Series EC-8C – 8.0 K-factor Special Application, Quick
Response Pendent and Recessed Pendent Sprinklers for
Corridors and Hallways of Light Hazard Occupancies
Page 1 of 4 APRIL 2021 TFP226
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
Discharge Coefficients
K=8.0 gpm/psi½
(115 ,2 lp m /bar½)
Temperature Ratings
155°F ( 68°C)
200°F (93°C)
Finish
Sprinkler: Natural Brass, Signal White
Polyester Coated, Pure White Polyester
Coated, Jet Black Polyester Coated, or
Chrome Plated
Recessed Escutcheon: Natural Brass,
Signal White, Pure White, Jet Black,
Chrome Plated
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button . . . . . . . . . . . . . . . . . . . . . . Brass/Copper
Sealing Assembly ..Beryllium Nickel w/TEFLON
Bulb .....................Glass (3 mm dia.)
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
General
Description
The EC-8C 8.0 K-factor Special Appli-
cation, Quick Response Pendent and
Recessed Pendent Sprinklers are UL
Listed for Light Hazard Occupancies
and were specifically designed for use
in long, narrow spaces such as corri-
dors or hallways with a maximum cov-
erage area of 28 ft by 10 ft (8,5 m x 3,1
m). Fewer sprinklers and lower system
pressure demands are required as
compared to the traditional extended
coverage sprinklers. Series EC-8C
sprinklers are intended for use in auto-
matic sprinkler systems designed in
accordance per NFPA 13.
The recessed version of the Series
EC-8C, Pendent Sprinkler intended
for use in areas with a finished ceiling,
uses either the two-piece Style 30 or
40 Recessed Escutcheon. The Style 30
Recessed Escutcheon provides up
to 1/2 in. (12,7 mm) of total adjust-
ment from the flush pendent posi-
tion, whereas, the Style 40 provides
3/4 in. (19,1 mm) of vertical adjustment
from the flush pendent position. The
adjustment provided by the Recessed
Escutcheons reduces the accuracy to
which the fixed pipe drops to the sprin-
klers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the life
of copper alloy sprinklers beyond that
which would otherwise be obtained
when exposed to corrosive atmo-
spheres. Although corrosion resistant
coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitabil-
ity of these corrosion resistant coatings
for any given corrosive environment.
The effects of ambient temperature,
concentration of chemicals, and gas/
chemical velocity, should be consid-
ered, as a minimum, along with the cor-
rosive nature of the chemical to which
the sprinklers will be exposed.
NOTICE
The Series EC-8C Pendent Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the
applicable standards of the NATIONAL
FIRE PROTECTION ASSOCIATION, in
addition to the standards of any other
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number (SIN)
T Y42 82 ............ Pendent, 8.0K
Technical
Data
Approvals
UL Listed
Note: Sprinklers with a polyester finish
are UL Listed as corrosion-resistant
sprinklers.
Maximum Working Pressure
250 psi (17,2 bar)
Pipe Thread Connection
3/4 in. NPT
TFP226
Page 2 of 4
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and flow water.
Design
Criteria
The EC-8C 8.0 K-factor Special Appli-
cation, Quick Response Pendent and
Recessed Pendent Sprinklers must
only be installed in accordance with
the applicable UL Listing requirements
as indicated below. Only the Style 30 or
40 Recessed Escutcheon is to be used
for recessed installation, as applicable.
UL Listing Requirements
1. The Series EC-8C Pendent Sprin-
klers may be used for the coverage
areas shown in Table A, based on
maintaining the minimum specied
ow rate as a function of coverage
area for all of the sprinklers in the
design area.
2. With respect to heat sensitivity,
the Series EC-8C Pendent Sprin-
