weintek cMT3108XH Series User manual

Installation and Startup Guide
This document covers the installation of cMT3108XH Series HMI, for the detailed specifications and
operation, please refer to Datasheet, Brochure and EasyBuilder Pro User Manual. Please read all
warnings, precautions, and instructions on the device carefully before use.
Install Environment:
NEMA Rating
The HMI product is NEMA 4 rated, indoor use only.
Electrical
Environment
The HMI product has been tested to conform to European CE requirements. This
means that the circuitry is designed to resist the effects of electrical noise. This
does not guarantee noise immunity in severe cases. Proper wire routing and
grounding will insure proper operation.
Environmental
Considerations
(1) Make sure that the displays are installed correctly and that the operating
limits are followed. Avoid installing units in environments where severe
mechanical vibration or shocks are present.
(2) The HMI product is certified in accordance with ATEX zone 2/22 categories
3 G/D. The unit has to be installed in an additional enclosure ensuring a
minimal protection level for 3G/D equipment. The enclosure equipped with
the unit has to be certified and shouldn’t be opened when an explosive
atmosphere is present.
(3) Do not install the unit where acid gas, such as SO2 exists.
(4) This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5) For use in Pollution Degree 2 Environment and dry location.
(6) Relative Humidity: 10% ~ 90% (non-condensing)
Cleaning
Considerations
Clean the device using dry cloths. Do not use liquid or spray detergents for
cleaning.
IP Rating
IP 66
Warning
Protection impairment if used in a manner not specified by the manufacturer.
Déficit de protection si utilisé d'une manière non spécifiée par le fabricant.
Unpacking the Unit
Unpack and check the delivery. If damage is found, please contact the supplier.
NOTE: Place the operator panel on a stable surface during installation. Dropping it or letting it
fall may cause damage.
The package includes:
(1) Installation Instruction, 2-sidedA4 *1 (2) Human Machine Interface *1 (3) Power Connector *1
(4) Brackets & Screws *1 pack (5) USB Stick Clamp & Tying Strap *1
Installation Instructions
Use a control box that provides enough stiffness. Cutout
Dimension: 255 mm x 185 mm. Secure the operator panel in
position, using all the fastening holes and the provided
brackets and screws. Screw Torque: 2.6 ~ 3.9 lbf.in. (For
reaching waterproof effect and preventing the panel from
being deformed.)
Plan for adequate space around the unit and inside the enclosure, for ventilation and cables. Consider
the heat from other devices insidethe enclosure. The ambient temperature around the unit must be 0 ~
55°C
Minimum required clearances (along the overlay): Top 15 mm / Bottom 50 mm / Sides 80 mm
Maximum panel thickness: 4.5 mm
USB Stick Clamp Usage
Combining the USB Stick with the clamp and the tying strap can prevent USB stick from disconnecting
with HMI when strong vibration is present.
1. Insert the USB connector to the clamp and tie them together with the tying strap.
2. Press the spring and insert the USB stick into HMI.
Expansion Module and Magnetic Mount Antenna
1. Connect the expansion module by inserting it into the given slot in HMI’s rear cover.
2. Tighten the module to HMI’s rear cover using two M3*8L screws.
3. Lock the antenna’s SMA connector to the module’s connector.
Please reserve space for installing the antenna with minimum bend radius taken into consideration, in
order to prevent physical damage to the antenna or impairment of the antenna’s performance.
Power Connections
Power Connector Specifications:
Wire AWG: 24~12
Wiring Conductor Minimum Temperature: 75°C
Screw Torque: 4.5 lbf-in (max.)
Copper conduct only.
Spécifications du connecteur d'alimentation:
AWG de fil: 24 ~ 12
Température minimale du conducteur de câblage: 75°C
Couple de vis: 4.5 lbf-in (max.)
Conducteur en cuivre seulement
NOTE:
1. Connect positive DC line to the ‘+’ terminal and the DC ground to the
‘-’ terminal.
2. When downloading project using a USB cable, do not connect HMI
with PLC and PC simultaneously, for electric potential difference may
result in damage to HMI or PC.
cMT3108XH series
Installation Instruction
3
4
1
2
System Settings
When HMI is powered up and displays image, press the round
Start Button in the upper-left corner of the screen to open the
Setting dialog box. Tap the lock icon and log in. (Default
System Password: 111111)
Go to the Network tab, and setup your network.
In Setting dialog box you can see device information, configure
general settings, set HMI Time/Date/Name, and more.
EasyBuilder Pro Software Settings
Launch EasyBuilder Pro software, select your project file, press F7 shortcut key to open the download
dialog box: Select Ethernet > IP tab > Enter your HMI IP > Click Download to download this project file
to HMI.
Using screensaver and backlight saver is recommended in order to avoid image persistence caused
