
TFP443
Page 4 of 6
Installation
The TYCO RAPID RESPONSE Series
LFII Residential Flat-Plate Concealed
Pendent Sprinklers must be installed
in accordance with the following
instructions.
NOTICE
Damage to the Solder Link Element dur-
ing installation can be avoided by han-
dling the sprinkler by the Support Cup
only; that is, do not apply pressure to the
Solder Link Element (Figure 1).
Obtain a leak-tight 1/2 inch NPT sprinkler
joint by applying a minimum-to-maxi-
mum torque of 7 to 14 ft.-lbs. (9,5 to 19,0
Nm). Higher levels of torque can distort
the sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in the Cover Plate/
Retainer Assembly by under- or over-
tightening the sprinkler. Re-adjust the
position of the sprinkler fitting to suit.
1. Install pendent sprinklers in the
pendent position, with the center-
line of the sprinkler perpendicular
to the mounting surface.
2. Remove the Protective Cap.
3. With pipe-thread sealant applied
to the pipe threads, and using the
W-Type 18 Wrench shown in Figure
2, install and tighten the Sprinkler/
Support Cup Assembly into the t-
ting. The W-Type 18 Wrench ac-
cepts a 1/2 inch ratchet drive.
4. Replace the Protective Cap by
pushing it upwards until it bottoms
out against the Support Cup. The
Protective Cap helps prevent dam-
age to the Deector and Guide
Pins during ceiling installation and/
or during application of the nish
coating of the ceiling.
NOTICE
As long as the protective Cap re-
mains in place, the system is con-
sidered “Out Of Service”.
5. After the ceiling has been com-
pleted with the 2-1/2 inch (63 mm)
diameter clearance hole and in
preparation for installing the Cover
Plate/Retainer Assembly, remove
and discard the Protective Cap,
and verify that the Deector moves
up and down freely.
If the Sprinkler has been damaged
and the Deector does not move up
and down freely, replace the entire
Sprinkler assembly. Do not attempt to
modify or repair a damaged sprinkler.
6. Screw on the Cover Plate/Retainer
Assembly until its ange contacts
the ceiling.
Do not continue to screw on the
Cover Plate/Retainer Assembly such
that it lifts a ceiling panel out of its
normal position.
If the Cover Plate/Retainer Assembly
cannot be engaged with the Mounting
Cup or the Cover Plate/Retainer As-
sembly cannot be engaged sufciently
to contact the ceiling, the Sprinkler
Fitting must be repositioned.
Care and
Maintenance
The TYCO RAPID RESPONSE
Series
LFII Residential Flat-Plate Concealed
Pendent Sprinkler (TY2524) must be
maintained and serviced in accordance
with the following instructions.
NOTICE
Before closing a fire protection system
main control valve for maintenance work
on the fire protection system that it con-
trols, obtain permission to shut down the
affected fire protection system from the
proper authorities and notify all person-
nel who may be affected by this action.
When properly installed, there is a nomi-
nal 1/8 inch (3,2 mm) air gap between
the lip of the Cover Plate and the ceil-
ing, as shown in Figure 3. This air gap
is necessary for proper operation of the
sprinkler by allowing heat ow from a
re to pass below and above the Cover
Plate to help assure appropriate release
of the Cover Plate in a re situation. If the
ceiling needs repainting after sprinkler
installation, exercise care to ensure that
the new paint does NOT seal off any of
the air gap. Failure to do so may impair
sprinkler operation.
Absence of a Cover Plate can delay the
sprinkler operation in a re situation.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Exercise care to avoid damage to sprin-
klers before, during, and after installa-
tion. Never paint, plate, coat, or other-
wise alter automatic sprinklers after they
leave the factory.
Never repaint factory-painted Cover
Plates. When necessary, replace cover
plates with factory-painted units. Non-
factory applied paint can adversely de-
lay or prevent sprinkler operation in the
event of a re.
Replace sprinklers that:
• were damaged by dropping, striking,
wrench twisting, wrench slippage, or
the like.
• were modied or over-heated.
• are leaking or exhibiting visible signs
of corrosion.
Responsibility lies with owners for the
inspection, testing, and maintenance of
their re protection system and devices
in compliance with this document, as
well as with the applicable standards of
the National Fire Protection Association
(for example, NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or sprinkler manufacturer
regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualied Inspec-
tion Service in accordance with local
requirements and/or national codes
.