Warmup OCC2 User manual

Type OCC2
USER MANUAL
57426 01/06 - (BJ)
Type: OCC2 1
BR929A09
R
A
B
C
F
E
D
G
Buttons Display symbols
N
M
L
K
H
I
J
A: B: C: D:
E: F: G:
Pin button
adjust of
clock
On/off Reset to
factory
setting
Adjustment
down
OK -
accept Adjustment
up Display
H: I: J: K:
L: M: N:
Clock
function Manual
mode Time and
temperature Day number
Heating on %
Monitoring
of switch-on
time
4-event symbol
1. Getting started
Introduction
The OCC 2 thermostat is capable of switching on your heating system at pre determined times on different days of the week. It is possible to set 4 periods
called events each day with different temperatures. From factory a default schedule is programmed suitable for most installations. Unless you change these
settings the thermostat will operate to this default program.
Working with lower temperatures during times that the room is unoccupied will lower your energy costs without reducing the comfort. The thermostat has an
adaptive function that automatically changes the start time of a heating period so that the desired temperature is reached at the time that you set. After 3
days the adaptive function has learned when the heating must be switched on.
Type OCC2-1991H1 has an external temperature sensor that is normally placed in the floor construction. In this configuration the thermostat controls the
temperature of the floor and not the temperature within the room.
Type OCC2-1999H1 has a built-in temperature sensor. In this configuration the thermostat controls the temperature of the room, and the external
temperature sensor should not be installed.
The thermostat has a pin button marked R, allowing you to reset the thermostat to factory settings. These are listed at the end of this manual with space for
you to record your own weekly schedule.
The display is backlit when operating the buttons. The heating element is switched off when the light is on in the display.
The heating system can be switched off on the built-in interrupter. The Microprocessor taking care of the time will still be supplied with power whereby time
and day will be maintained. When the heating is required and the thermostat is switched on, it will continue the 4-event programme based on present time
and day.
Setting the thermostat into operation
☞
☞
1-7
Press the UP ( ) or DOWN ( ) buttons to
select the correct time and press OK button ( ).
Then press the UP ( ) or DOWN ( ) button to
select the correct day and press OK ( ) button.
First time power is connected the clock and day will be flashing and must be set. If you need to
adjust the time of the thermostat at a later date, insert a pin into the hole for setting of time
and day. Adjustment must be made for summer and winter time.
Wake
Night
Out
Home
2. Daily use of the thermostat
4-event clock mode
The day has been split into 4 events describing a typical day. When the thermostat is in 4-event mode it will automatically adjust the temperature according
to the required temperature to the required time. As standard the thermostat has 5 days with 4 events, and 2 days with 2 events. Programming see 3.
4-event clock mode:
Comfort mode:
☞
☞
Manual mode:
☞
☞
Temporary override
To temporarily override the temperature in the 4-event schedule program, press the UP ( ) or DOWN ( ) button
once, to show the temperature, and press again to increase or decrease the temperature. The display will flash for
5 seconds, and will then revert to the time. The override will operate until the next programmed event when the
unit will resume the automatic programme.
The clock function symbol ( ) and one of the 4-event symbols ( ) will be indicated.
Programming see 3.
Cancel comfort mode
To cancel the override state, press the OK ( ) button twice.
Permanent override:
During holidays, the scheduled 4-event program can be overridden.
Press the OK ( ) button, and then the UP ( ) or DOWN ( ) button until the override temperature is set.
The unit will now operate to this temperature permanently.
Cancel manual mode
To cancel the permanent override state press the OK ( ) button once, and the unit will resume automatic function.
5 secs.
5 secs.
☞
☞
☞
☞
☞
☞
☞
☞
Press OK ( ) button for 3 secs. to begin programming
: Time and temperature
: Time and temperature
: Time and temperature
: Time and temperature
Day 1 - 5
Day 6 - 7
☞ ☞
: Time and temperature
☞ ☞
: Time and temperature
3. Programming
4-event time and temperature
For each event, the start time and required
