Tyco Issue D Quartzoid TY3191 User manual

General
Description
The Tyco®Issue D, 5.6 and 8.0 K-fac-
tor, Upright and Pendent Sprinklers
described in this data sheet are stand-
ard response - standard coverage, 11
mm glass bulb type spray sprinklers
designed for use in light, ordinary, or
extra hazard, commercial occupan-
cies where high ambient temperatures
may be encountered.
Corrosion-resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion-resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
NOTICE
The Issue D Sprinklers described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the
standards of any authorities having ju-
risdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TY3191 - Upright 5.6K, 1/2" NPT
TY3296 - Pendent 5.6K, 1/2" NPT
TY4191 - Upright 8.0K, 3/4" NPT
TY4292 - Pendent 8.0K, 3/4" NPT
TY3191 is a redesignation for G1036.
TY3296 is a redesignation for G1040.
TY4191 is a redesignation for G1136.
TY4292 is a redesignation for G1140.
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
(Refer to Table A for complete ap-
proval information including corrosion
resistant status.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 5.6 GPM/psi1/2 (80,6 LPM/bar1/2)
K = 8.0 GPM/psi1/2 (115,2 LPM/bar1/2)
Temperature Ratings
Refer to Table A.
Finishes
Refer to Table A.
Physical Characteristics
Frame . . . . . . . . . . . . Bronze
Deflector . . . . . . . . . . . Bronze
Bulb (11mm dia.) . . . . . . . Glass
Bulb Seats . . . . . . . . . . Bronze
Spacer . . . . . . . . . . . . Bronze
Pin . . . . . . . . . . . . . . Bronze
Button . . . . . . . . . . . . Bronze
Spring Plates . . . . . . . . Inconel
Gaskets . . . . . . . . . . . Copper
Issue D Quartzoid
®
— 5.6 and 8.0 K-factor
High Temperature, Upright and Pendent Sprinklers
Standard Response, Standard Coverage
Page 1 of 4 TFP690
SEPTEMBER 2009
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

FIGURE 1
STANDARD RESPONSE ISSUE D UPRIGHT (TY3191) AND PENDENT (TY3296) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
FIGURE 2
STANDARD RESPONSE ISSUE D UPRIGHT (TY4191) AND PENDENT (TY4292) SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT
650°F/343°C
650°F/343°C
(12,7 mm)
NOMINAL
UPRIGHT
PlatesSprinkler;
1/2"
(74,6 mm)
CROSS SECTION
NOMINAL
MAKE-IN
(12,7 mm)
MAKE-IN
1/2"
PENDENT
(79,4 mm)
5
3-1/8"
4
3
11
SSP-1 for
Upper Bulb
Lower Bulb
Temperature rating
is indicated on Lower
Bulb Seat.
*
Seat
2
*
-
3
4-
7
8
9
Sprinkler
Seat
Pendent
Lower
Bulb
Gasket
Gasket
Bulb
-
9
-
-
10
11
2-15/16" 10
NPT
3/4"
Components:
SSU-3 for
-
2
1
6
-
1
Upright
Deflector,
Frame
Spring
Spacer
Button
Pin
-
7
-
8
-
6
-
5
WRENCHING AREA
UPRIGHT CROSS SECTIONPENDENT
2-15/16"
(74,6 mm)
(79,4 mm)
3-1/8"
1
6
7
8
9
2
10
5
3
11
4
NPT
1/2"
NOMINAL
MAKE-IN
7/16"
(11,1 mm)
(11,1 mm)
NOMINAL
MAKE-IN
7/16"
Temperature rating
is indicated on Lower
*
650°F/343°C
650°F/343°C
Upright
Pendent
Upper Bulb
Spring
-Spacer7
-
-
-
-
10
11
8
9
Gasket
Bulb
Gasket
Lower
-
-
-
5
6
3
Button
Pin
SSP-1 for
-
-
Components:
1
2
Frame
Deflector,
SSU-3 for
Sprinkler;
Sprinkler
*
Seat
Plates
Bulb
Bulb Seat.
4-Lower Bulb
Seat
WRENCHING AREA
TFP690
Page2of4

