manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tyco
  6. •
  7. Irrigation System
  8. •
  9. Tyco ESFR-14 User manual

Tyco ESFR-14 User manual

Model ESFR-14
14.0 K-factor Pendent Sprinklers
Early Suppression, Fast Response
Worldwide
Contacts
www.tyco-fire.com
Page 1 of 4 NOVEMBER 2014 TFP319
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cau-
tions with respect to handling
and installation of sprinkler sys-
tems and components. Improp-
er handling and installation can
permanently damage a sprin-
kler system or its components
and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
General
Description
TYCO Model ESFR-14, 14.0 K-factor,
Pendent Sprinklers (TY6236) are Early
Suppression, Fast Response (ESFR)
sprinklers having a nominal K-factor
of 14.0. They are suppression-mode
sprinklers that are especially advanta-
geous as a means of eliminating the
use of in-rack sprinklers when pro-
tecting high-piled storage.
Model ESFR-14 Sprinklers are primar-
ily designed for protection of the fol-
lowing storage arrangements:
• most encapsulated or non-encap-
sulated common materials including
cartoned, unexpanded plastics
• some storage arrangements of
rubber tires, roll paper, ammable
liquids
For more specic criteria, refer to
Table A in this technical data sheet
as well as the applicable design
standard.
NOTICE
The TYCO Model ESFR-14 Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the ap-
plicable standards of the National Fire
Protection Association (NFPA), in ad-
dition to the standards of any other
authorities having jurisdiction (e.g., FM
Approvals). Failure to do so may im-
pair the performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condi-
tion. Contact the installing contrac-
tor or product manufacturer with any
questions.
In all cases, the appropriate NFPA,
FM Approvals installation standard,
or other applicable standard, must
be referenced to ensure applicabil-
ity and to obtain complete installation
guidelines. The general guidelines in
this technical data sheet are not in-
tended to provide complete installa-
tion criteria.
Sprinkler
Identification
Number (SIN)
TY6236 – Pendent, K=14.0
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
3/4 inch NPT or
ISO 7-R 3/4
Discharge Coefficient
K=14.0 gpm/psi1/2 (201,6 lpm/bar1/2)
Temperature Ratings
155°F (68°C)
200°F (93°C)
Finish
Natural Brass
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . Brass
Deector. . . . . . . . . . . . . . . . . . . . . Bronze
Compression Screw. . . . . . . . . . . . Bronze
Button. . . . . . . . . . . . . . . . . . . . . . . . Brass
Sealing Assembly. . . . . . . Beryllium Nickel
w/TEFLON
Bulb (3 mm) . . . . . . . . . . . . . . . . . . . Glass
Design
Criteria
The following general guidelines pro-
vided for the TYCO Model ESFR-14,
14.0 K-factor, Pendent Sprinklers
(TY6236) can be used for quick
reference.
NOTICE
The National Fire Protection Associa-
tion and FM Approvlas provide instal-
lation standards that must be used to
properly design an automatic sprinkler
system utilizing Early Suppression,
Fast Response (ESFR) Sprinklers. The
guidelines provided by NFPA and FM
Global may differ; consequently, the
appropriate standard must be used for
a given installation.
In all cases, the appropriate NFPA or
FM Approvals installation standard
must be referenced to assure appli-
cability and to obtain complete instal-
lation guidelines, since the following
general guidelines are not intended to
provide complete installation criteria.
TFP319
Page 2 of 4
System Type
Wet pipe
Roof Construction
Unobstructed or obstructed construc-
tion; for example, smooth ceiling, bar
joists, beam and girder, and so forth.
Where the depths of solid structural
members (e.g., beams and stem) ex-
ceed 12 inches (302 mm), install Model
ESFR-14 Sprinklers in each channel
formed by the structural members.
Ceiling Slope
Maximum 2 inch rise for 12 inch run
(16.7%)
Maximum Coverage Area
100 ft2(9,3 m2)
In some cases, the installation stan-
dards permit a greater coverage area.
Minimum Coverage Area
64 ft2(5,8 m2) per
NFPA 13 / FM Global 2-0
Maximum Spacing
12 ft (3,7 m) for building heights up to
30 ft (9,1 m)
10 ft (3,1 m) for building heights great-
er than 30 ft (9,1 m)
Minimum Spacing
8 ft (2,4 m)
Minimum Clearance to Commodity
36 inches (914 mm)
NFPA 13
Deflector-to-Ceiling Distance
6 to 14 inches (152 to 356 mm)
FM Global 2-0
Consult FM Global guidelines for al-
lowable deector-to-ceiling distances
as well as thermal-sensing element-
to-ceiling criteria.
Operation
The glass bulb contains a uid which
expands when exposed to heat. When
the rated temperature is reached, the
uid expands sufciently to shatter
the glass bulb, allowing the sprinkler
to activate and water to ow.
Installation
TYCO Model ESFR-14 Pendent Sprin-
