Vega VEGADIF 65 User manual

Operating Instructions
VEGADIF 65
Foundation Fieldbus
Document ID:
36130
Differential pressure

Contents
1About this document
1.1Function.................................. 5
1.2Target group .............................. 5
1.3Symbolism used............................ 5
2For your safety
2.1Authorised personnel ........................ 6
2.2Appropriate use ............................ 6
2.3Warning about misuse ....................... 6
2.4General safety instructions .................... 6
2.5Safety label on the instrument .................. 7
2.6CE conformity ............................. 7
2.7Fulfillment of NAMUR recommendations .......... 7
2.8Safety instructions for Ex areas ................. 7
2.9Safety instructions for oxygen applications ......... 7
2.10 Environmental instructions..................... 7
3Product description
3.1Structure ................................. 9
3.2Principle of operation ........................ 10
3.3Operation................................. 14
3.4Packaging,transport and storage ............... 14
4Mounting
4.1General instructions to use the instrument ......... 16
4.2Instructions for oxygen and ultra-pure gas applications.17
4.3Mounting and connection instructions ............ 18
4.4Measurement setup flow ...................... 21
4.5Measurement setup level ..................... 23
4.6Measurement setup density and interface ......... 28
4.7Measurement setup differential pressure .......... 31
4.8Mounting external housing .................... 33
4.9Installation control........................... 33
5Connecting to power supply
5.1Preparing the connection ..................... 34
5.2Connection procedure........................ 35
5.3Single chamber housing ...................... 37
5.4Double chamber housing ..................... 39
5.5Double chamber housing Ex d ................. 40
5.6Version IP 66/IP 68,1bar ..................... 41
5.7External housing with version IP 68 .............. 41
5.8Switch on phase............................ 42
6Adjustment with the indicating and adjustment module
PLICSCOM
6.1Short description ........................... 44
6.2Insert indicating and adjustment module........... 44
6.3Adjustment system .......................... 46
2VEGADIF 65 •Foundation Fieldbus
Contents
36130-EN-110510

6.4Parameter description........................ 47
6.5Menu schematic ............................ 57
6.6Saving the parameter adjustment data ............ 60
7Operating with PACTware and other adjustment programs
7.1Connect the PC via VEGACONNECT ............ 61
7.2Parameter adjustment with PACTware ............ 62
7.3Parameter adjustment with AMS™.............. 62
7.4Saving the parameter adjustment data ............ 62
8Setup
8.1Select the mode............................ 63
8.2Flow measurement .......................... 63
8.3Level measurement ......................... 65
8.4Density and interface measurement .............. 69
8.5Differential pressure measurement............... 69
9Maintenance and fault rectification
9.1Maintenance .............................. 72
9.2Fault rectification ........................... 72
9.3Exchanging the electronics module .............. 74
9.4Exchanging the electronics module .............. 74
9.5Software update ............................ 74
9.6Instrument repair ........................... 75
10 Dismounting
10.1Dismounting steps .......................... 76
10.2Disposal ................................. 76
11 Supplement
11.1Technical data ............................. 77
11.2Information on Foundation Fieldbus .............. 90
11.3Dimensions ............................... 94
Supplementary documentation
Information:
Supplementary documents appropriate to the ordered version come
with the delivery.You can find them listed in chapter "Product
description".
Instructions manuals for accessories and replacement parts
Tip:
To ensure reliable setup and operation of your instrument,we offer
accessories and replacement parts.The corresponding instructions
manuals are:
l27720 -External indication VEGADIS 61
l34296 -Protective cover
l36132 -Electronics module DF60 for VEGADIF 65
VEGADIF 65 •Foundation Fieldbus 3
Contents
36130-EN-110510

Information:
Editing status:2011-05-09
4VEGADIF 65 •Foundation Fieldbus
Contents
36130-EN-110510

1About this document
1.1Function
This operating instructions manual provides all the information you
need for mounting,connection and setup as well as important
instructions for maintenance and fault rectification.Please read this
information before putting the instrument into operation and keep this
manual accessible in the immediate vicinity of the device.
1.2Target group
This operating instructions manual is directed to trained qualified
personnel.The contents of this manual should be made available to
these personnel and put into practice by them.
1.3Symbolism used
Information,tip,note
This symbol indicates helpful additional information.
Caution:If this warning is ignored,faults or malfunctions can
result.
Warning:If this warning is ignored,injury to persons and/or serious
damage to the instrument can result.
Danger:If this warning is ignored,serious injury to persons and/or
destruction of the instrument can result.
Exapplications
This symbol indicates special instructions for Ex applications.
lList
The dot set in front indicates a list with no implied sequence.
àAction
This arrow indicates a single action.
1Sequence
Numbers set in front indicate successive steps in a procedure.
VEGADIF 65 •Foundation Fieldbus 5
1About this document
36130-EN-110510

