Installation and Startup Guide
This document covers the installation of MT8073iE Series HMI, for the detailed specifications and
operation, please refer to Brochure and EasyBuilder Pro User Manual.
Install Environment:
NEMA Rating
The HMI product is NEMA 4 rated (Indoor Only).
Electrical
Environment
The HMI product has been tested to conform to European CE requirements. This
means that the circuitry is designed to resist the effects of electrical noise. This
does not guarantee noise immunity in severe cases. Proper wire routing and
grounding will insure proper operation.
Environmental
Considerations
(1) Make sure that the displays are installed correctly and that the operating
limits are followed. Avoid installing units in environments where severe
mechanical vibration or shocks are present.
(2) The HMI product is certified in accordance withATEX zone 2/22 categories
3 G/D. The unit has to be installed in an additional enclosure ensuring a
minimal protection level for 3G/D equipment. The enclosure equipped with
the unit has to be certified and shouldn’t be opened when an explosive
atmosphere is present.
(3) Do not install the unit where acid gas, such as SO2 exists.
(4) This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5) Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in
Pollution Degree 2 Environment.
Unpacking the Unit
Unpack and check the delivery. If damage is found,
notify the supplier.
Installation Instructions
Secure the operator panel in position, using all the fastening holes and the provided brackets
and screws. Screw Torque: 2.6 ~ 3.9 lbf.in. (For reaching waterproof effect and preventing the panel
from being deformed.)
Type
A(mm)
B(mm)
MT8073iE
192
138
USB Stick Clamp Usage
Combining the USB Stick with the clamp and the tying strap can prevent USB stick from disconnecting
with HMI when strong vibration is present.
1. Insert the USB connector to the clamp and tie them together with the tying strap.
2. Press the spring and insert the USB stick into HMI.
Power Connections
System Settings
When HMI is powered up and displays image, press the
system setting button in the lower-right corner of the screen.
(Default System Password: 111111)
Go to the Network tab, you may choose to auto get DHCP IP, or
designate your own IP.
MT8073iE has two10/100/1000 Base-T Ethernet ports.
The default IP addresses are:
LAN 1: DHCP
LAN 2: 192.168.100.1
MT8073iE series
Installation Instruction
1
2
NOTE:
Place the operator panel on a stable
surface during installation. Dropping it or
letting it fall may cause damage.
NOTE:
1. Connect positive DC line to the ‘+’ terminal and the DC
ground to the ‘-’terminal.
2. When using a USB cable to download project file, please
do not connect HMI with PLC and PC simultaneously to
prevent potential difference from destroying USB ports of
HMI and PC.
(A)
(B)
Cutout
3
5
4
(1)
(2)
(3)
(5) (4)
(6)
(1) Installation Instruction, 2-sided A4 *1
(2) Human Machine Interface *1
(3) Power Connector *1
(4) Brackets & Screws *1 pack
(5) USB Stick Clamp & Tying Strap *1
(6) Fuse 1.25A/250V 5*20mm *1
EasyBuilder Pro Software Settings
Launch EasyBuilder Pro software, select your
project file, press F7 shortcut key to open
the download dialog box:
Select Ethernet > IP tab > Enter your HMI IP
> Click Download to download this project
file to HMI.
( Please refer to EasyBuilder Pro User Manual
for software operation details )
Communication Connections
COM1 / COM3 [RS232] 9 Pin, Male, D-sub COM2 / COM3 [RS485] 9 Pin, Female, D-sub
DIP SW Settings
Another way to enter touch screen calibration mode is: Press and hold anywhere on the screen for
more than 2 seconds when HMI starts.
Limited Warranty
This product is limited warranted against defects in design and manufacture.
The proven defective product will either be repaired or replaced, at Weintek’s discretion.
This warranty shall not cover any product which is
(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products.
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.
PIN#
COM1 [RS232]
COM3 [RS232]
1
2
RxD
3
TxD
4
5
GND
6
7
RTS
TxD
8
CTS
RxD
9
GND
PIN#
COM2 [RS485]
COM3 [RS485]
2w
4w
1
Data-
Rx-
2
Data+
Rx+
3
Tx-
4
Tx+
5
GND
6
Data-
7
8
9
Data+
SW1
SW2
SW3
SW4
Mode
ON
OFF
OFF
OFF
Touch Screen Calibration Mode
OFF
ON
OFF
OFF
Hide HMI System Setting Bar
OFF
OFF
ON
OFF
Boot Loader Mode
OFF
OFF
OFF
ON
Not supported
OFF
OFF
OFF
OFF
Normal
NOTE: 1. COM2 and COM3 [RS485] 2W support MPI 187.5K, please use one at one time.
2. Only Tx & Rx (no RTS/CTS) may be used for COM1 RS-232 when COM3 RS-232
is also used.
6
7
8
Power
The unit can be powered by DC power only, voltage range: 24±20% Volts DC, compatible with
most controller DC systems. The power conditioning circuitry inside the unit is accomplished by a
switching power supply. The peak starting current can be as high as 2A.
Fusing
Require-
ments
If the display does not come on within 5 seconds of power up, remove power. An internal fuse will
prevent damage if the polarity of the DC power is incorrect. Check wiring for proper connections
and try to power up again.
High
Voltage
An Internal fuse will prevent damage for overcurrent condition however it isn’t guaranteed. DC
voltage sources should provide proper isolation from main AC power and similar hazards.
Emergency
Stop
A Hard-wired EMERGENCY STOP should be fitted in any system using HMI to comply with ICS
Safety Recommendations.
Supply
Voltage
Condition
Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same
power supply. Note: The 24 VDC output from some controllers may not have enough current to
power the
unit.
Wire
Routing
a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).
b. Please use twisted pair cables for power wire and signal wire and conform to the impedance
matching.
c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices.
d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.
e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power
supply and the frame ground. This provides a path for static and high frequency dissipation.
Typical values to use are 1M Ohm and 4700pF.
CAUTION
NOTE: Make sure that all local and national electrical standards are met when
installing the unit. Contact your local authorities to determine which codes apply.
Hardware
Considerations
The system designer should be aware that devices in Controller systems could fail and thereby
create an unsafe condition. Furthermore, electrical interference in an operator interface can lead to
equipment start-up, which could result in property damage and/or physical injury to the operator.
If you use any programmable control systems that require an operator, be aware that this potential
safety hazard exists and take appropriate precautions. Although the specific design steps depend on
your particular application, the following precautions generally apply to installation of solid-state
programmable control devices, and conform to the guidelines for installation of Controllers
recommended in NEMA ICS 3-304 Control Standards.
Programming
Considerations
To conform with ICS Safety Recommendations, checks should be placed in the controller to ensure
that all writable registers that control critical parts of plant or machinery have limit checks built into
the program, with an out-of-limit safe shut down procedure to ensure safety of personnel.
GME8073E0_MT8073iE1_Installation_160722
DANGER
CAUTION
NOTE:
Make sure that all local and national electrical standards are met when installing
the unit. Contact your local authorities to determine which codes apply.

