Venitem RIO L User manual

MA-SE-RIO0-01-03 Manuale Rio eng rev3 Rev.3 Page 1 of 6
INSTALLATION MANUAL
SOUNDER MODELS
RIO L –RIO LS

MA-SE-RIO0-01-03 Manuale Rio eng rev3 Rev.3 Page 2 of 6
GENERAL DESCRIPTION
Sounder mod. RIO L self-powered 12 Vdc sounder with high-brightness low-consumption LED flashing unit –anti-opening and anti-
removal tamper –programmable sounds and timings –alarm counting –microprocessor self-check of: recharge, battery and
speaker with corresponding negative output for anomalies –possibility to choose the sounder trigger type –input for speaker
block –permanent or momentary optical indication of alarm system ON/FF (arming/disarming) –electronic circuit protected against
polarity inversion and tropicalized by resin immersion.
External cover and sounder base are in ABS while the internal cover is made of zinc-plated steel.
The tamper devices detecting removal, sounder opening, foam and shock are to be connected in series. In case of tamper attempt, they
open the contact between the two TAMPER terminals thus triggering off the alarm.
Sounder mod. RIO LS: technical features as RIO L with double micro switch anti-foam circuit provided of anti-shock technology against hard
hits.
TECHNICAL FEATURES
Voltage
Nominal battery recharge
13.0 13.8 Vdc
Minimum command
4.1 Vdc
Minimum supplying
10 Vdc
Max supplying
15 Vdc
Current
Max consumption from
control panel (for battery
recharge and sound)
500mA 100 mA
Battery consumption in
alarm
1.3 A +100/-300 mA
Flashing unit consumption
90mA 10 mA
Consumption in stand-by
15mA
Consumption from control
inputs
+0.5 mA @Vc=12V; -0.3 mA @Vc=0V
Open collector
-10mA Max
Fundamental frequency
See CHART 6
Sound pressure
See DIAGRAM 1
Life of LED flashing light
1,000,000 flashes
Timings
3 minutes, settable at 8 min
Battery
Housing capacity
12V 1.2Ah or 12V 2.2 Ah max
Duration in stand-by
120 hours using 12V 2.2 Ah model
Control panel command
2 or 3 wires
Tamper switch
N.C. 0.2 A max; cover opening and
sounder removal from wall
Mechanic
Cover
Painted ABS
Base
ABS
Internal cover
Zinc-plated steel
Flash cover
Polycarbonate
Temperature conditions
from –25° to +55° C
Environmental class
Class IV
IP protection
IP 44
Relative humidity condition
from 20% to 100% of RH
Size
330x220x110 (H x W x D)
Weight
1.850 gr
Standards compliance
T031:2014
EN50131-4:2010
Security
Grade 3

MA-SE-RIO0-01-03 Manuale Rio eng rev3 Rev.3 Page 3 of 6
MOUNTING:
1. Screw the sounder on the wall and check if the tamper works properly;
2. Insert the connection cables through the holes located on the lower part of the sounder base;
3. If necessary, modify the default settings by acting on the dipswitches as shown in the charts below;
4. Connect battery and power supplying to the alarm control panel;
5. Close both internal and external covers using the screws provided.
6. Battery must have UL94-HB flammability rate;
7. Power supply must be of SELV type
Attention: not to have condensation in the sounder, it is important to avoid any air flow inside the duct. To such purpose, once the
sounder is connected, seal the hole using some silicon or any other plaster. This operation prevents condensation from forming inside
the sounder; condensation mostly appears in winter and it is usually caused by warm and humid air coming out of the wall where the
sounder is installed and passing through the holes located on the sounder base.
CONNECTION SCHEMES
1. FOUR-WIRE CONNECTION
Connect 13.8 Volt supplying coming from control panel to the dedicated terminals:
-RIC negative; +RIC positive; +C positive-missing trigger; RES negative trigger for flash reset.
Note: by default, DIPSWITCH N°2 is set in OFF position, POSITIVE-MISSING TRIGGER
LEFT FLASH
RIGHT FLASH
ANTI-DRILLING
DIP
SWITCH
6
5
4
3
2
1
LED 1
TAMPER TERMINALS
LOUDSPEAKER
AND BATTERY
CONNECTOR
JUMPER 5
Negative Recharge
Positive Recharge
Positive missing trigger
Main tamper line
Micro-switch wires
MAIN
Flash reset trigger