2For your safety
2.1Authorised personnel
All operations described in this operating instructions manual must be
carried out only by trained specialist personnel authorised by the plant
operator.
During work on and with the device the required personal protective
equipment must always be worn.
2.2Appropriate use
VEGADIF 65 is a differential pressure transmitter for measurement of
flow,level,differential pressure,density and interface.
You can find detailed information on the application range in chapter
"Product description".
Operational reliability is ensured only if the instrument is properly used
according to the specifications in the operating instructions manual as
well as possible supplementary instructions.
For safety and warranty reasons,any invasive work on the device
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by the manufacturer.Arbitrary
conversions or modifications are explicitly forbidden.
2.3Warning about misuse
Inappropriate or incorrect use of the instrument can give rise to
application-specific hazards,e.g.vessel overfill or damage to system
components through incorrect mounting or adjustment.
2.4General safety instructions
This is a high-tech instrument requiring the strict observance of
standard regulations and guidelines.The user must take note of the
safety instructions in this operating instructions manual,the country-
specific installation standards as well as all prevailing safety
regulations and accident prevention rules.
The instrument must only be operated in a technically flawless and
reliable condition.The operator is responsible for trouble-free
operation of the instrument.
During the entire duration of use,the user is obliged to determine the
compliance of the necessary occupational safety measures with the
current valid rules and regulations and also take note of new
regulations.
6VEGADIF 65 •Foundation Fieldbus
2For your safety
36130-EN-110510

2.5Safety label on the instrument
The safety approval markings and safety tips on the device must be
observed.
2.6CE conformity
This device fulfills the legal requirements of the applicable EC
guidelines.By attaching the CE mark,VEGA provides a confirmation
of successful testing.You can find the CE conformity declaration in the
download area of www.vega.com.
2.7Fulfillment of NAMUR recommendations
With respect to compatibility,the NAMUR recommendation NE 53 is
fulfilled.This applies also to the corresponding indicating and
adjustment components.VEGA instruments are generally upward and
downward compatible.
lSensor software to DTM VEGADIF 65
lDTM VEGADIF 65 for adjustment software PACTware
lIndicating and adjustment module for sensor software
The parameter adjustment of the basic sensor functions is independ-
ent of the software version.The range of available functions depends
on the respective software version of the individual components.
2.8Safety instructions for Ex areas
Please note the Ex-specific safety information for installation and
operation in Ex areas.These safety instructions are part of the
operating instructions manual and come with the Ex-approved
instruments.
2.9Safety instructions for oxygen applications
For instruments in oxygen applications the special instructions in
chapters "Storage and transport","Mounting"as well as "Technical
data"under "Process conditions"must be noted.Furthermore the valid
national regulations,implementation instructions and memorandums
of the professional assocations must be noted.
2.10 Environmental instructions
Protection of the environment is one of our most important duties.That
is why we have introduced an environment management system with
the goal of continuously improving company environmental protection.
The environment management system is certified according to DIN
EN ISO 14001.
Please help us fulfil this obligation by observing the environmental
instructions in this manual:
VEGADIF 65 •Foundation Fieldbus 7
2For your safety
36130-EN-110510

lChapter"Packaging,transport and storage"
lChapter "Disposal"
8VEGADIF 65 •Foundation Fieldbus
2For your safety
36130-EN-110510

