
The UPS has its own battery charger and adopts advanced temperature compensation technology to effectively prolong
the battery service life. The inverter adopts three level T-type IGBT topology and uses advanced SVPWM control
technology to derive the stable AC voltage from the DC bus voltage. When the mains is normal, the rectifier and inverter
work together to supply the loads and charge the battery.
When the mains is abnormal, the rectifier stops working, and the battery supplies power to the loads through the inverter. If
the battery voltage falls to end of discharge (EOD) voltage and the mains still has not been recovered, the UPS will shut
down (if the system uses split bypass configuration and the bypass is normal, the system will transfer to bypass). The
battery EOD voltage is preset.
When the mains is abnormal, the battery maintains the UPS operation till the battery voltage is reduced to EOD voltage and
the UPS shuts down, this time is called 'Backup Time'. The length of backup time depends on the battery capacity and the
loads.
2.2.2 By pass
Through the intelligent control of the 'Static Switch' module (as shown in Figure 2.1 on the previous page) containing the
controllable electronic switch, the loads can be supplied by the inverter or the bypass. In normal situation, the loads are
supplied by the inverter, in this case the automatic inverter switch at inverter side is closed. In the case of overload (the
overload delay time expires) or inverter failure, the automatic inverter switch is opened, and the 'Static Switch' module will
automatically transfer the loads to the bypass.
In normal operating state, to realize the uninterrupted transfer between inverter and bypass, the inverter output must be
synchronized with the bypass.
Therefore, when the bypass frequency is within the synchronization range, the inverter control circuit will synchronize the
inverter output frequency with the bypass frequency and phase.
Besides, the UPS has a manual maintenance bypass switch for shutdown of the UPS upon maintenance. In this situation, the
bypass will directly supply the critical loads through the maintenance bypass.
N O T E : W h en th e lo ad is s u pp lied b y th e b yp ass o r m ain ten a n ce b yp as s , th e p o w er s u p ply qu ality w ill
b e u n certain .
2.2.3 S y stem C ontro l Prin ciple
N o rm al o peratio n
Normal mode: It means that the UPS has normal input mains, the rectifier and inverter operate normally, the load is supplied
by the inverter, the battery circuit breaker is closed, and the battery is in stable floating charge state.
P arallel SystemAs the UPS single module outputs are connected in parallel, the system checks that the inverter control
circuits are perfectly synchronized with one another and with the bypass in terms of both frequency and phase, and that
they have the same output voltages. Current supplied to the load is automatically divided among UPSs. A warning message
appears while synchronization is in progress.
M ain s abn o rm al
When the mains fails or is abnormal, the rectifier will stop working automatically, and the load will be catered by the battery
output (through inverter). The length of the operation time in battery mode depends on the load and the battery capacity.
During this period, if the battery voltage falls to the EOD voltage and the mains still has not been recovered, the inverter will
stop working automatically, and the UPS operator control and display panel will display corresponding alarm messages. If
the system uses split bypass configuration and the bypass is normal, the system will transfer to bypass.
2 Overview 7
Vertiv™ Liebert® EXM2 UPS User Manual