Product Information
The benefits at a glance:
HSpace heating circuit controlled by
room thermostat
HSingle-stage boiler control
HBuilt-in boiler low temperature
protection
HShort assembly time and start-up due
to diagnostic and Rast-5 plug-in
systems
Modular structure
The control unit consists of:
system ON/OFF switch, temperature
display, pump aquastat for boiler
protection,
–adjustable high limit
(type RAK 51.1/3382, Mfg. Etheco or
type TR 97.55180.251, Mfg. EGO)
–fixed high limit
(type RAK 75.4/3412, Mfg. Etheco or
type STW 56.10525.400, Mfg. EGO)
–electronic circuit board with power
supply
–quick-connect Rast-5 plug-in system
–fixed high limit test terminals
Vitotronic 100,Model KK5
HElectronic boiler control:
–for single-boiler systems
–for heating circuits without mixing
valve
–for a single-stage burner
–with analog temperature display
Boiler-specific functions
The Vitotronic 100 controls the boiler
temperature according to heat demand
input (room thermostat connections).
Boiler water temperature is limited
through the adjustable aquastat.
Minimum boiler water temperature
protection is achieved with the built-in
pump aquastat.
Standard Equipment
Vitotronic 100, Model KK5
(Part No. 7133 373)
with
Hadjustable and fixed high limit
Hbuilt-in pump aquastat
Hpower supply cord
Technical data
Operating Voltage: 120 VAC
Operating Frequency: 60 Hz
Nominal Current: 6A
Power Consumption: 10 W
Certification: CSA certified
(in conjunction with
Viessmann Vitorond boiler)
Max. ambient temperature:
–at operation: 32 to 104 ºF
0to 40ºC
(in rooms and installation sites
with normal ambient conditions)
–when storing or transporting:
–4 to +149 ºF
–20 to +65 ºC
Output rating:
–Heating circuit pump:3 FLA, 120 V
–Burner: 2 FLA, 120 V
Minimum boiler temperature protection
The minimum boiler water temperature is
selected with the adjustable pump
aquastat.
Application
In conjunction with the following Viessmann boilers
Boiler Model and Series
Fuel Minimum boiler water
temperature
without low
limit
with low limit
(average temp.)
Oil-fired hot water
heating boiler with
power burner
Vitorond 200 Oil 104 ºF/40 ºC
5265 489 v1.3 Technical information subject to change without notice. Printed on environmentally friendly