3Product description
3.1Structure
The scope of delivery encompasses:
lVEGADIF 65 differential pressure transmitter
lDepending on the version ventilation valves and/or closing screws
lOptional accessory
lDocumentation
-this operating instructions manual
-Operating instructions manual 27835 "Indicating and adjust-
ment module PLICSCOM"(optional)
-Supplementary instructions manual 31708 "Heating for in-
dicating and adjustment module"(optional)
-Operating instructions 36133 "Chemical seal CSB"(optional)
-Operating instructions 36134 "Chemical seal CSS"(optional)
-Supplementary instructions manual "Plug connector for con-
tinuously measuring sensors"(optional)
-Ex-specific"Safety instructions"(with Ex versions)
-Certificate "Oil and grease-free for oxygen applications"(with
respective versions)
-if necessary,further certificates
The following illustration shows the components of VEGADIF 65:
+ –
1
2
3
Fig.1:VEGADIF 65 in basic version
1Housing cover,optionally with integrated indicating and adjustment module
2Housing with electronics
3Process component with measuring cell
The components are available in different versions.
The type label contains the most important data for identification and
use of the instrument:
Scope of delivery
Constituent parts
Type label
VEGADIF 65 •Foundation Fieldbus 9
3Product description
36130-EN-110510

lInstrument type
lArticle number instrument
lEx approval
lTechnical data:Measuring range,process pressure,process
temperature,signal output,voltage supply,protection,protection
class
lOrder number,serial number instrument
lHardware and software version
lArticle numbers,documentation
With the serial number,you can access the delivery data of the
instrument via www.vega.com,"VEGA Tools"and "serial number
search".In addition to the type label outside,you can also find the
serial number on the inside of the instrument.
3.2Principle of operation
VEGADIF 65 is a differential pressure transmitter for measurement of
flow,level,differential pressure,density and interface.Measured
products are gases,vapours and liquids.
Flow measurement
QQ
p1p1
p2p2
Q ~ p Q ~ p
++ ––
1 2
Fig.2:Flow measurement with VEGADIF 65 and DP flow element,Q=flow, Δp=
differential pressure, Δp=p
1
-p
2
1Orifice
2Pitot tube
Application area
10 VEGADIF 65 •Foundation Fieldbus
3Product description
36130-EN-110510

Level measurement
123
h = p
ρ g
+
+
––
h
+ –
Fig.3:Level measurement with VEGADIF 65. Δp=differential pressure,ρ=
density of the medium,g=acceleration of gravity
1Basic version with effective pressure lines
2Version with flange chemical seal
3Version with capillaries and cell chemical seals
Differential pressure measurement
+
2
1
Fig.4:Differential pressure measurement with VEGADIF 65
1Filter
2VEGADIF 65
VEGADIF 65 •Foundation Fieldbus 11
3Product description
36130-EN-110510

Density measurement
=∆p
hg
+
–
h
1
Fig.5:Density measurement with VEGADIF 65,h=defined mounting distance,
Δp=differential pressure,ρ=density of the medium,g=acceleration of gravity
1VEGADIF 65
Interface measurement
1
+
–
h
2
3
Fig.6:Interface measurement with VEGADIF 65
1VEGADIF 65
2Liquid with highest density
3Liquid with lowest density
Ametallic measuring cell is used as sensor element.The process
pressures are transmitted via the separating diaphragms and filling oils
to a resistance measuring bridge (semi-conductor technology).
The difference of the existing pressures generates a change of the
bridge voltage.This change is measured,further processed and
converted into a corresponding output signal.
Functional principle
12 VEGADIF 65 •Foundation Fieldbus
3Product description
36130-EN-110510

For connection to the processe,the marking "+"and "-"on the process
component in chapter "Mounting and connection instructions"must
hence be noted.The pressure effective on "+"goes positive,the
effective pressure on "-"goes negative into the calculation of the
pressure difference.
The configuration of the measuring cells differs depending on the
measuring range:
1
2
3
4
5
1
p2
p
Fig.7:Metallic measuring cell 10 mbar and 30 mbar -p
1
and p
2
process
pressures
1Measuring element
2Silicone diaphragm
3Separating diaphragm
4Filling oil
5Integrated overvoltage arrester
1
p2
p
12
3
4
Fig.8:Metallic measuring cell from 100 mbar -p
1
and p
2
process pressures
1Measuring element
2Overload diaphragm/Middle diaphragm
3Filling oil
4Separating diaphragm
Power is supplied via the H1Fieldbus.Atwo-wire cable according to
Fieldbus specification serves as carrier of both power and digital data
for multiple sensors.This cable can be operated in two versions:
lvia an H1interface card in the control system and additional power
supply
Power supply and bus
communication
VEGADIF 65 •Foundation Fieldbus 13
3Product description
36130-EN-110510

