Vega VEGABAR 54 User manual

Operating Instructions
VEGABAR 54
4…20 mA/HART
p

Contents
1About this document
1.1Function ............................. 5
1.2Target group .......................... 5
1.3Symbolism used ....................... 5
2For your safety
2.1Authorised personnel.................... 6
2.2Appropriate use........................ 6
2.3Warning about misuse ................... 6
2.4General safety instructions................ 6
2.5CE conformity ......................... 6
2.6Compatibility acc.to NAMUR NE 53......... 7
2.7Safety information for Ex areas............. 7
2.8Environmental instructions ................ 7
3Product description
3.1Configuration.......................... 8
3.2Principle of operation.................... 8
3.3Adjustment ........................... 9
3.4Storage and transport ................... 9
4Mounting
4.1General instructions..................... 11
4.2Mounting procedure..................... 11
4.3Mounting steps,remote housing -Non-Ex..... 13
4.4Mounting steps,remote housing -Ex........ 13
5Connecting to power supply
5.1Preparing the connection ................. 15
5.2Connection procedure ................... 16
5.3Wiring plans,single chamber housing........ 20
5.4Wiring plans,double chamber housing ....... 22
5.5Wiring plans,double chamber housing Exd.... 24
5.6Wiring plans,version IP 66/IP 68 (1bar)...... 26
5.7Wiring plans,remote housing with IP 68 version -
Non-Ex.............................. 27
5.8Wiring plans,remote housing with IP 68 version -
Ex................................. 30
5.9Switch on phase ....................... 31
6Setup with the indicating and adjustment module
PLICSCOM
6.1Short description ....................... 32
2VEGABAR 54 -4…20 mA/HART
Contents
29694-EN-051004

6.2Installing the indicating and adjustment module
PLICSCOM ........................... 32
6.3Adjustment system ..................... 34
6.4Setup procedure ....................... 35
6.5Menu schematic ....................... 42
6.6Saving the parameter adjustment data ....... 45
7Setup with PACTware™and other adjustment
programs
7.1Connecting the PC ..................... 46
7.2Parameter adjustment with PACTware™...... 47
7.3Parameter adjustment with AMS™and PDM .. 48
7.4Saving the parameter adjustment data ....... 48
8Maintenance and fault rectification
8.1Maintenance .......................... 49
8.2Fault rectification ....................... 49
8.3Exchanging the electronics................ 51
8.4Instrument repair ....................... 51
9Dismounting
9.1Dismounting procedure .................. 53
9.2Disposal ............................. 53
10 Functional safety acc.to IEC 61508-4(SIL)
10.1General.............................. 54
10.2Planning ............................. 56
10.3Adjustment instructions and parameter
adjustment ........................... 58
10.4Set up .............................. 59
10.5Reaction during operation and in case of failure.59
10.6Recurring function test ................... 60
10.7Safety-related characteristics .............. 60
11 Supplement
11.1Technical data......................... 64
11.2Dimensions ........................... 73
11.3Certificates ........................... 79
11.4Industrial property rights.................. 82
VEGABAR 54 -4…20 mA/HART 3
Contents
29694-EN-051004

Supplementary operating instructions manuals
Information:
VEGABAR 54 is available in different versions and is supplied
order-specifically.Depending on the selected version,sup-
plementary operating instructions manuals come with the
shipment.The supplementary operating instructions are stated
in paragraph "Product description".
Operating instructions manuals for accessories and
replacement parts
Tip:
VEGA offers accessories and replacement parts for reliable
use and operation of your VEGABAR 54.The corresponding
operating instructions manuals are:
lOperating instructions manual "External indicating and
adjustment unit VEGADIS 61"
lOperating instructions manual "Oscillator VEGABAR series
50 and 60"
4VEGABAR 54 -4…20 mA/HART
Contents
29694-EN-051004

1About this document
1.1Function
This operating instructions manual has all the information you
need for quick setup and safe operation of VEGABAR 54.
Please read this manual before you start setup.
1.2Target group
This operating instructions manual is directed to trained
personnel.The contents of this manual should be made
available to these personnel and put into practice by them.
1.3Symbolism used
Information,tip,note
This symbol indicates helpful additional information.
Caution,warning,danger
This symbol informs you of a dangerous situation that could
occur.Ignoring this cautionary note can impair the person and/
or the instrument.
Ex applications
This symbol indicates special instructions for Ex applications.
lList
The dot set in front indicates a list with no implied sequence.
àAction
This arrow indicates a single action.
1Sequence
Numbers set in front indicate successive steps in a procedure.
VEGABAR 54 -4…20 mA/HART 5
About this document
29694-EN-051004

