manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco
  6. •
  7. Irrigation System
  8. •
  9. Tyco ESFR-1 User manual

Tyco ESFR-1 User manual

Page 1 of 4 APRIL 2022 TFP318
Worldwide
Contacts
www.tyco-fire.com
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/model-esfr-1-
14-k-pen-early-sup-fast-res
Model ESFR-1
14.0 K-factor Pendent Sprinkler
Early Suppression, Fast Response
General
Description
The TYCO Model ESFR-1 Pendent
Sprinklers are Early Suppression,
Fast Response (ESFR) sprinklers with
a nominal K-factor of 14.0. They are
suppression-mode sprinklers that are
especially advantageous as a means of
eliminating the use of in-rack sprinklers
when protecting high-piled storage.
Model ESFR-1 Sprinklers are primarily
designed for protection of the following
storage arrangements:
•
Most encapsulated or non-encap-
sulated common materials including
cartoned, unexpanded plastics
•
Some storage arrangements of
rubber tires, roll paper, ammable
liquids
For more specific criteria, see
Table B and the applicable design
standard.
NOTICE
The Model ESFR-1 Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association (NFPA), in addition
to the standards of any other authorities
having jurisdiction, such as FM Global.
Failure to do so may impair the perfor-
mance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
In all cases, the appropriate NFPA,
FM Global installation standard, or
other applicable standard, must be
referenced to ensure applicability and
to obtain complete installation guide-
lines. The general guidelines in this
data sheet are not intended to provide
complete installation criteria.
Sprinkler
Identification
Number (SIN)
See Table A
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
VdS Approved
NYC Approved under MEA 356-01-E
LPCB Approved (Cert. Nos. 094b and
007l)
EAC Approved
Finish
Natural Brass
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Compression Screw . . . . . . . . . . Stainless Steel
Hook . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL
Link Assembly. . . . . . . . . . . . . . . . Solder, Nickel
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Ejection Spring . . . . . . . . . . . . . . . . . . INCONEL
Sealing Assembly ..Beryllium Nickel w/TEFLON
Additional Technical Data
See Table A
TFP318
Page 2 of 4
Operation
The fusible link assembly is com-
prised of two link halves that are
joined together by a thin layer of
solder. When the rated temperature is
reached, the solder melts and the two
link halves separate, activating the
sprinkler and flowing water.
Item Description
Sprinkler Identication Number (SIN) TY6226
TY6226 is a re-designation for Central SIN C6226, Gem
SIN G8440, and Star SIN S8000.
K-factor, gpm/psi½(Lpm/bar½) 14.0 gpm/psi1/2 (201,6 lpm/bar½)
Temperature Rating ˚F (˚C) 165˚F (74˚C)
212˚F (100˚C)
Thread Size 3/4 in. NPT
Sprinkler Orientation Pendent
Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)
Components:
(12,7 mm)
NOMINAL
MAKE-IN
1/2"
FLATS
WRENCH
3-9/16"
(90,5 mm)
1-7/8"
(47,6 mm)
SENSING
ELEMENT
THERMAL
1-1/2"
(38,1 mm)
TEMPERATURE
RATING
Screw
Frame
Deector
Compression
Assembly
Button
Sealing
Ejection Spring
Link Assembly
-
9-
6
8
7-
-
-
3
5
4-
-
1
2-
-
Strut
Hook
3/4" NPT
2
3
4
5
8
9
6
7
1
FIGURE 1
MODEL ESFR-1 PENDENT SPRINKLER, 14.0K
EARLY SUPPRESSION, FAST RESPONSE
TABLE A
MODEL ESFR-1 PENDENT SPRINKLER
TECHNICAL DATA
TFP318
Page 3 of 4
Design
Criteria
The following general guidelines pro-
vided for the TYCO ESFR-1 Sprinklers
can be used for quick reference.
NOTICE
The National Fire Protection Associa-
tion (NFPA) and FM Global (FM Approv-
als) provide installation standards that
must be used to properly design an
automatic sprinkler system utilizing
Early Suppression, Fast Response
(ESFR) Sprinklers. The guidelines pro-
vided by NFPA and FM may differ; con-
sequently, the appropriate standard
must be used for a given installation.
In all cases, the appropriate NFPA or
FM installation standard must be ref-
erenced to assure applicability and to
obtain complete installation guidelines,
since the following general guidelines
are not intended to provide complete
installation criteria.
Roof Construction
Unobstructed or obstructed construc-
tion, such as smooth ceiling, bar joists,
beam and girder.
Where the depths of solid structural
members, such as beams and stem,
exceed 12 in. (302 mm), install ESFR
Sprinklers in each channel formed by
the structural members.