temperature must be set.
For example, in the morning you wish the heating to
start at 07:00 and the temperature to rise to 25˚C.
Press OK ( ) button for 3 seconds and the start time
is displayed. Change this to 07:00 with the
UP ( ) or DOWN ( ) button. Press OK ( ) to
confirm.
The temperature is now displayed. Change this to 25˚C
with the UP ( ) or DOWN ( ) button.
Press OK ( ) button to confirm. This action can now
be repeated for the second event.
These settings will be valid with days 1-5 showing on
the display. To program the days 6 and 7, repeat the
above. Days 6 and 7 are usually Saturday and Sunday,
and only have two events.
The temperature can be set within the range of +5 to
+40˚C. It is also possible to select the heating OFF at
that event by reducing the setting to 5˚C, and then
pressing the ( ) once more.
22
Monitoring of energy consumption
The thermostat calculates average time it has been switched on allowing you to monitor your energy consumption.
In the thermostat you can read out:. Total switch-on time in percentage in the latest 2 days, 30 days or 365 days.
Calculation of operational costs per day: (switch-on time:100) x kW x kWh-price x 24 h per day
Example: Read-out: 30 % in the latest 365 days
Size of heating system: 1,2 kW (ask the installer)
Cost of power: 0,2 EUR / kWh
Calculation: (30:100) x 1,2 kW x 0,2 EUR / kWh x 24 h = 1,7 EUR per day
4. Advanced settings and read-out
4-event sequence
The present event sequence flashes: Days 1-5, followed by days 6-7. To change, press the UP ( ) button until you have days 1-6
and then day 7 flashing, or all 7 days are flashing. Select the required sequence with the OK ( ) button.
☞✚
☞
☞
5-2: 4 events in 5 days +
2 events in 2 days.
6-1: 4 events in 6 days +
2 events in 1 day
7-0: 4 events in 7 days
☞
☞
}
2 days
30 days
365 days
Software version
Actual sensor temperature
}
Max and min allowed temperature range
The temperature setting range of +5˚ to 40˚ C can be limited to prevent at comfort or manual mode a too high or too low temperature
being selected. For example, a wood floor covering should not be allowed to exceed a maximum of 27˚C. Low limitation is used where
the temperature of the floor is required never to fall below the minimum set temperature.
Time and temperature scale selection
Adaptive function
This function enables the thermostat to calculate when it needs to switch ON so that the required temperature is reached at the set
time. With a start time of 07:00 therefore, the thermostat may switch ON as early as 06:00 so that the desired temperature of 25˚C is
achieved by 07:00. Without this function set, the thermostat will start to heat at the time you set.
☞
☞
☞
☞
Maximum allowed temperature setting. Use the UP ( ) or
DOWN ( ) button to increase or reduce, and OK ( ) button to
accept.
Next is displayed LoLi. Press OK ( ) button to continue.
Minimum allowed temperature setting. Use the UP ( ) or
DOWN ( ) button to increase or reduce and OK ( ) button to
accept.
You can select either ˚C or ˚F scale, and 12 or 24 hour clock as
follows:
Press UP ( ) or DOWN ( ) button to change settings. Confirm
the required scale with the OK button ( ) button.
☞
☞
}
}
☞
☞
☞
☞
☞
Press the DOWN ( ) button to switch between on and off.
Press OK ( ) button to confirm.
Press OK ( ) button to end programming and to return to
scheduled programme.
☞
☞
☞
☞
Press both UP ( ) and DOWN ( ) buttons together for 3 seconds. INFO is displayed.
Press UP( ) button until you reach the desired sub menu. Select the sub menu with the OK ( ) button.
Press UP ( ) or DOWN ( ) button to show the different
readouts.
No changes can be made here. Use the OK ( ) button to end.
3
Press the pin button for 3 secs. and the thermostat returns to factory settings. Time
and day is also reset and must be set according to “Setting the thermostat into
operation”.
5. Reset to factory setting
4-event time and temperature
Day 1-5
06:00
Time Temperature
08:00
16:00
22:30
08:00
23:00
Hi-Low temp.
5:2
24 H / ˚C
ON
4-event sequence
Scale
Adaptive control
Day 6-7
25˚C
OCC2-1991
w/floor sensor OCC2-1999
w/room sensor
20˚C
15˚C
22˚C
15˚C
22˚C
15˚C
28˚C / 15˚C
20˚C
27˚C
20˚C
27˚C
20˚C
55˚C / 5˚C
6. Failure codes
E0 = Internal failure, replace thermostat
E1 = Built-in sensor short-circuit or disconnected, replace thermostat
E2 = External sensor short-circuit or disconnected
Warmup Plc
702 Tudor Estate
Abbey Road
London
NW10 7UW
T. +44 845 345 2288
F. +44 845 345 2299
warmup.com
Factory settings
4