2For your safety
2.1Authorised personnel
All operations described in this operating instructions manual
must be carried out only by trained,specialised personnel
authorised by the operator.For safety and warranty reasons,
any internal work on the instruments must be carried out only
by personnel authorised by the manufacturer.
2.2Appropriate use
VEGABAR 54 is a pressure transmitter for measurement of
gauge pressure,absolute pressure and vacuum.
2.3Warning about misuse
Inappropriate or incorrect use of the instrument can give rise to
application-specific hazards,e.g.vessel overfill or damage to
system components through incorrect mounting or adjustment.
2.4General safety instructions
VEGABAR 54 is a high-tech instrument requiring the strict
observance of standard regulations and guidelines.The user
must take note of the safety instructions in this operating
instructions manual,the country-specific installation standards
(e.g.the VDE regulations in Germany)as well as all prevailing
safety regulations and accident prevention rules.
2.5CE conformity
VEGABAR 54 is in CE conformity with EMC (89/336/EWG),
fulfils the NAMUR recommendation NE 21 and is in CE
conformity with LVD (73/23/EWG).
Conformity has been judged acc.to the following standards:
lEMC:
-Emission EN 61326:2004 (class B)
-Susceptibility EN 61326:2004 incl.supplement A
lLVD:EN 61010-1:2001
VEGABAR 54 is not subject to the pressure device guideline.1)
1)Due to the flush diaphragm,no own pressure compartment is formed.
6VEGABAR 54 -4…20 mA/HART
For your safety
29694-EN-051004

2.6Compatibility acc.to NAMUR NE 53
VEGABAR 54 meets NAMUR recommendation NE 53.VEGA
instruments are generally upward and downward compatible:
lsensor software for DTM-VEGABAR 54 HART,PA or FF
lDTM VEGABAR 54 for adjustment software PACTware™
ladjustment module PLICSCOM for sensor software
The parameter adjustment of the basic sensor functions is
independent of the software version.The range of available
functions depends on the respective software version of the
individual components.
The software version of VEGABAR 54 can be determined as
follows:
lvia PACTware™
lon the type label of the electronics
lvia the adjustment module PLICSCOM
On our website www.vega.com you will find all software
histories.Make use of this convenience and get registered for
update information via e-mail.
2.7Safety information for Ex areas
Please note the Ex-specific safety information for installation
and operation in Ex areas.These safety instructions are part of
the operating instructions manual and come with the Ex-
approved instruments.
2.8Environmental instructions
Protection of the environment is one of our most important
duties.That is why we have introduced an environment
management system with the goal of continuously improving
company environmental protection.The environment man-
agement system is certified acc.to DIN EN ISO 14001.
Please help us fulfil this obligation by observing the environ-
mental instructions in this manual:
lChapter "Storage and transport"
lChapter "Disposal"
VEGABAR 54 -4…20 mA/HART 7
For your safety
29694-EN-051004

3Product description
3.1Configuration
The scope of delivery encompasses:
lVEGABAR 54 process pressure transmitter
lDocumentation
-this operating instructions manual
-test certificate
-Ex-specific safety instructions (with Ex versions)and,if
necessary,further certificates
-Operating instructions manual "Indicating and adjust-
ment module PLICSCOM"-optional
-Supplementary instructions manual "Plug connector for
continuously measuring sensors"-optional
VEGABAR 54 consists of the following components:
lProcess fitting with measuring cell
lHousing with electronics,optionally available with plug
connector
lHousing cover,optionally available with indicating and
adjustment module PLICSCOM
The components are available in different versions.
1
2
3
Fig.1:Example of a VEGABAR 54 with process fitting G1Aand plastic housing
1Housing cover with integrated PLICSCOM (optional)
2Housing with electronics
3Process fitting with measuring cell
3.2Principle of operation
VEGABAR 54 is a pressure transmitter for use in the paper,
food processing and pharmaceutical industries as well as in
water/sewage water plants.Depending on the version,it is
Scope of delivery
Components
Area of application
8VEGABAR 54 -4…20 mA/HART
Product description
29694-EN-051004