Ceiling Slope
Maximum 2 in. rise for 12 in. run (16.7%)
Maximum Coverage Area
100 ft2(9,3 m2)
Minimum Coverage Area
64 ft2(5,8 m2) per
NFPA 13 and FM Global 2-0
Maximum Spacing
• 12 ft (3,7 m) for building heights up
to 30 ft (9,1 m)
• 10 ft (3,1 m) for building heights
greater than 30 ft (9,1 m)
Minimum Spacing
8 ft (2,4 m)
Minimum Clearance to Commodity
36 in. (914 mm)
NFPA
Deflector-to-Ceiling Distance
6 in. to 14 in. (152 mm to 356 mm)
FM Global
Centerline of Thermal Sensing
Element-to-Ceiling Distance
Refer to FM Global 2-0 for Storage
Sprinklers.
Storage Type NFPA FM Global
Sprinkler Type ESFR Storage
Response Type QR QR
System Type Wet Wet
Temperature Rating ºF (ºC) 165 ºF (74 ºC)
212 ºF (100 ºC)
165 ºF (74 ºC)
212 ºF (100 ºC)
Open Frame (i.e., no solid shelves) Single, Double, Multiple-
Row, or Portable Rack Storage of Class I-IV and Group A or
B Plastics
Refer to NFPA 13 Refer to FM 2-0 and 8-9
Solid Pile or Palletized Storage of Class I-IV and Group A or
B Plastics Refer to NFPA 13 Refer to FM 2-0 and 8-9
Idle Pallet Storage Refer to NFPA 13 Refer to FM 2-0, 8-9, and 8-24
Rubber Tire Storage Refer to NFPA 13 Refer to FM 2-0 and 8-3
Roll Paper Storage
(Refer to the Standard) Refer to NFPA 13 Refer to FM 8-21
Flammable/Ignitable Liquid Storage
(Refer to the Standard) Refer to NFPA 30 Refer to FM 7-29
Aerosol Storage
(Refer to the Standard) Refer to NFPA 30B Refer to FM 7-31
Automotive Components in Portable Racks
(Control mode only; refer to the Standard) N/A N/A
N/A – Not Applicable
TABLE B
MODEL ESFR-1 PENDENT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
TFP318
Page 4 of 4
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
MONEL and INCONEL are registered trademarks of Special Metals Corporation;
TEFLON is a trademark of The Chemours Company FC, LLC
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Installation
TYCO Model ESFR-1 Early Suppres-
sion, Fast Response 14.0K Pendent
Sprinklers must be installed in accor-
dance with this section.
NOTICE
Damage to the fusible Link Assem-
bly during installation can be avoided
by handling the sprinkler by the frame
arms only and by using the appropri-
ate sprinkler wrench. Do not apply
pressure to the fusible Link Assembly
Failure to do so can lead to an unstable
link assembly and premature activation
of the sprinkler. Damaged sprinklers
must be replaced.
A leak-tight 3/4 in. NPT sprinkler joint
should be obtained by applying a min-
imum-to-maximum torque of 10 to 20
lb-ft (13,4 to 26,8 N∙m). Higher levels
of torque can distort the sprinkler inlet
with consequent leakage or impairment
of the sprinkler.
Note: Install the Model ESFR-1
Pendent Sprinkler in the pendent posi-
tion as shown in Figure 2.
Step 1. With pipe thread sealant
applied, hand-tighten the sprinkler into
the sprinkler fitting. Do not apply pres-
sure to the Link Assembly, and handle
the Model ESFR-1 Sprinkler only by the
Frame arms.
Step 2. Wrench-tighten the Model
ESFR-1 Sprinkler using only the W-Type
2 Sprinkler Wrench as shown in Figure
2, and by fully engaging (seating) the
wrench on the sprinkler wrench flats as
shown in Figure 1.
Step 3. After installation, inspect
the Link Assembly of each Model
ESFR-1 Sprinkler for damage. In par-
ticular, verify that the Link Assembly
and Hook are positioned as shown in
Figure 1, and that the Link Assembly
is not bent, creased, or forced out of
normal position in any way. Replace
damaged sprinklers.
Care and
Maintenance
TYCO Model ESFR-1 Early Suppres-
sion, Fast Response 14.0K Pendent
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. For more informa-
tion, see the Installation section.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associ-
ation, such as NFPA 25, in addition to
the standards of any authorities having
jurisdiction. Contact the installing con-
tractor or product manufacturer with
any questions.
Automatic sprinkler systems are
recommended to be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and part number
(P/N).
Sprinkler Assemblies
Specify: Model ESFR-1 Early Suppres-
sion, Fast Response 14.0K Pendent
Sprinklers (TY6226), (specify tempera-
ture rating), with Natural Brass finish,
P/N (specify):
165 °F (74 °C) .................58- 440-1-165
212 °F (100 °C) ................58- 440-1-214
Sprinkler Wrench
Specify: W-Type 2 Sprinkler Wrench,
P/N 56-872-1- 0 01
"FITTING SIDE"
FITTING
TOWARDS SPRINKLER
RECESS
WRENCH
FIGURE 2
W-T YPE 2
SPRINKLER WRENCH