MA-SE-RIO0-01-03 Manuale Rio eng rev3 Rev.3 Page 4 of 6
2. THREE-WIRE CONNECTION
Connect 13.8 Volt supplying coming from control panel to the dedicated terminals:
-RIC negative; +RIC positive. (+C trigger must be jumped to +RIC ); RES negative trigger for flash reset.
Note: by default, DIPSWITCH N°2 is set in OFF position, POSITIVE-MISSING TRIGGER
3. OPTICAL INDICATION OF SYSTEM STATUS (MOMENTARY OR PERMANENT ON-OFF)
If a positive is given to terminal STI (System status) all LEDs of the flashing light make 3 flashes (ON);
If the positive is removed, all LEDs light on steady for 5 seconds (OFF) and the complete sounder test is launched (remote test).
By default, DIPSWITCH N°4 is set in OFF position (MOMENTARY ON-OFF)
DIPSWITCH N°4 in ON position (MOMENTARY ON-OFF) and 1 LED keeping on flashing as long as positive tension = 0V is given to terminal STI.
4. SOUNDER TIMING
By default, timing is 3 minutes (DIPSWITCH N°1 in OFF position) and it can be modified into 8 minutes.
5. TERMINAL 5 - NEGATIVE SOUND-BLOCK INPUT
It gives a 0V signal to terminal 5 thus activating the sound interruption trigger.
6. TERMINAL OUT ANM AND FAULTS LED
The microcontroller managing the sounder is able to check if recharge, battery, loudspeaker and drivers are working properly. In case of faults, the
open collector output OUT ANM opens while the LED located on the sounder board shows the type of fault by making a certain number of flashes
followed by a short pause (please see chart here below for FAULTS LED signalisation).
The microcontroller automatically performs every 4 hours the battery current test. Moreover, other tests are performed on regular basis. Usually, if
the sounder is properly supplied, the faults output (terminal 7) remains at 0V (max consumption 50mA). In case any of the tests performed fails,
the faults output disconnects from the ground and becomes free. Moreover, the microprocessor is always under self-test and in case of failure or
malfunctioning, it gives a free output with sound interruption.
To reset the fault appeared: eliminate the fault cause. Then:
-(see scheme below): wait 10 seconds, let terminal n°4 (STI) free, take it to 12V, wait 10 seconds and let terminal n°4 free again. This procedure
resets all faults;
-all faults are anyway reset after every alarm (+C), with the exception of those concerning the battery that are reset after 4 hours from battery
restore (replacement). The sounder performs all tests again and therefore updates battery faults too.
At the first sounder supplying (13.8V or battery), anomalies automatically reset once the cause disappears; this makes the installation easier. After
the first activation of the sounder, anomalies reset through a command to STI terminal or through +C.
To launch the remote test, see scheme here above. This action launches the test that lasts 60 seconds. During the test, the sounder verifies if it is
working properly and provides signalization of any faults through the faults output (OUT ANM) and the faults LED as shown in CHART 1: FAULTS
below.
In case a fault occurs, the LEDs of the flashing light flash faster.
FREE
ELIMINATE FAULT CAUSE –10 SEC –FREE
12V
+12V
10 SEC
Negative Recharge
Positive Recharge
Positive recharge/command +13.8 Vdc
Main tamper line
Micro-switch wires
MAIN
Flash reset trigger