Other manuals for OCC2

1

Other Warmup Thermostat manuals

Warmup 5iE Quick start guide

Warmup

Warmup 5iE Quick start guide

Warmup Tempo User manual

Warmup

Warmup Tempo User manual

Warmup Luxury 2 LUXY2D44 User manual

Warmup

Warmup Luxury 2 LUXY2D44 User manual

Warmup TH115 A User manual

Warmup

Warmup TH115 A User manual

Warmup 3IE User manual

Warmup

Warmup 3IE User manual

Warmup 3IE User manual

Warmup

Warmup 3IE User manual

Warmup 6iE User manual

Warmup

Warmup 6iE User manual

Warmup One User manual

Warmup

Warmup One User manual

Warmup 5iE User manual

Warmup

Warmup 5iE User manual

Warmup PT502 Manual

Warmup

Warmup PT502 Manual

Warmup Portrait 4iE Installation instructions

Warmup

Warmup Portrait 4iE Installation instructions

Warmup 4iE WiFi User manual

Warmup

Warmup 4iE WiFi User manual

Warmup konekt WIRELESS KW-UKETRV User manual

Warmup

Warmup konekt WIRELESS KW-UKETRV User manual

Warmup OTN-1991-WA User manual

Warmup

Warmup OTN-1991-WA User manual

Warmup Element User manual

Warmup

Warmup Element User manual

Warmup konekt WIRELESS KW-STATH User manual

Warmup

Warmup konekt WIRELESS KW-STATH User manual

Warmup ELTPB User manual

Warmup

Warmup ELTPB User manual

Warmup WA-TSTAT-V User manual

Warmup

Warmup WA-TSTAT-V User manual

Warmup + Kit User manual

Warmup

Warmup + Kit User manual

Warmup UCCG Installation manual

Warmup

Warmup UCCG Installation manual

Warmup Terra RSW Series User manual

Warmup

Warmup Terra RSW Series User manual

Warmup MTC-1991-WU User manual

Warmup

Warmup MTC-1991-WU User manual

Warmup TH115-AF-GA User manual

Warmup

Warmup TH115-AF-GA User manual

Warmup 6iE User manual

Warmup

Warmup 6iE User manual

Popular Thermostat manuals by other brands

PNI CT25PW user manual

PNI

PNI CT25PW user manual

Galletti reko TDV manual

Galletti

Galletti reko TDV manual

OERTLI OE-tronic 3 manual

OERTLI

OERTLI OE-tronic 3 manual

nest Learning thermostat installation guide

nest

nest Learning thermostat installation guide

Hessaire HTH01 quick start guide

Hessaire

Hessaire HTH01 quick start guide

Network Thermostat NetX X Series Installation and programming manual

Network Thermostat

Network Thermostat NetX X Series Installation and programming manual

Mercato ABC806FCT-4 series Installation and operation manual

Mercato

Mercato ABC806FCT-4 series Installation and operation manual

Thermona PT59X quick start guide

Thermona

Thermona PT59X quick start guide

TUYA MCS 750 Instructions for use and installation

TUYA

TUYA MCS 750 Instructions for use and installation

HOTOWELL HTW-31-WKT13-WF manual

HOTOWELL

HOTOWELL HTW-31-WKT13-WF manual

AMX ENV-VST-C Operation/reference guide

AMX

AMX ENV-VST-C Operation/reference guide

hager 54185 User instructions

hager

hager 54185 User instructions

Airzone AZX6CSMASTER Series Installation and user manual

Airzone

Airzone AZX6CSMASTER Series Installation and user manual

Sonder Siesta -TA Series instruction manual

Sonder

Sonder Siesta -TA Series instruction manual

Derale 16720 installation instructions

Derale

Derale 16720 installation instructions

Heatit Controls HEATIT Z-TRM3 Installer manual

Heatit Controls

Heatit Controls HEATIT Z-TRM3 Installer manual

LK Systems SR 310 installation instructions

LK Systems

LK Systems SR 310 installation instructions

Honeywell Y9420H Sundial RF2 installation instructions

Honeywell

Honeywell Y9420H Sundial RF2 installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.