klers must be installed in accordance
with this section.
General Instructions
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present.
A leak-tight 3/4 inch NPT sprinkler
joint should be obtained by applying
a minimum-to-maximum torque of 10
to 20 ft.-lbs. (13,4 to 26,8 Nm). Higher
levels of torque can distort the sprin-
kler inlet with consequent leakage or
impairment of the sprinkler.
Note: Install the Model ESFR-14 Pen-
dent Sprinkler in the pendent position
(Figure 1).
Step 1. With pipe thread sealant ap-
plied, hand-tighten the sprinkler into
the sprinkler tting.
Step 2. Wrench-tighten the Model
ESFR-14 Sprinkler using only the W-
Type 2 Sprinkler Wrench (Figure 2) or
the W-Type 30 Sprinkler Wrench (Fig-
ure 3) and by fully engaging (seating)
the wrench on the sprinkler wrench
ats (Figure 1).
Step 3. After installation, inspect the
bulb of each Model ESFR-14 Sprinkler
for damage. In particular, verify that
the bulb is not cracked. Replace dam-
aged sprinklers.
*
*
*
**
**
Temperature rating is
indicated on Deector.
Pipe thread connections per
ISO 7-1 can be provided on
special request.
2-3/8"
(60,3 mm)
WRENCH
FLATS
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
Components:
2
3
4
5
6
1
-Sealing Assembly
6
-Compression Screw
3
Bulb
Button
-
4
-
5
Deector
Frame
-
1
2
-
3/4" NPT
1-1/2"
(38,1 mm)
CENTERLINE
THERMAL
SENSING
ELEMENT
WRENCH
RECESS
"FITTING SIDE"
TOWARD SPRINKLER
FITTING
1" WRENCH
ACCEPTS
WRENCH
RECESS
1/2" DRIVE
ACCEPTS
SOCKET
HEX
FLATS
WRENCH
FIGURE 3
W-TYPE 30
SPRINKLER WRENCH
FIGURE 1
MODEL ESFR-14, 14.0 K-FACTOR, PENDENT SPRINKLER
EARLY SUPPRESSION, FAST RESPONSE
FIGURE 2
W-TYPE 2
SPRINKLER WRENCH
TFP319
Page 3 of 4
Care and
Maintenance
TYCO Model ESFR-14, 14.0 K-factor,
Pendent Sprinklers (TY6236) must
be maintained and serviced in accor-
dance with this section.
Before closing a re protection system
main control valve for maintenance
work on the re protection system that
it controls, obtain permission to shut
down the affected re protection sys-
tems from the proper authorities and
notify all personnel who may be af-
fected by this action.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be
replaced. Also, replace any sprinkler
that has a cracked bulb or that has
lost liquid from its bulb. (Refer to In-
stallation Section.)
The owner is responsible for the in-
spection, testing, and maintenance of
their re protection system and devic-
es in compliance with this document,
as well as with the applicable stan-
dards of the National Fire Protection
Association (e.g., NFPA 25), in addition
to the standards of any other authori-
ties having jurisdiction. Contact the
installing contractor or product manu-
facturer with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualied Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions,
visit www.tyco-re.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indi-
cate the full product name and Part
Number (P/N).
Sprinkler Assemblies
Specify: Model ESFR-14 (TY6236),
K=14.0, Pendent Sprinkler with (spec-
ify) temperature rating, Natural Brass,
P/N (specify):
155°F (68°C) .............. P/N 58-449-1-155
200°F (93°C).............. P/N 58-449-1-200
Special Order
Sprinkler Assemblies with
ISO 7/1 Thread Connections
Specify: Model ESFR-14 (TY6236),
K=14.0, Early Suppression, Fast Re-
sponse Pendent Sprinkler with ISO
7/1 Thread Connection, (specify) tem-
perature rating, Natural Brass, P/N
(specify):
155°F (68°C) .............. P/N 58-443-1-155
200°F (93°C).............. P/N 58-443-1-200
Sprinkler Wrenches
Specify: W-Type 2 Sprinkler Wrench,
P/N 56-872-1-001
Specify: W-Type 30 Sprinkler Wrench,
P/N 56-001-0-688
Storage Type NFPA FM Global
Open Frame (i.e., no solid shelves)
Single, Double, Multiple-Row, or Portable Rack Storage
of Class I-IV and Group A or B Plastics
Refer to NFPA 13,
Chapters 16 and 17
Refer to FM Global
2-0 and 8-9
Solid Pile or Palletized Storage
of Class I-IV and Group A or B Plastics
Refer to NFPA 13,
Chapters 14 and 15
Refer to FM Global
2-0 and 8-9
Idle Pallet Storage Refer to NFPA 13,
Chapter 12
Refer to FM Global
2-0, 8-9, and 8-24
Rubber Tire Storage Refer to NFPA 13,
Chapter 18
Refer to FM Global
2-0 and 8-9
Rolled Paper Storage
(Refer to the standard)
Refer to NFPA 13,
Chapter 19
Refer to FM Global
8-21
Flammable Liquid Storage
(Refer to the standard) Refer to NFPA 30 Refer to FM Global
7-29
Aerosol Storage
(Refer to the standard) Refer to NFPA 30B Refer to FM Global
7-31
Automotive Components in Portable Racks
(Control mode only, refer to the standard) N/A N/A
N/A – Not Applicable
TABLE A
MODEL ESFR-14 PENDENT SPRINKLERS
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
TFP319
Page 4 of 4
Copyright © 2014 Tyco Fire Products, LP. All rights reserved.
TEFLON is trademark of the DuPont Corporation.