klers can be used with unobstruct-
ed construction consisting of at,
smooth ceilings (including bar
joists) with a maximum pitch of one
in six as dened and permitted by
NFPA 13.
3. The minimum allowable spacing
between the Series EC-8C Pendent
Sprinklers, to prevent cold sol-
dering, is 12 ft (3,7 m) in the 28 ft
(8,5 m) long spray direction.
4. The Series EC-8C Pendent Sprin-
klers are not to be installed with the
short spray direction, 8 ft (2,4 m) or
10 ft (3,1 m), oriented towards an-
other Series EC-8C Pendent Sprin-
kler’s short spray direction (See
Figure 6).
5. The Series EC-8C Pendent Sprin-
klers are to be installed in accor-
dance with all other requirements
of NFPA 13 for extended coverage
pendent sprinklers.
Installation
The Series EC-8C 8.0 K-factor Special
Application, Quick Response Pendent
and Recessed Pendent Sprinklers
must be installed in accordance with
this section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm).
A leak tight 3/4 in. NPT sprinkler joint
should be obtained with a torque of
10 to 20 lb-ft (13,6 to 27,1 N·m). Higher
levels of torque may distort the sprin-
kler inlet with consequent leakage or
impairment of the sprinkler.
Do not attempt to compensate for
insufficient adjustment of an escutch-
eon plate by under-or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Step 1. The sprinkler must be installed
with the deflector parallel to the mount-
ing surface. Pendent sprinklers must be
installed in the pendent position. The
deflector is marked with “<-28 FEET
(8,5 M)->” to indicate the direction of
the 28 ft (8,5 m) coverage length. The
frame arms do not need to be aligned
parallel to the sprinkler pipe.
Step 2. After installing the Style 30 or
40 mounting plate (or other escutch-
eon, as applicable) over the sprinkler
pipe threads, and with pipe thread
sealant applied to the pipe threads,
hand tighten the sprinkler into the
sprinkler fitting.
Step 3. Wrench tighten the deflector so
that the marking “<-28 FEET (8,5 M)->”
on the deflector is in the direction of
the 28 ft (8,5 m) coverage length. The
frame arms do not need to be aligned
parallel to the sprinkler pipe. Use
only the W-Type 6 (End “B”) Sprinkler
Wrench or with a recessed escutcheon
the W-Type 7 Sprinkler Wrench. The
wrench recess of the applicable sprin-
kler wrench (See Figures 4 and 5) is to
be applied to the sprinkler wrench flats
(See Figure 1).
Description Coverage
Area Flow
Rate Pressure
TY4282 (K=8.0)
Pendent
28 ft x 8 ft
(8,5 m x 2,4 m)
23 gpm
(87,1 l p m)
8.3 psi
(0,6 bar)
28 ft x 10 ft
(8,5 m x 3,1 m)
28 gpm
(106 lpm)
12.3 psi
(0,9 bar)
Note: For coverage area dimensions less than or between those listed, use the minimum ow required for
the next highest coverage area.
-
-
-
-
-
-
4
2
3
1
6
5
Bulb
Button
Frame
Deector
Components:
Temperature
rating indicated
on Deector
Sealing
Assembly
Compression
Screw
*
*
*
RECESSED PENDENTPENDENTCROSS SECTION
1/2" (12,7 mm)
NOMINAL MAKE-IN
ESCUTCHEON
PLATE SEATING
SURFACE
STYLE 30 or 40
RECESSED
ESCUTCHEON
WRENCH
FLATS
6
5
3
1
2
4
2-7/8" (73,0 mm) DIA.
3/4" NPT
1-7/16"
(36,5 mm)
2-1/4"
(57,2 mm)
FIGURE 1
SERIES EC-8C (TY4282)
SPECIAL APPLICATION PENDENT AND RECESSED PENDENT SPRINKLER
TABLE A
FLOW CRITERIA FOR UL LISTING
OF SERIES EC-8C SPRINKLERS
TFP226
Page 3 of 4
2-1/4" DIA.
(57,2 mm)
2-7/8" DIA.
(73,0 mm)
MOUNTING
SURFACE
FACE OF
SPRINKLER
FITTING
MOUNTING
PLATE
1/8"
(3,2 mm)
CLOSURE
1/2" (12,7 mm)
FLUSH
TY4282 1-1/2" (38,1 mm)
1" (25,4 mm)
3/8±1/4"
(9,5±6,4 mm) 2-1/4" DIA.
(57,2 mm)
2-7/8" DIA.
(73,0 mm)
MOUNTING
SURFACE
FACE OF
SPRINKLER
FITTING
MOUNTING
PLATE
1/8"
(3,2 mm)
CLOSURE 1-1/2" (38,1 mm)
3/4" (19,1 mm)
3/4" (19,1 mm)
FLUSH
TY4282
1/2±3/8"
(12,7±9,5 mm)
WRENCH RECESS
(END "B" USED