used for level,gauge,absolute pressure or vacuum meas-
urement.Measured products are gases,vapours and liquids,
also those containing abrasive substances.
The sensor element is the small CERTEC
®
measuring cell with
flush,abrasion resistant ceramic diaphragm.The hydrostatic
pressure of the medium or the process pressure causes a
capacitance change in the measuring cell via the diaphragm.
This change is converted into an appropriate output signal and
outputted as measured value.
The CERTEC
®
measuring cell is also equipped with a
temperature sensor.The temperature value can be displayed
via PLICSCOM or processed via the signal output.
Two-wire electronics 4…20 mA/HART for power supply and
measured value transmission on the same cable.
The power supply range can differ depending on the instru-
ment version.The exact range is stated in the "Technical data"
in the "Supplement".
3.3Adjustment
VEGABAR 54 can be adjusted with four different adjustment
media:
lthe indicating and adjustment module PLICSCOM
lwith the suitable VEGA DTM in conjunction with an
adjustment software acc.to FDT/DTM standard,e.g.
PACTware™and PC
lwith manufacturer-specific adjustment programs AMS™or
PDM
laHART handheld
The entered parameters are generally saved in VEGABAR 54,
optionally also in PLICSCOM or in PACTware™.
3.4Storage and transport
Your instrument was protected by packaging during transport.
Its capacity to handle normal loads during transport is assured
by a test acc.to DIN EN 24180.
The packaging of standard instruments consists of environ-
ment-friendly,recyclable cardboard.For special versions,PE
foam or PE foil is also used.Dispose of the packaging material
via specialised recycling companies.
Physical principle
Power supply
Packaging
VEGABAR 54 -4…20 mA/HART 9
Product description
29694-EN-051004

lStorage and transport temperature see "Supplement –
Technical data –Ambient conditions"
lRelative humidity 20 …85 %
Storage and transport tem-
perature
10 VEGABAR 54 -4…20 mA/HART
Product description
29694-EN-051004

4Mounting
4.1General instructions
Check if the wetted materials such as seal,process fitting etc.
are suitable for the existing process conditions,such as
product,temperature etc.
Select an installation position you can easily reach for
mounting and connecting as well as later retrofitting of an
indicating and adjustment module.The housing can be rotated
by 330°without the use of any tools.You can also install the
indicating and adjustment module in four different positions
(each displaced by 90°).
Use the recommended cable (see chapter "Connecting to
power supply")and tighten the cable gland.
You can give your VEGABAR 54 additional protection against
moisture penetration by leading the connection cable down-
ward in front of the cable entry.Rain and condensation water
can thus drain off.This applies mainly to mounting outdoors,in
areas where moisture is expected (e.g.by cleaning processes)
or on cooled or heated vessels.
Fig.2:Measures against moisture penetration
4.2Mounting procedure
Welded sockets are available from the line of VEGA
accessories for the following process fittings:
lG½A,article no.2.29796
lG¾A,article no.2.29641
lG1A,article no.2.27867
Wetted materials
Installation location
Moisture
Welding the socket
VEGABAR 54 -4…20 mA/HART 11
Mounting
29694-EN-051004

lM30x1.5,article no.2.30444
lM30x1.5,for headbox,article no.2.30739
lPASVE 2)1",for pipelines article no.2.29934,for vessels
article no.2.29642
àNote the applicable welding standards (segment welding
procedure)when welding the socket.
Use the appropriate seal:
lThread G½A:seal on the hexagon Viton article no.
2.29557
lThread G¾A:seal on the hexagon Viton,article no.
2.29558
lThread G1A:seal to the medium Viton,article no.2.27229,
EPDM article no.2.28169,Kalrez article no.2.27608
lThread G1A:seal on the hexagon Viton,article no.
2.28172
lThread M30x1,5:seal to the medium Viton,article no.
2.25664,EPDM article no.2.25666,Kalrez article no.
2.27353
àScrew VEGABAR 54 into the welded socket with an
appropriate spanner applied to the hexagon on the process
fitting.Spanner width see dimensional drawings,max.
torque see Technical data.
Warning:
The housing must not be used to screw the instrument in!
Applying tightening force to the housing can damage its
internal mechanical components.
Warning:
The VEGABAR 54 with thread G½Ais only sealed on the
hexagon.The front of the process fitting must not be used for
sealing!Tightening,e.g.in a welded socket for manometer
connection can damage the process fitting.
Use the appropriate seal:
lPMC 1":seal to the medium Viton,article no.2.30267
lPMC 1¼":seal to the medium Viton,article no.2.23668
lPMC 1½":seal to the medium Viton,article no.2.30251
àShift VEGABAR 54 with PMC connection into the socket
and fasten with two screws M8x10.
2)Trade name of Messrs.Satron Instruments Oy.
Sealing/Screwing in threaded
versions
Mounting socket versions
12 VEGABAR 54 -4…20 mA/HART
Mounting
29694-EN-051004