lvia aLinking device with HSE (High speed Ethernet)and
additional power supply according to IEC 61158-2
The DD (Device Descriptions)and CFF (capability files)necessary for
planning and configuration of your FF (Foundation Fieldbus)commu-
nication network are available in the download area of the VEGA
homepage www.vega.com under "Services -Downloads -Software -
Foundation Fieldbus".The appropriate certificates are also available
there.A CD with the appropriate files and certificates can be ordered
via e-mail under info@de.vega.com or by phone from one of the VEGA
agencies under the order number "DRIVER.S".
The backlight of the indicating and adjustment module is powered by
the sensor.Prerequisite is a certain level of operating voltage.
The data for power supply are specified in chapter "Technical data".
The optional heating requires its own operating voltage.You can find
details in the supplementary instructions manual "Heating for indicat-
ing and adjustment module".
This function is generally not available for approved instruments.
3.3Operation
The instrument can be adjusted with the following adjustment media:
lwith indicating and adjustment module
lwith the suitable VEGA DTM in conjunction with an adjustment
software according to the FDT/DTM standard,e.g.PACTware and
PC
la configuration tool
3.4Packaging,transport and storage
Your instrument was protected by packaging during transport.Its
capacity to handle normal loads during transport is assured by a test
according to DIN EN 24180.
The packaging of standard instruments consists of environment-
friendly,recyclable cardboard.For special versions,PE foam or PE foil
is also used.Dispose of the packaging material via specialised
recycling companies.
Caution:
Instruments for oxygen applications are sealed in PE foil and provided
with a label "Oxygen!Use no Oil".Remove this foil just before
mounting the instrument!See instruction under "Mounting".
Transport must be carried out under consideration of the notes on the
transport packaging.Nonobservance of these instructions can cause
damage to the device.
DD/CFF
Packaging
Transport
14 VEGADIF 65 •Foundation Fieldbus
3Product description
36130-EN-110510

The delivery must be checked for completeness and possible transit
damage immediately at receipt.Ascertained transit damage or
concealed defects must be appropriately dealt with.
Up to the time of installation,the packages must be left closed and
stored according to the orientation and storage markings on the
outside.
Unless otherwise indicated,the packages must be stored only under
the following conditions:
lNot in the open
lDry and dust free
lNot exposed to corrosive media
lProtected against solar radiation
lAvoiding mechanical shock and vibration
lStorage and transport temperature see chapter "Supplement -
Technical data -Ambient conditions"
lRelative humidity 20 …85 %
Transport inspection
Storage
Storage and transport
temperature
VEGADIF 65 •Foundation Fieldbus 15
3Product description
36130-EN-110510

4Mounting
4.1General instructions to use the instrument
Make sure that all parts of the instrument exposed to the process,in
particular the sensor element,process seal and process fitting,are
suitable for the existing process conditions.These include above all
the process pressure,process temperature as well as the chemical
properties of the medium.
You can find the specifications in chapter "Technical data"or on the
type label.
Use the recommended cables (see chapter "Connecting to power
supply")and tighten the cable gland.
You can give the instrument additional protection against moisture
penetration by leading the connection cable downward in front of the
cable entry.Rain and condensation water can thus drain off.This
applies mainly to outdoor mounting as well as installation in areas
where high humidity is expected (e.g.through cleaning processes)or
on cooled or heated vessels.
The ventilation for the electronics housing is realised via a filter
element in the vicinity of the cable glands.
2
1
2
1
2
1
1
2
Fig.9:Position of the filter element with single and double chamber housing
1Filter element for ventilation of the electronics housing
2Blind stopper
Information:
Make sure that the filter element is always free of buildup during
operation.Ahigh-pressure cleaner must not be used for cleaning.
Suitability for the pro-
cess conditions
Moisture
Ventilation
16 VEGADIF 65 •Foundation Fieldbus
4Mounting
36130-EN-110510

