
TFP228
Page 4 of 4
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a trademark of The Chemours Company FC, LLC
1467 Elmwood Avenue, Cranston, RI 02910 | Telephone +1-401-781-8220
© 2022 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Care and
Maintenance
The Series EC-5 Extended Coverage
Pendent Sprinklers must be maintained
and serviced in accordance with this
section.
Before closing a re protection system
main control valve for maintenance
work on the re protection system that
it controls, permission to shut down the
affected re protection systems must
be obtained from the proper authorities
and all personnel who may be affected
by this action must be notied.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section).
Frequent visual inspections are rec-
ommended to be initially performed
for corrosion resistant coated sprin-
klers, after the installation has been
completed, to verify the integrity of the
corrosion resistant coating. Thereafter,
annual inspections according to NFPA
25 should sufce; however, instead
of inspecting from the oor level, a
random sampling of close-up visual
inspections should be made, so as to
better determine the exact sprinkler
condition and the long term integrity
of the corrosion resistant coating as it
may be affected by the corrosive con-
ditions present.
The owner is responsible for the
inspection, testing, and maintenance of
their re protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualied Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-re.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series EC-5 (TY3232), K=5.6,
Extended Coverage Pendent Sprinkler,
(specify) temperature rating, (specify)
nish, P/N (specify):
135°F (57°C)
Natural Brass ................. 51-051-1-135
Pure White (RAL9010)*
Polyester ....................51-051-3-135
Signal White (RAL9003)
Polyester ....................51-051-4-135
Chrome Plated ................51-051-9-135
155°F (68°C)
Natural Brass ................. 51-051-1-155
Pure White (RAL9010)*
Polyester ....................51-051-3-155
Signal White (RAL9003)
Polyester ....................51-051-4-155
Chrome Plated ................51-051-9-155
*Eastern Hemisphere sales only
Recessed Escutcheon
Specify: Style 50 Recessed Escutch-
eon, (specify*) nish, P/N (specify*)
*Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Recessed Sprinkler
Wrench, P/N 56-850-4-001