Other Tyco Irrigation System manuals

Tyco DS-2 Series User manual

Tyco

Tyco DS-2 Series User manual

Tyco TY-FRL Series User manual

Tyco

Tyco TY-FRL Series User manual

Tyco RAPID RESPONSE Series User manual

Tyco

Tyco RAPID RESPONSE Series User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco F690 User manual

Tyco

Tyco F690 User manual

Tyco DSC WTK5504 User manual

Tyco

Tyco DSC WTK5504 User manual

Tyco ESFR-1 User manual

Tyco

Tyco ESFR-1 User manual

Tyco ELO-231FRB Series User manual

Tyco

Tyco ELO-231FRB Series User manual

Tyco FASTFLEX YN25 User manual

Tyco

Tyco FASTFLEX YN25 User manual

Tyco RapidResponse SIN TY4334 Instruction Manual

Tyco

Tyco RapidResponse SIN TY4334 Instruction Manual

Tyco DS-1 Series User manual

Tyco

Tyco DS-1 Series User manual

Tyco DS-2 Series User manual

Tyco

Tyco DS-2 Series User manual

Tyco ESFR-17 User manual

Tyco

Tyco ESFR-17 User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco EC-11 Series User manual

Tyco

Tyco EC-11 Series User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco G1 User manual

Tyco

Tyco G1 User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco ESFR-14 User manual

Tyco

Tyco ESFR-14 User manual

Tyco DS-1 Series User manual

Tyco

Tyco DS-1 Series User manual

Tyco LD User manual

Tyco

Tyco LD User manual

Tyco Royal Flush II User manual

Tyco

Tyco Royal Flush II User manual

Tyco TFP MAX User manual

Tyco

Tyco TFP MAX User manual

Popular Irrigation System manuals by other brands

ASC FLEXHEAD Installation and Maintenance

ASC

ASC FLEXHEAD Installation and Maintenance

Hunter ST Series owner's manual

Hunter

Hunter ST Series owner's manual

Task Force Tips Masterstream Series INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

Task Force Tips

Task Force Tips Masterstream Series INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

Reliable G4 manual

Reliable

Reliable G4 manual

Victaulic VS1 Series installation instructions

Victaulic

Victaulic VS1 Series installation instructions

Rain Bird LG3HE Installation & operating guide

Rain Bird

Rain Bird LG3HE Installation & operating guide

SNOWJOE AQUAJOE AJ-IS10WB-RM manual

SNOWJOE

SNOWJOE AQUAJOE AJ-IS10WB-RM manual

Johnson Controls tyco TFP PH5 manual

Johnson Controls

Johnson Controls tyco TFP PH5 manual

SNOWJOE AQUAJOE AJ-OSPR20 manual

SNOWJOE

SNOWJOE AQUAJOE AJ-OSPR20 manual

Rain Bird wtd 2900 Operation guide

Rain Bird

Rain Bird wtd 2900 Operation guide

Reliable F1FR56 quick start guide

Reliable

Reliable F1FR56 quick start guide

Reliable HL22 Bulletin

Reliable

Reliable HL22 Bulletin

Viking HORIZON H-3 Technical data

Viking

Viking HORIZON H-3 Technical data

Gardena aquaBloom Set Operator's manual

Gardena

Gardena aquaBloom Set Operator's manual

Johnson Controls tyco ILLUSION manual

Johnson Controls

Johnson Controls tyco ILLUSION manual

Reliable DH56 HSW-PL quick start guide

Reliable

Reliable DH56 HSW-PL quick start guide

SNOWJOE AQUAJOE SJI-OMS20 manual

SNOWJOE

SNOWJOE AQUAJOE SJI-OMS20 manual

K-Rain KRX6 manual

K-Rain

K-Rain KRX6 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.