DP flow elements are calculated for certain pipeline and operating
data.Therefore,check the pipeline data before installation at the
measuring point and compare the measurement loop number.
Detailed instructions for mounting the DP flow element are stated in
DIN EN ISO 5167 as well as in the instrument documentation from the
respective manufacturer.
You will find general recommendations for the installation of effective
pressure lines in DIN 19210 "Effective pressure lines for flow systems"
or the corresponding national or international standards.When
installing effective pressure lines outdoors,consider applying suitable
anti-freeze protection,e.g.tube heating.Install effective pressure lines
with a monotonic downward slope of at least 10 %.
In case of strong vibrations at the application position,the instrument
version with external electronics should be used.
Higher process temperatures often mean also higher ambient
temperatures for electronics and connection cable.Make sure that the
upper temperature limits stated in chapter "Technical data"for the
environment of the electronics housing and connection cable are not
exceeded.
4.2Instructions for oxygen and ultra-pure gas
applications
Oxygen and other gases can be explosive when brought into contact
with oils,grease and plastics,so the following measures must also be
taken:
lAll components of the plant,such as e.g.measuring instruments
must be cleaned according to the requirements of BAM
(DIN 19247)
lDepending on the seal material,certain temperatures and
pressures must not be exceeded in oxygen applications,see
chapter "Technical data"
Danger:
Instruments for oxygen applications must be unpacked just before
mounting.After removing the protective cover of the process fitting,the
label "O₂"will be visible on the process fitting.Penetration of oil,
grease and dirt should be avoided.Danger of explosion!
We also offer oil and grease free instruments for special applications
such as e.g.ultra-pure gas.There are no special restrictions with
respect to the process conditions.
Effective pressure
transmitter
Effective pressure lines
Vibrations
Temperature limits
Oxygen applications
Pure gas applications
VEGADIF 65 •Foundation Fieldbus 17
4Mounting
36130-EN-110510

4.3Mounting and connection instructions
When connecting the VEGADIF 65 to the measurement loop,take
note of the plus/minus side of the process component.The plus side is
marked with a "+",the minus side with a "-"on the process component
next to the oval flanges.
+ –
2
1
Fig.10:Marking for plus/minus side on the process component
1Plus side
2Minus side
The following illustration shows the elements for a tube mounting and
an example for a mounting arrangement with valve block.
Connection plus/minus
side
Mounting arrangement
18 VEGADIF 65 •Foundation Fieldbus
4Mounting
36130-EN-110510

234
5
6
7
8
9
1
Fig.11:Mounting arrangement with tube mounting
1Strap for tube mounting
2Mounting bracket
3Ventilation valve
4Fixing screws
5VEGADIF 65
6PTFE seal
7 5-fold valve block
8Oval flange adapter
9Fixing screws
The use of the valve block with inlet and outlet valves allows simple
installation and setup of the differential pressure transmitter.The valve
block separates the differential pressure transmitter from the process
side and enables simple maintenance and checking of the measure-
ment loop.The integrated equalization valve ensures the same
pressure conditions on the plus and minus side during setup.The five-
fold valve block contains also two valves for checking/ventilating the
differential pressure transmitter after it is installed.
The valve block is used for direct connection to the differential
pressure transmitter.The following figure shows the connection of a 5-
fold valve block.
Valve block
Connection valve block
VEGADIF 65 •Foundation Fieldbus 19
4Mounting
36130-EN-110510

A:
A
1 2
43
5 7 89 6
2 2
3 1
8
4 6
7 9
5
Fig.12:Connection of a 5-fold valve block
1Process fitting
2Process fitting
3Check/Ventilate
4Check/Ventilate
5Valve for checking/ventilating
6Valve for checking/ventilating
7Inlet valve
8Inlet valve
9Breather valve
20 VEGADIF 65 •Foundation Fieldbus
4Mounting
36130-EN-110510
Other manuals for VEGADIF 65
6
Table of contents
Other Vega Transmitter manuals

Vega
Vega VEGABAR 86 User manual

Vega
Vega VEGABAR 86 User manual

Vega
Vega VEGABAR 64 User manual

Vega
Vega VEGABAR 80 Series Wiring diagram

Vega
Vega VEGABAR 81 User manual

Vega
Vega VEGABAR 51 User manual

Vega
Vega VEGABAR 54 User manual

Vega
Vega VEGABAR 67 User manual

Vega
Vega VEGABAR 82 User manual

Vega
Vega VEGABAR 17 User manual

Vega
Vega VEGABAR 81 User manual

Vega
Vega VEGABAR 66 User manual

Vega
Vega VEGABAR 83 User manual

Vega
Vega VEGABAR 83 User manual

Vega
Vega RMT-10 User manual

Vega
Vega VEGABAR 82 User manual

Vega
Vega VEGABAR 54 User manual

Vega
Vega VEGABAR 81 User manual

Vega
Vega VEGABAR 66 User manual

Vega
Vega T-25 User manual