4.3Mounting steps,remote housing -Non-Ex
1Mark the holes acc.to the following drilling template
2Depending on the mounting surface,fasten the wall
mounting plate with 4screws
90mm (3 35/64")
R3,5mm
(
9
/
64
")
3mm
(1/8")
70mm (2 3/4") 8mm
(5/16")
93mm (3 21/32")
110mm (4 21/64")
Fig.3:Drilling template -wall mounting plate
Tip:
Mount the wall mounting plate so that the cable entry of the
socket housing points downward.The socket housing can be
displaced by 180°to the wall mounting plate.
Warning:
The four screws of the socket housing must only be hand-
screwed.Atorque >5Nm can damage the wall mounting
plate.
4.4Mounting steps,remote housing -Ex
VEGABAR 54 with remote housing for wall mounting is
supplied with a mounting socket.
Wall mounting
Wall mounting
VEGABAR 54 -4…20 mA/HART 13
Mounting
29694-EN-051004

1Mark the holes acc.to the following drilling template
2Depending on the mounting surface,fasten the wall
mounting plate with 4screws
62mm (2 7/16")
12mm
(15/32")
7mm (9/32")
85mm (3 11/32")
Fig.4:VEGABAR 54 for wall mounting,bottom view of mounting plate.
1Drill dimension
VEGABAR 54 for mounting on carrier rail is supplied with a
mounting adapter.
1 32
Fig.5:VEGABAR 54 for carrier rail mounting
1Adapter plate
2Screw M4x6
3Carrier rail
Carrier rail mounting
14 VEGABAR 54 -4…20 mA/HART
Mounting
29694-EN-051004

5Connecting to power supply
5.1Preparing the connection
Always observe the following safety instructions:
lConnect only in the complete absence of line voltage
lIf overvoltages are expected,overvoltage arresters should
be installed.
Tip:
We recommend VEGA overvoltage arresters ÜS-F-LB-Iand
ÜSB 62-36G.X.
In hazardous areas you should take note of the appropriate
regulations,conformity and type approval certificates of the
sensors and power supply units.
Power supply and current signal are transmitted via the same
two-wire connection cable.The power supply range can differ
depending on the instrument version.The exact range is
stated in the "Technical data"in the "Supplement".
Provide a reliable separation between the supply circuit and
the mains circuits acc.to DIN VDE 0106 part 101.The VEGA
power supply units VEGATRENN 149AEx,VEGASTAB 690,
VEGADIS 371 as well as all VEGAMETs meet this require-
ment.
Bear in mind the following factors regarding supply voltage:
lthe reduction of the output voltage of the power supply unit
under nominal load (with a sensor current of 20.5mAor
22 mAin case of fault signal)
lthe influence of additional instruments in the circuit (see
load values in "Technical data").
VEGABAR 54 is connected with standard two-wire cable
without screen.An outer cable diameter of 5…9mm ensures
the seal effect of the cable entry.If strong electromagnetic
interference is expected,we recommend the use of screened
cable.
OnVEGABAR 54 with cable gland ½NPT and plastic housing,
a metal ½" threaded insert is moulded in the plastic housing.
Note safety instructions
Take note of safety
instructions for Ex
applications
Select power supply
Selecting the connection ca-
ble
Cable gland ½NPT
VEGABAR 54 -4…20 mA/HART 15
Connecting to power supply
29694-EN-051004

Caution:
No grease should be used when screwing the NPT cable
gland or steel tube into the threaded insert.Standard grease
can contain additives affecting the connection between
threaded insert and housing.This will influence the stability of
the connection and the tightness of the housing.
If screened cable is necessary,connect the cable screen on
both ends to ground potential.In the sensor,the screen must
be connected directly to the internal ground terminal.The
ground terminal outside on the housing must be connected to
the potential equalisation (low impedance).
If potential equalisation currents are expected,the connection
on the evaluation side must be made via a ceramic capacitor
(e.g.1nF,1500 V). The low frequency potential equalisation
currents are thus suppressed,but the protective effect against
high frequency interference signals remains.
Take note of the corresponding installation regulations for Ex
applications.In particular,make sure that no potential equal-
isation currents flow over the cable screen.In case of
grounding on both sides this can be achieved by the use of a
capacitor or a separate potential equalisation.
5.2Connection procedure
Proceed as follows:
1Unscrew the housing cover
2IfaPLICSCOM indicating and adjustment module is
installed,remove it by turning it slightly to the left.
3Loosen compression nut of the cable entry
4Remove approx.10 cm of the cable mantle,strip approx.
1cm insulation from the ends of the individual wires
5Insert the cable into the sensor through the cable entry
6Lift the opening levers of the terminals with a screwdriver
(see following illustration)
7Insert the wire ends into the open terminals according to
the wiring plan
8Press down the opening levers of the terminals,you will
hear the terminal spring closing
Cable screening and ground-
ing
Select connection
cable for Ex applica-
tions
Single/Double chamber hous-
ing
16 VEGABAR 54 -4…20 mA/HART
Connecting to power supply
29694-EN-051004

