer features
inlet and outlet connections equal in
size, stainless steel basket assembly,
and outlet connection located at Angle
"J" 180° from flushing connection (Ref.
Figure 1). Adjusted outlet connection
available on request, refer to Special
Order Strainers.
Special Order Strainers
Specify: Standard Model A Pipe Line
Strainer, Figure No� (specify), (specify
Stainless Steel or MONEL) Basket
Assembly, (specify) Inlet Size, (specify)
Outlet Size, Outlet Angle "J" (specify
degrees)
Notes: Special order strainer features
any of the following: MONEL basket
assembly; inlet and outlet connec-
tions differing in size; outlet connec-
tion oriented at angle other than the
standard 180° Angle "J" (90° to 270°
counter-clockwise from flushing con-
nection when viewing strainer from end
closure). Ref. Figure 1.
It is recommended that orders for
strainers with special outlet locations
or angles be accompanied by sketches.
Part numbers are not specified for
special order strainers.
Replacement Parts
Specify: (specify inlet size) Model A
Strainer (specify part description),
P/N (specify):
Stainless Steel Basket Assembly
3 Inch �����������������������92-270-1-211
4 Inch �����������������������92-270-1-213
6 Inch �����������������������92-270-1-215
8 Inch �����������������������92-270-1-216
10 Inch ����������������������92-270-1-217
MONEL Basket Assembly
3 Inch �����������������������92-370-3-211
4 Inch �����������������������92-370-3-213
6 Inch �����������������������92-370-3-215
8 Inch �����������������������92-370-3-216
10 Inch ����������������������92-370-3-217
Ring Gasket
3 Inch �����������������������92-370-1-015
4 Inch �����������������������92-370-1-016
6 & 8 Inch ��������������������92-370 -1- 018
10 Inch ����������������������92-370 -1- 020
Note: Ring gaskets are identified per
strainer inlet size. Actual gasket sizes
vary per Body Nominal Pipe Sizes given
in Figure 1.

Other Tyco Industrial Equipment manuals

Tyco AMD-3 User manual

Tyco

Tyco AMD-3 User manual

Tyco KANTECH KTES-FBOX Operating and maintenance manual

Tyco

Tyco KANTECH KTES-FBOX Operating and maintenance manual

Tyco Deluge Red-E User manual

Tyco

Tyco Deluge Red-E User manual

Tyco 65 User manual

Tyco

Tyco 65 User manual

Tyco HV User manual

Tyco

Tyco HV User manual

Tyco GRINNELL F445 User manual

Tyco

Tyco GRINNELL F445 User manual

Tyco AQUAMIST Red-E Mist Supply Skid User manual

Tyco

Tyco AQUAMIST Red-E Mist Supply Skid User manual

Tyco SHB1 User manual

Tyco

Tyco SHB1 User manual

Tyco Rovalve S20 User manual

Tyco

Tyco Rovalve S20 User manual

Tyco TAV-D User manual

Tyco

Tyco TAV-D User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco DV-5A User manual

Tyco

Tyco DV-5A User manual

Tyco VIZOR User manual

Tyco

Tyco VIZOR User manual

Popular Industrial Equipment manuals by other brands

Graco ProMix PD2K Installation

Graco

Graco ProMix PD2K Installation

REO REOVIB MFS 368 operating instructions

REO

REO REOVIB MFS 368 operating instructions

Water Protec E 2.0 user guide

Water Protec

Water Protec E 2.0 user guide

SMC Networks CS2 125 Series Operation manual

SMC Networks

SMC Networks CS2 125 Series Operation manual

Rexnord Falk MCF 1135 Installation & maintenance

Rexnord

Rexnord Falk MCF 1135 Installation & maintenance

SICK V4000 operating instructions

SICK

SICK V4000 operating instructions

Feina SF70-1EH quick start guide

Feina

Feina SF70-1EH quick start guide

KSB 9972073510/200 Operating and maintenance instructions

KSB

KSB 9972073510/200 Operating and maintenance instructions

Toshiba JK Series instruction manual

Toshiba

Toshiba JK Series instruction manual

Lippert Curt 16574 installation manual

Lippert

Lippert Curt 16574 installation manual

schmersal AZM400Z-ST2-I2-2P2P-E Instructions for operation and use

schmersal

schmersal AZM400Z-ST2-I2-2P2P-E Instructions for operation and use

ABB HT611078 Operation manual

ABB

ABB HT611078 Operation manual

Urrea 862 User manual and warranty

Urrea

Urrea 862 User manual and warranty

LNS GT 112-E instruction manual

LNS

LNS GT 112-E instruction manual

Zimmer MGH8000 Installation and operating instructions

Zimmer

Zimmer MGH8000 Installation and operating instructions

Squibb-Taylor A120MAN Installation, operation & maintenance manual

Squibb-Taylor

Squibb-Taylor A120MAN Installation, operation & maintenance manual

Nexen Air Champ TSE-800-1 instructions

Nexen

Nexen Air Champ TSE-800-1 instructions

Humboldt H-4156M product manual

Humboldt

Humboldt H-4156M product manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.