4Mounting
4.1Application conditions
Before mounting,setup and operation,take note that the isolating
system as well as the pressure transmitter were selected according to
measuring range,version and material.The load limits must be
maintained in order to guarantee accuracy and operational life span.
Caution:
In dangerous substances such as e.g.oxygen,acetylene,combustible
or toxic products as well as in refrigerating plants,compressors,etc.,
the pertinent instructions must be observed in addition to the general
regulations.
The differential pressure transmitter must be mounted in such a way
that the permissible ambient and product temperature limits,also
under consideration of the influence of convection and heat radiation,
are neither underrun nor exceeded.
When selecting the pressure transmitter,the pressure temperature
resistance of the fitting and flange components must be considered
through the selection of the material and pressure stage.The pressure
stage stated on the isolating diaphragm applies to ambient temper-
atures.In case of higher temperatures,the max.permissible pressure
must be taken from the standard indicated on the isolating diaphragm.
To keep the temperature influence as low as possible,configuration or
mounting must be carried out in such a way that the plus and minus
sides are symmetrical with respect to ambient temperatures.
4.2Instructions for handling
lThe instruments must be protected against soiling and strong
fluctuations of the ambient temperature
lLeave the measuring system in the packaging until mounting to
protect it against mechanical damages
lWhen removing the packaging and when mounting,take special
care to avoid damage and mechanical deformation of the
diaphragm
lDo not carry the pressure transmitter by holding the capillary line
lDo not bent the capillary lines.Kinks can cause leakage and lead
to an increase in response time
lNever loosen sealed screws on the isolating diaphragm or the
pressure transmitter
lDo not damage the isolating diaphragm:scratches on the isolating
diaphragm (e.g.from sharp subjects)are the main areas where
corrosion can occur
Suitability for process
conditions
Consideration of the
ambient temperature
8Isolating diaphragm CSS •for VEGADIF 65
4Mounting