by displaying the same image on HMI for a long time.
(Please refer to EasyBuilder Pro User Manual for software operation details.)
Communication Connections
NOTE:
1. Only Tx & Rx (no RTS/CTS) may be used for COM1 RS232 when COM3 RS-232 is also used.
2. COM2 and COM3 RS-485 2W support MPI 187.5K, please use one at a time.
Con.B Con.A
COM1/COM3 [RS232] 9 Pin, Male, D-sub COM2/COM3 [RS485]/CAN Bus 9 Pin, Female, D-sub
Touchscreen Calibration & Restore Factory Default
Touchscreen Calibration:
Press and hold anywhere on the screen when HMI starts until it enters touchscreen calibration mode.
Restore Factory Default:
Follow Step 5 to open the Settingdialog box. Go to "Reset options" tab, press the button of “Reset HMI
to default”. An Attention window shows, enter “yes”.
Another way to restore factory default is entering “default111111”when logging in. An Attention window
shows, enter “yes”.
Please note that the projects and data stored in the unit are all cleared after restoring factory default.
Battery Replacement
Battery Specification: Type CR2032, Rated 3V
Battery replacement shall be performed by qualified personnel (engineer) only and care must be taken
when handling lithium batteries. For more information on battery replacement and disposal
considerations, please refer to the following link:
http://www.weintek.com/download/MT8000/eng/FAQ/FAQ_103_Replace_Battery_en.pdf
NOTE: Make sure that all local and national electrical standards are met when
installing the unit. Contact your local authorities to determine which codes apply.
Power
Use power output that meets SELV (Safety Extra-Low Voltage) requirements. The unit can be
powered by DC power only, voltage range: 24±20%, compatible with most controller DC
systems. The power conditioning circuitry inside the unit is accomplished by a switching power
supply. The peak starting current can be as high as 2A.
Fusing Require-
ments
If the display does not come on within 5 seconds of power up, remove power. A resettable fuse
will protect against overcurrent faults in DC circuit and the resetting will take place after a period
of time. Check wiring for proper connections and try to power up again.
High Voltage
A resettable fuse will prevent damage for overcurrent condition however it isn’t guaranteed.
DC voltage sources should provide proper isolation from main AC power and similar hazards.
Emergency Stop
A Hard-wired EMERGENCY STOP should be fitted in any system using an HMI to comply with
ICS Safety Recommendations.
Supply Voltage
Condition
Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same
power supply. Note: The 24 VDC output from some controllers may not have enough current to
power the unit.
Wire Routing
a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).
b. Please use twisted pair cables for power wire and signal wire and conform to the
impedance matching.
c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression
devices.
d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.
e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power
supply and the frame ground. This provides a path for static and high frequency
dissipation. Typical values to use are 1M Ohm and 4700pF.
Hardware
Considerations
The system designer should be aware that devices in Controller systems could fail and
thereby create an unsafe condition. Furthermore, electrical interference in an operator
interface can lead to equipment start-up, which could result in property damage and/or
physical injury to the operator.
If you use any programmable control systems that require an operator, be aware that this
potential safety hazard exists and take appropriate precautions. Although the specific design
steps depend on your particular application, the following precautions generally apply to
installation of solid-state programmable control devices, and conform to the guidelines for
installation of Controllers recommended in NEMA ICS 3-304 Control Standards.
Programming
Considerations
To conform to ICS Safety Recommendations, checks should be placed in the controller to
ensure that all writable registers that control critical parts of plant or machinery have limit
checks built into the program, with an out-of-limit safe shut down procedure to ensure safety of
personnel. GMEC3A8X0_cMT3108XH_Installation_230515
CAUTION
DANGER
6
7
5
PIN#
COM1
[RS232] 4W
COM3
[RS232] 2W
1
2
RxD
3
TxD
4
5
GND
6
7
RTS
TxD
8
CTS
RxD
9
GND
Limited Warranty
This product is limited warranted against defects in design and manufacture.
The proven defective product will either be repaired or replaced, at Weintek’s discretion.
This warranty shall not cover any product which is
(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products.
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.
PIN#
COM2
[RS485]2W
COM2
[RS485]4W
COM3
[RS485]2W
CAN
Bus
1
Data-
Rx-
2
Data+
Rx+
3
Tx-
4
Tx+
5
GND
6
Data-
7
CAN_L
8
CAN_H
9
Data+
8
9

