
addition to the standards of any oth-
er authorities having jurisdiction. The
installing contractor or sprinkler man-
ufacturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected, test-
ed, and maintained by a qualified In-
spection Service in accordance with
local requirements and/or national
code.
Care and
Maintenance
The Series TY-FRL Sprinklers must
be maintained and serviced in accor-
dance with the following instructions:
NOTICE
Before closing a fire protection sys-
tem main control valve for mainte-
nance work on the fire protection sys-
tem that it controls, permission to shut
down the affected fire protection sys-
tem must be obtained from the prop-
er authorities and all personnel who
may be affected by this action must be
notified.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied or over-heated sprinklers must be
replaced.
Care must be exercised to avoid dam-
age to the sprinklers -before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be
replaced.
The owner is responsible for the in-
spection, testing, and maintenance
of their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Pro-
tection Association (e.g., NFPA 25), in
manufacturer’s warranties, as well as
possibly void the sprinkler’s Approvals
and/or Listings.
Installation
The Series TY-FRL Sprinklers must be
installed in accordance with the fol-
lowing instructions:
NOTICE
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuf-
ficient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
Step 1. The Series TY-FRL Horizontal
Sidewall Sprinklers must be installed
with their centerline of waterway par-
allel to the ceiling and perpendicu-
lar to the back wall surface. The word
“TOP” on the deflector must face up-
wards toward the ceiling.
Step 2. After installing an escutcheon
(as applicable) over the sprinkler pipe
threads and with pipe thread seal-
ant applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
9 Sprinkler Wrench (Ref. Figure 3).
With reference to Figure 1 or 2, the W-
Type 9 Sprinkler Wrench is to be ap-
plied to the wrench area.
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) per Table B.1.
Listed by Underwriters Laboratories, Inc. for use in Canada per Table B.2.
Approved by Factory Mutual Research Corporation (FM) per Table C.3.
Approved by the City of New York under MEA 112-04-E.4.
TABLE A
LABORATORY LISTINGS AND APPROVALS
(Refer to the Design Criteria Section)
KTYPE T EMP.
RATING
FRAME
COLOR
CODE
SPRINKLER FINISH
NATURAL
BRASS
CHROME
PLATED
5.6
1/2” NPT
EC HSW
(TY3322) 165º F/74ºC Unpainted 1, 2, 3, 4
8.0
3/4” NPT
EC HSW
( TY4 32 2 ) 165ºF/74º C Unpainted 1, 2, 3, 4
Page 2 of 6 TFP280