9Check the hold of the wires in the terminals by lightly
pulling on them
10 Connect the screen to the internal ground terminal and the
external ground terminal to potential equalisation
11 Tighten the compression nut of the cable entry,the seal
ring must completely encircle the cable
12 Screw the housing cover back on
The electrical connection is finished.
Fig.6:Connection steps 6and 7
Proceed as follows:
1Loosen the four screws on the housing socket with an Allen
key size 4
2Remove the mounting plate from the housing socket
IP 68 version with remote
housing -Non-Ex
VEGABAR 54 -4…20 mA/HART 17
Connecting to power supply
29694-EN-051004

3
2
1
Fig.7:Components of the remote housing for plics instruments
1Screws
2Wall mounting plate
3Cable gland
3Lead the connection cable through the cable gland on the
housing socket3)
Information:
The cable gland can be mounted in three positions each
displaced by 90°.Simply exchange the cable gland against the
blind stopper in the suitable thread opening.
4Connect the wire ends as described under "Single/Double
chamber housing"acc.to the numbering
5Connect the screen to the internal ground terminal and the
external ground terminal on top of the housing to potential
equalisation
6Tighten the compression nut of the cable entry,the seal
ring must completely encircle the cable.
7Attach the mounting plate again and tighten the screws
The electrical connection of the sensor to the remote housing
is finished.
3)The connection cable is already preconfectioned.If necessary shorten to
the requested length,cut the breather capillaries clean.Remove approx.
5cm of the cable mantle,strip approx.1cm insulation from the ends of the
individual wires.After shortening the cable,fasten the type plate with sup-
port back onto the cable.
18 VEGABAR 54 -4…20 mA/HART
Connecting to power supply
29694-EN-051004

Proceed as follows:
1Loosen the screw in the cover of the plug connector and
remove it
2Open the cover and remove it
3Press the plug insert downwards
4Loosen the screws of the strain relief and cable entry
4
32
1
3
2
1
Fig.8:Plug connector with opened cover
1Plug insert
2Strain relief
3Cable gland
4Housing
5Insert the connection cable through the cable entry and into
the plug housing4)
6Connect the wire ends to the screw terminals acc.to the
wiring plan
4)The connection cable is already preconfectioned.If necessary shorten to
the requested length,cut the breather capillaries clean.Remove approx.
5cm of the cable mantle,strip approx.1cm insulation from the ends of the
individual wires.After shortening the cable,fasten the type plate with sup-
port back onto the cable.
IP 68 version with remote
housing -Ex
VEGABAR 54 -4…20 mA/HART 19
Connecting to power supply
29694-EN-051004

3
1
2
Fig.9:Connection to the screw terminals
1Plug insert
2Housing
3Cable gland
7Insert the plug insert into the plug housing
Information:
Note correct alignment,see figure "Plug connector with open
cover"!
8Tighten the screws on the strain relief and cable entry
9Hook in the cover and press it onto the plug connector
10 Attach the plug seal,tighten the plug connector with the
screw
The electrical connection of the sensor to the remote housing
is finished.
5.3Wiring plans,single chamber housing
The following illustrations apply to the non-Ex as well as to the
Ex ia version.
20 VEGABAR 54 -4…20 mA/HART
Connecting to power supply
29694-EN-051004
Other manuals for VEGABAR 54
5
Table of contents
Other Vega Transmitter manuals

Vega
Vega VEGABAR 81 User manual

Vega
Vega VEGABAR 82 User manual

Vega
Vega VEGABAR 86 User manual

Vega
Vega VEGADIF 85 User manual

Vega
Vega VEGABAR 82 User manual

Vega
Vega VEGABAR 54 User manual

Vega
Vega VEGABAR 83 User manual

Vega
Vega VEGAWELL 52 User manual

Vega
Vega VEGABAR 82 User manual

Vega
Vega VEGABAR 83 User manual

Vega
Vega VEGADIF 65 User manual

Vega
Vega VEGABAR 82 User manual

Vega
Vega VEGABAR 87 User manual

Vega
Vega VEGABAR 82 User manual

Vega
Vega VEGABAR 81 User manual

Vega
Vega VEGABAR 82 User manual

Vega
Vega VEGABAR 51 User manual

Vega
Vega VEGADIF 65 User manual

Vega
Vega VEGADIF 85 User manual

Vega
Vega VEGABAR 82 User manual