Operation
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Tyco®Issue D Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (for exam-
ple, UL Listing is based on the require-
ments of NFPA 13, and FM Approval
is based on the requirements of FM
Loss Prevention Data Sheets).
Installation
The Issue D Sprinklers must be in-
stalled in accordance with the follow-
ing instructions.
NOTICE
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/4 inch
(6,4 mm).
Obtain a leak-tight 1/2 inch NPT sprin-
kler joint by applying a minimum-to-
maximum torque of 7 to 14 ft.lbs. (9,5
to 19,0 Nm). Obtain a leak-tight 3/4
inch NPT sprinkler joint by applying a
minimum-to-maximum torque of 10 to
20 ft.lbs. (13,4 to 26,8 Nm). Higher
levels of torque can distort the sprin-
kler inlet and cause leakage or impair-
ment of the sprinkler.
Step 1. Install pendent sprinklers in
the pendent position and upright sprin-
klers in the upright position.
Step 2. With pipe-thread sealant ap-
plied to the pipe threads, hand-tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
11 Sprinkler Wrench (refer to Figure
3). With reference to Figures 1 and 2,
apply the W-Type 11 Sprinkler Wrench
to the wrenching area.
Care and
Maintenance
The Tyco®Issue D Sprinklers must be
maintained and serviced in accord-
ance with the following instructions.
NOTICE
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, obtain permission to shut
down the affected fire protection sys-
tem from the proper authorities and
notify all personnel who may be af-
fected by this action.
Exercise care to avoid damage to the
sprinklers before, during, and after in-
stallation. Never paint, plate, coat, or
otherwise alter automatic sprinklers
after they leave the factory.
Replace sprinklers that:
•were modified.
•were damaged by dropping, striking,
wrench twisting, wrench slippage, or
the like.
•are leaking or exhibiting visible signs
of corrosion.
•were exposed to corrosive products
of combustion but have not oper-
ated, if they cannot be completely
cleaned by wiping the sprinkler with
a cloth or by brushing it with a soft
bristle brush.
•have a cracked bulb or that have lost
liquid from the bulb (refer to the In-
stallation section).
Frequent visual inspections of random
samples are recommended to be in-
itially performed for corrosion-resis-
tant coated sprinklers to verify the in-
tegrity of the corrosion-resistant
coating. Thereafter, annual inspec-
tions per NFPA 25 should suffice. In-
spections of corrosion-resistant sprin-
TYPE TEMP.
RATING
BULB
LIQUID
COLOR NATURAL
BRASS
CHROME
PLATED
SPRINKLER FINISH (See Note 4)
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL)
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL)
3. Approved by Factory Mutual Research Corporation (FM)
4. Where Lead Coated Sprinklers are noted as UL and C-UL Listed, the sprinklers are UL
and C-UL Listed as Corrosion Resistant Sprinklers.
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
LEAD
COATED
5.6
1/2"
NPT
PENDENT
(TY3296)
and
UPRIGHT
(TY3191)
8.0
3/4"
NPT
PENDENT
(TY4292)
and
UPRIGHT
(TY4191)
400°F/204°C
500°F/260°C Black
Black
1, 2
K
400°F/204°C
500°F/260°C
650°F/343°C
Black
Black
Black
1, 2, 3 1, 2
1, 2
3 N/A
FIGURE 3
W-TYPE 11 SPRINKLER
WRENCH
"LARGE FRAME
SPKR" END FOR
QUARTZOID
ONLY USE
SPRINKLERS
TFP690
Page 3 of 4

klers are recommended to be at close
range (instead of inspecting from the
floor level per NFPA 25). Inspection at
close range can better determine the
exact sprinkler condition and the long-
term integrity of the corrosion-resis-
tant coating, which can be affected by
the corrosive conditions present.
Responsibility lies with the owner for
the inspection, testing, and mainte-
nance of their fire protection system
and devices in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association (for example,
NFPA 25), in addition to the standards
of any authorities having jurisdiction.
Contact the installing contractor or
sprinkler manufacturer regarding any
questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
Products manufactured by Tyco Fire
Suppression & Building Products
(TFSBP) are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by TFSBP. No warranty is given
for products or components manufac-
tured by companies not affiliated by
ownership with TFSBP or for products
and components which have been
subject to misuse, improper installa-
tion,corrosion, or which have not been
installed, maintained, modified or re-
paired in accordance with applicable
Standards of the National Fire Protec-
tion Association, and/or the standards
of any other Authorities Having Juris-
diction. Materials found by TFSBP to
be defective shall be either repaired or
replaced, at TFSBP’s sole option.
TFSBP neither assumes, nor author-
izes any person to assume for it, any
other obligation in connection with the
sale of products or parts of products.
TFSBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer’s repre-
sentatives.
In no event shall TFSBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether
TFSBP was informed about the possi-
bility of such damages, and in no event
shall TFSBP’s liability exceed an
amount equal to the sales price.
Theforegoingwarrantyismadeinlieu
of any and all other warranties, ex-
press or implied, including warranties
of merchantability and fitness for a par-
ticular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indi-
cate the full product name. Refer to the
Price List for a complete listing of Part
Numbers.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Model/SIN), Standard Re-
sponse, (K-factor), (temperature rat-
ing), Issue D (Pendent or Upright)
Sprinkler with (type of finish or coat-
ing), P/N (from Table B).
Sprinkler Wrench:
Specify: W-Type 11 Sprinkler Wrench,
P/N 56-452-1-001.
© 2007-2009 TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
P/N 51 — XXX — X — XXX
500°F/260°C500
TEMPERATURE
RATING
400°F/204°C4001
SPRINKLER
TABLE B
PART NUMBER SELECTION
ISSUE D UPRIGHT AND PENDENT SPRINKLERS
650°F/343°C
(5.6K Only)
650
NATURAL BRASS
9
MODEL/SIN
CHROME PLATED
7LEAD COATED
(400°F & 500°F Only)
136 8.0K UPRIGHT (3/4"NPT)
140 8.0K PENDENT (3/4"NPT)
5.6K UPRIGHT (1/2"NPT)
5.6K PENDENT (1/2"NPT)
036
040 TY3296
TY3191
TY4292
TY4191
TFP690
Page4of4
This manual suits for next models
3
Other Tyco Irrigation System manuals

Tyco
Tyco TY-L Series User manual

Tyco
Tyco ESFR-1 User manual

Tyco
Tyco TY-B Series User manual

Tyco
Tyco ESFR-17 User manual

Tyco
Tyco TY-B Series User manual

Tyco
Tyco TY-QRF User manual

Tyco
Tyco TY-FRB Series User manual

Tyco
Tyco RAPID RESPONSE Series User manual

Tyco
Tyco Style 60 User manual

Tyco
Tyco EC-5 Series User manual

Tyco
Tyco TY-FRB Series User manual

Tyco
Tyco TY-FRL Series User manual

Tyco
Tyco ELO-231 Series User manual

Tyco
Tyco Ultra K17 User manual

Tyco
Tyco TY-L Series User manual

Tyco
Tyco Ultra K17 User manual

Tyco
Tyco TFP PH2 Instruction Manual

Tyco
Tyco RFII Series User manual

Tyco
Tyco EC-25 User manual

Tyco
Tyco RFII Series User manual