MA-SE-RIO0-01-03 Manuale Rio eng rev3 Rev.3 Page 5 of 6
CHART 1: FAULTS
FAULT TYPE
LED LD1
Output OUT ANM
Speaker interruption (test performed every 10s)
1 FLASH
OPEN
No recharge current (recharge V < 12V) (test performed every 10s)
2 FLASHES
OPEN
Battery not connected (test performed every 12 hours)
3 FLASHES
OPEN
Low battery (battery V < 10.5V) (test performed every 10s)
4 FLASHES
OPEN
Damaged battery –internal resistor over 3.5 Ohm (test performed every 12 hours)
5 FLASHES
OPEN
Speaker drivers failure
6 FLASHES
OPEN
No anomaly
OFF
0V
7. CONNECTION OF MICRO SWITCH ANTI-OPENING AND ANTI-REMOVAL TAMPER
Connect the tamper line coming from control panel in series to the two wires of micro switch located on the sounder using the dedicated terminals
TAMPER 8 and 9.
8. CONNECTION OF ANTI-FOAM (LS model)
Connect the two wires of the antifoam device in series to the micro switch and the tamper line coming from control panel.
Diagram 1
CONNECTION and SETTINGS
RIO LS DIP 3 in ON position
Angolo
dB (A) @1m
15°
102.3
45°
112.2
75°
113.2
105°
111.3
135°
108.7
165°
100.8
RIO L DIP 3 in ON position
Angolo
dB (A) @1m
15°
102.0
45°
110.6
75°
112.9
105°
111.8
135°
109.1
165°
100
Chart 3: wiring
Terminals
Connections
-RIC (1)
Negative supplying 0V GND
+RIC (2)
Positive supplying +13.8V
+C (3)
Sounder control chart 5
STI (4)
ON/OFF indication of alarm system status
5
Input for sound block
OUT ANM (6)
Fault output. Open collector, 0V = no anomaly
RES (7)
Flash reset
TAMPER (8)
Self-protection N.C.
TAMPER (9)
Self-protection N.C.
Chart 2: dipswitches and jumpers
DIP 1
Alarm timing
DIP 2
Polarity of alarm input +C
DIP 3
Tone selection
DIP 4
Alarm system STI (ON/OFF) notice setting
DIP 5
Flash reset mode
DIP 6
Alarm trigger mode +C
JUMPER
5
Max daily alarms
Chart 4: alarm timing
DIP
Alarm duration
OFF (default)
3 minutes
ON
8 minutes
Chart 5: polarity of alarm input +C
DIP 2
Terminal +C
OFF (default)
Positive-missing trigger (Alarm if not connected or 0V)
ON
Negative-missing trigger (Alarm if not connected or +12V)
112.9 dB (L)
113.2 dB (LS)

MA-SE-RIO0-01-03 Manuale Rio eng rev3 Rev.3 Page 6 of 6
INSTALLATION SUGGESTIONS
In case the sounder does not work properly, check if the on-board LED flashes. If it flashes, check FAULTS CHART here above.
WARRANTY
All Venitem products are granted against factory or material defects. In order to improve design and quality of the products, Venitem
reserves the right to modify the products without prior notice. All faulty or defective products must be returned to the supplier
Venitem srl
via del lavoro, 10 –30030 Salzano (VE)
Tel.: +39 041 5740374
Fax: +39 041 5740388
Website: www.venitem.com
Chart 6: tone selection
DIP 3
Tone
Frequency limits (Hz)
OFF (default)
Increasing-continuous-decreasing
1,200 ÷ 1,750
ON
Increasing-decreasing (NFC 48-265) –IMQ CERTIFIED
1,400 ÷ 1,600
Chart 7: Alarm system STI (ON/OFF) signalization setting
DIP 4
Terminal 4
Flash status (ON/OFF)
OFF (default)
+12V
All LEDs flash 3 times
Not connected or 0V
All LEDs remain steady on for 4 seconds then switch off
ON
+12V
All LEDs flash 3 times and 1 LED keeps on flashing
Not connected or 0V
All LEDs remain steady on for 4 seconds then switch off
Chart 8: flash reset mode
DIP 5
Flash behaviour –Terminals +C and RES
OFF (default)
Flash activates through +C trigger and deactivates through a negative signal to RES terminal (Flash reset)
ON
Flash activates through +C trigger and deactivates through +C trigger
Chart 9: Alarm trigger mode +C
DIP 6
Terminal +C
OFF (default)
Missing trigger
ON
Giving trigger
Chart 10: Max daily alarms
JUMPER 5
Number of alarms during 24 hrs after the first alarm
CONNECTED (default)
Infinite alarms
CUT
Restriction to 4 daily alarms (24 hours) of sound activation (STI resets the counter to zero)
Certified for Belgium
Compliant to T031
standards
This manual suits for next models
1
Table of contents
Other Venitem Marine Equipment manuals

Venitem
Venitem DOGE EV12 User manual

Venitem
Venitem GIUDECCA User manual

Venitem
Venitem SP200 User manual

Venitem
Venitem HOLA F24EN User manual

Venitem
Venitem HEMA L User manual

Venitem
Venitem ONDA User manual

Venitem
Venitem TRIADE F24 User manual

Venitem
Venitem DOGE EV12 User manual

Venitem
Venitem MINI MARINA L User manual

Venitem
Venitem RIALTO L Guide