Other weintek Control Panel manuals

weintek MT6071 Series User manual

weintek

weintek MT6071 Series User manual

weintek MT8101iE Series User manual

weintek

weintek MT8101iE Series User manual

weintek MT-6050iV3 Series User manual

weintek

weintek MT-6050iV3 Series User manual

weintek cMT3162X Series User manual

weintek

weintek cMT3162X Series User manual

weintek MT8071iER1 Series User manual

weintek

weintek MT8071iER1 Series User manual

weintek cMT-FHDX User manual

weintek

weintek cMT-FHDX User manual

weintek cMT3090 Series User manual

weintek

weintek cMT3090 Series User manual

weintek MT-8080T User manual

weintek

weintek MT-8080T User manual

weintek MT6072 Series User manual

weintek

weintek MT6072 Series User manual

weintek MT607iE User manual

weintek

weintek MT607iE User manual

weintek MT6071iE Series User manual

weintek

weintek MT6071iE Series User manual

weintek M02 User guide

weintek

weintek M02 User guide

weintek cMT-FHDX User manual

weintek

weintek cMT-FHDX User manual

weintek cMT-SVR Series User manual

weintek

weintek cMT-SVR Series User manual

weintek cMT2166X Series User manual

weintek

weintek cMT2166X Series User manual

weintek MT8103iE Series User manual

weintek

weintek MT8103iE Series User manual

weintek MT6071iP Series User manual

weintek

weintek MT6071iP Series User manual

weintek cMT-iPC10 series User manual

weintek

weintek cMT-iPC10 series User manual

weintek cMT3108XH Series User manual

weintek

weintek cMT3108XH Series User manual

weintek cMT3072X2 Series User manual

weintek

weintek cMT3072X2 Series User manual

weintek HMIVT8071iE Series User manual

weintek

weintek HMIVT8071iE Series User manual

weintek MT-8000 Series User manual

weintek

weintek MT-8000 Series User manual

weintek cMT3072XH2 Series User manual

weintek

weintek cMT3072XH2 Series User manual

weintek MT600iWP Series User manual

weintek

weintek MT600iWP Series User manual

Popular Control Panel manuals by other brands

Stramatel Multisport 452 operating instructions

Stramatel

Stramatel Multisport 452 operating instructions

UPS Aviation Technologies 10 user guide

UPS Aviation Technologies

UPS Aviation Technologies 10 user guide

Bentel Omnia user manual

Bentel

Bentel Omnia user manual

Furman RS1 owner's manual

Furman

Furman RS1 owner's manual

United Technologies Interlogix Advisor Advanced ATS1000A-SM Manager manual

United Technologies

United Technologies Interlogix Advisor Advanced ATS1000A-SM Manager manual

TechNexion TOUCAN TC-0710 SLIM HMI product manual

TechNexion

TechNexion TOUCAN TC-0710 SLIM HMI product manual

Ziton ZP2 Series Protocol guide

Ziton

Ziton ZP2 Series Protocol guide

Teletek electronics iRIS8 User Operation & Maintenance Manual

Teletek electronics

Teletek electronics iRIS8 User Operation & Maintenance Manual

Fabman Bridge FB-V2 user manual

Fabman

Fabman Bridge FB-V2 user manual

marklin 72720 quick start guide

marklin

marklin 72720 quick start guide

See Water Oil Smart OSSIM-30 Installation and operation manual

See Water

See Water Oil Smart OSSIM-30 Installation and operation manual

Mitsubishi GT2715XTBA installation manual

Mitsubishi

Mitsubishi GT2715XTBA installation manual

Northern N-1000-III Installation and programming manual

Northern

Northern N-1000-III Installation and programming manual

VTS Medical Systems HMI WING HY manual

VTS Medical Systems

VTS Medical Systems HMI WING HY manual

Panasonic AV-HS60C4E operating instructions

Panasonic

Panasonic AV-HS60C4E operating instructions

Balboa TP500 user guide

Balboa

Balboa TP500 user guide

CBE PC380-ST user manual

CBE

CBE PC380-ST user manual

Garmin GPSMAP 8X10 owner's manual

Garmin

Garmin GPSMAP 8X10 owner's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.