TFP672
Page 4 of 4
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a trademark of The Chemours Company FC, LLC
1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220
© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Care and
Maintenance
The Series TY-B Sprinklers must be
maintained and serviced in accordance
with this section.
Before closing a re protection system
main control valve for maintenance
work on the re protection system that
it controls, permission to shut down the
affected re protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notied.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or other-
wise altered after leaving the factory.
Modied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. Ref to the Installa-
tion section for more information.
The owner is responsible for the inspec-
tion, testing, and maintenance of their
re protection system and devices in
compliance with this document, as well
as with the applicable standards of the
NATIONAL FIRE PROTECTION ASSO-
CIATION (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualied Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-re.com
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assembly
Specify: (Specify) SIN, (specify) K-fac-
tor, Series TY-B (specify Pendent or
Upright) Sprinkler Special Response,
(specify) temperature rating, with
(specify) nish, P/N (specify from Table
A)
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
* Eastern Hemisphere sales only
P/N 57 – XXX – X – XXX
SIN
480 57K UPRIGHT (ISO 7-1 R 3/8) TY2149
481 57K PENDENT (ISO 7-1 R 3/8 TY2249
470 80K UPRIGHT (1/2 in. NPT) TY3141
471 80K PENDENT (1/2 in. NPT) TY3241
490 115K UPRIGHT (3/4 in. NPT) TY4141
491 115K PENDENT (3/4 in. NPT) T Y4241
SPRINKLER
FINISH
1NATURAL BRASS
3PURE WHITE (RAL9010)*
POLYESTER
4SIGNAL WHITE (RAL9003)
POLYESTER
9CHROME PLATED
TEMPERATURE
RATING
135 57°C
155 68°C
175 79°C
200 93°C
286 141°C
TABLE A
SERIES TY-B SPECIAL RESPONSE PENDENT AND UPRIGHT SPRINKLERS
PART NUMBER SELECTION