Other weintek Control Panel manuals

weintek MT-8000 Series User manual

weintek

weintek MT-8000 Series User manual

weintek MT6071iE Series User manual

weintek

weintek MT6071iE Series User manual

weintek MT607iE User manual

weintek

weintek MT607iE User manual

weintek HMIVT8071iE Series User manual

weintek

weintek HMIVT8071iE Series User manual

weintek MT6071iP Series User manual

weintek

weintek MT6071iP Series User manual

weintek cMT3072XH2 Series User manual

weintek

weintek cMT3072XH2 Series User manual

weintek cMT3072X2 Series User manual

weintek

weintek cMT3072X2 Series User manual

weintek MT6071 Series User manual

weintek

weintek MT6071 Series User manual

weintek MT8073iE Series User manual

weintek

weintek MT8073iE Series User manual

weintek cMT-FHDX User manual

weintek

weintek cMT-FHDX User manual

weintek cMT-FHDX User manual

weintek

weintek cMT-FHDX User manual

weintek MT8103iE Series User manual

weintek

weintek MT8103iE Series User manual

weintek MT-8080T User manual

weintek

weintek MT-8080T User manual

weintek cMT-iPC10 series User manual

weintek

weintek cMT-iPC10 series User manual

weintek cMT3090 Series User manual

weintek

weintek cMT3090 Series User manual

weintek MT8071iER1 Series User manual

weintek

weintek MT8071iER1 Series User manual

weintek cMT2166X Series User manual

weintek

weintek cMT2166X Series User manual

weintek MT-6050iV3 Series User manual

weintek

weintek MT-6050iV3 Series User manual

weintek cMT3108XP Series User manual

weintek

weintek cMT3108XP Series User manual

weintek MT8101iE Series User manual

weintek

weintek MT8101iE Series User manual

weintek MT6072 Series User manual

weintek

weintek MT6072 Series User manual

weintek MT600iWP Series User manual

weintek

weintek MT600iWP Series User manual

weintek cMT3162X Series User manual

weintek

weintek cMT3162X Series User manual

weintek cMT-SVR Series User manual

weintek

weintek cMT-SVR Series User manual

Popular Control Panel manuals by other brands

GE NetworX NX-8E user manual

GE

GE NetworX NX-8E user manual

BOSSLASER LS Series Operator's manual

BOSSLASER

BOSSLASER LS Series Operator's manual

Ansul AutoPulse Z-28 Ext installation instructions

Ansul

Ansul AutoPulse Z-28 Ext installation instructions

Emerson E2 Installation and operation manual

Emerson

Emerson E2 Installation and operation manual

DMP Electronics XR2400F installation guide

DMP Electronics

DMP Electronics XR2400F installation guide

Ecolab MD421-P Software manual

Ecolab

Ecolab MD421-P Software manual

Videofied XV 210 installation manual

Videofied

Videofied XV 210 installation manual

WAGO PERSPECTO WP 57 QVGA manual

WAGO

WAGO PERSPECTO WP 57 QVGA manual

Junkers TR 100 instruction manual

Junkers

Junkers TR 100 instruction manual

Incite Fire Syncro AS product manual

Incite Fire

Incite Fire Syncro AS product manual

MOOSE Z1100E How to use

MOOSE

MOOSE Z1100E How to use

Profelmnet 3033 manual

Profelmnet

Profelmnet 3033 manual

Immergas MAGIS M4-30 instructions

Immergas

Immergas MAGIS M4-30 instructions

Pro-tec Digilite installation manual

Pro-tec

Pro-tec Digilite installation manual

SIGMA TEK 1U619-001 installation manual

SIGMA TEK

SIGMA TEK 1U619-001 installation manual

Johnson Controls YORK OPTIVIEW CONTROL CENTER Operation manual

Johnson Controls

Johnson Controls YORK OPTIVIEW CONTROL CENTER Operation manual

Divus Touchzone Series user manual

Divus

Divus Touchzone Series user manual

System Sensor PDRP-2001E instruction manual

System Sensor

System Sensor PDRP-2001E instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.