FOR TY4282)
RECESS
WRENCH
WITH SPRINKLER
ENGAGEMENT
IN TO ENSURE
WRENCHING AREA
PUSH WRENCH
*
Extended Coverage Sprinkler*
Series EC-8C or Model RFII-C Sprinkler (Orient Long
Standard Coverage Sprinkler*
area adjacent to Series EC-8C Sprinkler:
Sprinklers permitted in Short Spray Direction
Spray Direction parallel to Short Spray Direction only)
Maintain spacing requirements per
Standard or Extended Coverage sprinkler
-
-
-
Extended Coverage Sprinkler
Series EC-8C or Model RFII-C Sprinkler
Standard Coverage Sprinkler
area adjacent to Series EC-8C Sprinkler:
Sprinklers permitted in Long Spray Direction
-
-
-
(Orient Long or Short Spray Direction)
SHORT SPRAY
DIRECTION
LONG SPRAY
DIRECTION
SERIES EC-8C
SPRINKLER
SHORT SPRAY
DIRECTION
LONG SPRAY
DIRECTION
FIGURE 2
SERIES EC-8C RECESSED PENDENT SPRINKLER
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
FIGURE 3
SERIES EC-8C RECESSED PENDENT SPRINKLER
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
FIGURE 4
W-TYPE 6
SPRINKLER WRENCH
FIGURE 5
W-TYPE 7 RECESSED
SPRINKLER WRENCH
FIGURE 6
SPRINKLERS ADJACENT TO
SERIES EC-8C SPRINKLER
TFP226
Page 4 of 4
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
MONEL and INCONEL are registered trademarks of Special Metals Corporation; LOCTITE is a registered trademark of Henkel Corporation;
RILSAN is a registered trademark of Arkema, Inc.; TEFLON is a trademark of The Chemours Company FC, LLC; DOW CORNING NO. 7 is a registered trademark of Dow Corning Corporation
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2021 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Care and
Maintenance
The EC-8C 8.0 K-factor Special Appli-
cation, Quick Response Pendent and
Recessed Pendent Sprinklers must be
maintained and serviced in accordance
with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection systems must
be obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. See Installa-
tion Section.
Frequent visual inspections are rec-
ommended to be initially performed
for corrosion resistant coated sprin-
klers, after the installation has been
completed, to verify the integrity of the
corrosion resistant coating. Thereafter,
annual inspections per NFPA 25 should
suffice; however, instead of inspecting
from the floor level, a random sampling
of close-up visual inspections should
be made, so as to better determine the
exact sprinkler condition and the long
term integrity of the corrosion resistant
coating, as it may be affected by the
corrosive conditions present.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION, such as NFPA 25, in
addition to the standards of any other
authorities having jurisdiction. The
installing contractor or sprinkler man-
ufacturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assembly
Specify: Series EC-8C (TY4282),
K=8.0, Special Application Quick
Response, Pendent Sprinkler, (specify)
temperature rating, (specify) finish, P/N
(specify):
155°F (68°C)
Natural Brass ................. 57-351-1-155
Signal White (RAL9003)
Polyester ....................57-351-4-155
Chrome Plated ................57-351-9-155
Pure White (RAL9010)
Polyester ....................57-351-3-155
Jet Black (RAL9005)
Polyester ....................57-351-5-155
200°F (93°C)
Natural Brass .................57-351-1-200
Signal White (RAL9003)
Polyester ....................57-351-4-200
Chrome Plated ................57-351-9-200
Pure White (RAL9010)
Polyester ....................57-351-3-200
Jet Black (RAL9005)
Polyester ....................57-351-5-200
Recessed Escutcheon
Specify: Style (30 or 40) Recessed
Escutcheon with (specify*) finish, P/N
(specify*)
*Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Recessed Sprinkler
Wrench, P/N 56-850-4-001