Other Tyco Irrigation System manuals

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco Integra Ci1 User manual

Tyco

Tyco Integra Ci1 User manual

Tyco rapidresponse RSV-1 User manual

Tyco

Tyco rapidresponse RSV-1 User manual

Tyco Rapidresponse LFII Series User manual

Tyco

Tyco Rapidresponse LFII Series User manual

Tyco LFII Series User manual

Tyco

Tyco LFII Series User manual

Tyco DS-2 Series User manual

Tyco

Tyco DS-2 Series User manual

Tyco ILLUSION User manual

Tyco

Tyco ILLUSION User manual

Tyco Power Pro Series User manual

Tyco

Tyco Power Pro Series User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco LFII Series User manual

Tyco

Tyco LFII Series User manual

Tyco TY-FRB Series User manual

Tyco

Tyco TY-FRB Series User manual

Tyco LFII Series User manual

Tyco

Tyco LFII Series User manual

Tyco ESFR-25 User manual

Tyco

Tyco ESFR-25 User manual

Tyco TY-FRL Series User manual

Tyco

Tyco TY-FRL Series User manual

Tyco Style 60 User manual

Tyco

Tyco Style 60 User manual

Tyco DS-1 Series User manual

Tyco

Tyco DS-1 Series User manual

Tyco 3002B User manual

Tyco

Tyco 3002B User manual

Tyco TY-L Series User manual

Tyco

Tyco TY-L Series User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco DS-ECC Series User manual

Tyco

Tyco DS-ECC Series User manual

Tyco Ultra K17 K-factor User manual

Tyco

Tyco Ultra K17 K-factor User manual

Tyco ESFR-22 User manual

Tyco

Tyco ESFR-22 User manual

Tyco TY-B Series User manual

Tyco

Tyco TY-B Series User manual

Tyco ESFR-1 User manual

Tyco

Tyco ESFR-1 User manual

Popular Irrigation System manuals by other brands

ASC FLEXHEAD Installation and Maintenance

ASC

ASC FLEXHEAD Installation and Maintenance

Hunter ST Series owner's manual

Hunter

Hunter ST Series owner's manual

Task Force Tips Masterstream Series INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

Task Force Tips

Task Force Tips Masterstream Series INSTRUCTIONS FOR SAFE OPERATION AND MAINTENANCE

Reliable G4 manual

Reliable

Reliable G4 manual

Victaulic VS1 Series installation instructions

Victaulic

Victaulic VS1 Series installation instructions

Rain Bird LG3HE Installation & operating guide

Rain Bird

Rain Bird LG3HE Installation & operating guide

SNOWJOE AQUAJOE AJ-IS10WB-RM manual

SNOWJOE

SNOWJOE AQUAJOE AJ-IS10WB-RM manual

Johnson Controls tyco TFP PH5 manual

Johnson Controls

Johnson Controls tyco TFP PH5 manual

SNOWJOE AQUAJOE AJ-OSPR20 manual

SNOWJOE

SNOWJOE AQUAJOE AJ-OSPR20 manual

Rain Bird wtd 2900 Operation guide

Rain Bird

Rain Bird wtd 2900 Operation guide

Reliable F1FR56 quick start guide

Reliable

Reliable F1FR56 quick start guide

Reliable HL22 Bulletin

Reliable

Reliable HL22 Bulletin

Viking HORIZON H-3 Technical data

Viking

Viking HORIZON H-3 Technical data

Gardena aquaBloom Set Operator's manual

Gardena

Gardena aquaBloom Set Operator's manual

Johnson Controls tyco ILLUSION manual

Johnson Controls

Johnson Controls tyco ILLUSION manual

Reliable DH56 HSW-PL quick start guide

Reliable

Reliable DH56 HSW-PL quick start guide

SNOWJOE AQUAJOE SJI-OMS20 manual

SNOWJOE

SNOWJOE AQUAJOE SJI-OMS20 manual

K-Rain KRX6 manual

K-Rain

K-Rain KRX6 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.