This manual suits for next models

1

Other Tyco Irrigation System manuals

Tyco Rapidresponse LFII Series User manual

Tyco

Tyco Rapidresponse LFII Series User manual

Tyco CC2 User manual

Tyco

Tyco CC2 User manual

Tyco Central ESFR-25/WilFlow User manual

Tyco

Tyco Central ESFR-25/WilFlow User manual

Tyco TY720 User manual

Tyco

Tyco TY720 User manual

Tyco TY-L Series User manual

Tyco

Tyco TY-L Series User manual

Tyco TY-QRF-5.6 User manual

Tyco

Tyco TY-QRF-5.6 User manual

Tyco ESFR-1 User manual

Tyco

Tyco ESFR-1 User manual

Tyco ESFR-22 User manual

Tyco

Tyco ESFR-22 User manual

Tyco RAVEN Institutional TY3281 User manual

Tyco

Tyco RAVEN Institutional TY3281 User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco DS-2 Series User manual

Tyco

Tyco DS-2 Series User manual

Tyco Rapidresponse LFII Series User manual

Tyco

Tyco Rapidresponse LFII Series User manual

Tyco K17-231 User manual

Tyco

Tyco K17-231 User manual

Tyco TY3201 User manual

Tyco

Tyco TY3201 User manual

Tyco DS-2 Series User manual

Tyco

Tyco DS-2 Series User manual

Tyco RFII Series User manual

Tyco

Tyco RFII Series User manual

Tyco Rapidresponse LFII Series User manual

Tyco

Tyco Rapidresponse LFII Series User manual

Tyco Rapidresponse LFII Series Operating and maintenance instructions

Tyco

Tyco Rapidresponse LFII Series Operating and maintenance instructions

Tyco rapid response LFII Series User manual

Tyco

Tyco rapid response LFII Series User manual

Tyco Ultra K17 User manual

Tyco

Tyco Ultra K17 User manual

Tyco TY-FRL Series User manual

Tyco

Tyco TY-FRL Series User manual

Tyco LFII Series User manual

Tyco

Tyco LFII Series User manual

Tyco K17-231 User manual

Tyco

Tyco K17-231 User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Popular Irrigation System manuals by other brands

Hunter Institutional Series quick start guide

Hunter

Hunter Institutional Series quick start guide

Elgo MDS8 installation guide

Elgo

Elgo MDS8 installation guide

Johnson Controls tyco EC-25 manual

Johnson Controls

Johnson Controls tyco EC-25 manual

Komet Trigon 105 Technical manual

Komet

Komet Trigon 105 Technical manual

Tyco Fire Product Star SuperNova S120 instruction manual

Tyco Fire Product

Tyco Fire Product Star SuperNova S120 instruction manual

Elsner Jardana Installation, setting, operation

Elsner

Elsner Jardana Installation, setting, operation

Viking MICROFAST VK311 Technical data

Viking

Viking MICROFAST VK311 Technical data

IrriGreen 2 Quick install guide

IrriGreen

IrriGreen 2 Quick install guide

Holman co1606 user guide

Holman

Holman co1606 user guide

Reliable DH56 HSW-PL manual

Reliable

Reliable DH56 HSW-PL manual

Viking VK535 Technical data

Viking

Viking VK535 Technical data

Viking D-1 Sprinkler Guard Technical data

Viking

Viking D-1 Sprinkler Guard Technical data

Viking VK192 Technical data

Viking

Viking VK192 Technical data

Gardena OS 140 operating instructions

Gardena

Gardena OS 140 operating instructions

Viking VK3521 Technical data

Viking

Viking VK3521 Technical data

Rain elite 9 VDC instructions

Rain

Rain elite 9 VDC instructions

Task Force Tips FM Series INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

Task Force Tips

Task Force Tips FM Series INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

Elgo AS2 installation guide

Elgo

Elgo AS2 installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.