weintek MT607iE User manual

Installation and Startup Guide
This document covers the installation of MT607/610iE Series HMI, for the detailed specifications and
operation, please refer to Brochure and Windows CE User Manual.
Install Environment:
NEMA Rating
MT607/610iE Series HMI is NEMA 4 rated (Indoor Only).
Electrical
Environment
The MT607/610iE Series has been tested to conform to European CE
requirements. This means that the circuitry is designed to resist the effects of
electrical noise. This does not guarantee noise immunity in severe cases. Proper
wire routing and grounding will insure proper operation.
Environmental
Considerations
(1) Make sure that the displays are installed correctly and that the operating
limits are followed. Avoid installing units in environments where severe
mechanical vibration or shocks are present.
(2) Do not operate the unit in areas subject to explosion hazards due to
flammable gases, vapors or dusts.
(3) Do not install the unit where acid gas, such as SO2 exists.
(4) This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5) Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in
Pollution Degree 2 Environment.
Unpacking the Unit
Unpack and check the delivery. If damage is found,
notify the supplier.
Installation Instructions
Secure the operator panel in position, using all the fastening holes and the provided brackets
and screws:
Type
A(mm)
B(mm)
MT607iE
192
138
MT610iE
260
202
Power Connections
Calibration Mode
There are two ways to start calibration mode.
Way 1: Flip DIP SW1 to ON position and then turn on HMI power.
Way 2: Click [Touch Screen] in CECP and then click [Calibrate] button.
MT607iE MT610iE series
Installation Instruction
1
2
NOTE:
Place the operator panel on a stable
surface during installation. Dropping it or
letting it fall may cause damage.
NOTE:
1. Connect positive DC line to the ‘+’ terminal
and the DC ground to the ‘-’terminal.
2. Please do not connect HMI with PLC and PC
simultaneously to prevent potential difference
from destroying USB ports of HMI and PC.
(A)
(B)
Cutout
(1)
(2)
(5)
(4)
(3)
(1) Installation Instruction, 2-sided A4 *1
(2) Human Machine Interface *1
(3) Power Connector *1
(4) Brackets & Screws *1 pack
(5) Fuse 1.25A/250V 5*20mm *1
3
5
4
( Note 1: For the details of HMI DIP SW function settings please refer to Part 8 in this guide. )
System Setting
Click [Start] > [Programs] > [CECPv2] to
open the CECP windowfor touch screen
calibration, backlight adjustment, screen
rotation, COM port mode selection, and
more.
Communication Connections
9 Pin, Male, D-sub
COM1 [RS232]
9 Pin, Female, D-sub
COM1 / COM3 [RS485]
DIP SW Settings
CAUTION
NN
NOTE:
Make sure that all local and national electrical standards are met when installing
the unit. Contact your local authorities to determine which codes apply.
PIN#
Symbol
COM1 [RS232]
1
Not used
2
RxD
Received Data
3
TxD
Transmitted Data
4
Not used
5
GND
Signal Ground
6
Not used
7
RTS
Ready to send output
8
CTS
Clear to send input
9
Not used
PIN#
Symbol
Com1
[RS485]2w
Com1
[RS485]4w
Com3
[RS485]
1
Rx-
Data-
Rx-
2
Rx+
Data+
Rx+
3
Tx-
Tx-
4
Tx+
Tx+
5
GND1
Ground1
6
Not used
7
Data-
Data-
8
Data+
Data+
9
GND2
Ground2
SW1
SW2
SW3
SW4
Mode
ON
OFF
OFF
OFF
Touch Screen Calibration Mode
OFF
ON
OFF
OFF
Reserved
OFF
OFF
ON
OFF
Boot Loader Mode
OFF
OFF
OFF
ON
Reserved
OFF
OFF
OFF
OFF
Normal
NOTE: 1. COM1 and COM3 [RS485] 2W support MPI 187.5K, please use one at one time.
2. COM1 [RS485] / COM3 [RS485] with isolation protection.
6
7
8
Limited Warranty
This product is limited warranted against defects in design and manufacture.
The proven defective product will either be repaired or replaced, at Weintek’s discretion.
This warranty shall not cover any product which is
(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products.
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.
Power
The HMI can be powered by DC power only, voltage range: 24±20% Volts DC, compatible with
most controller DC systems. The power conditioning circuitry inside the unit is accomplished by a
switching power supply. The peak starting current can be as high as 2A.
Fusing
Require-
ments
If the display does not come on within 5 seconds of power up, remove power.An internal fuse will
prevent damage if the polarity of the DC power is incorrect. Check wiring for proper connections
and try to power up again.
High
Voltage
An Internal fuse will prevent damage for overcurrent condition however it isn’t guaranteed. DC
voltage sources should provide proper isolation from main AC power and similar hazards.
Emergency
Stop
A Hard-wired EMERGENCY STOP should be fitted in any system using HMI to comply with ICS
Safety Recommendations.
Supply
Voltage
Condition
Do not power the HMI and inductive DC loads, or input circuitry to the controller, with the same
power supply. Note: The 24 VDC output from some controllers may not have enough current to
power the HMI.
Wire
Routing
a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).
b. Please use twisted pair cables for power wire and signal wire and conform to the impedance
matching.
c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices.
d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.
e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power
supply and the frame ground. This provides a path for static and high frequency dissipation.
Typical values to use are 1M Ohm and 4700pF.
CAUTION
NOTE: Make sure that all local and national electrical standards are met when
installing the unit. Contact your local authorities to determine which codes apply.
Hardware
Considerations
The system designer should be aware that devices in Controller systems could fail and thereby
create an unsafe condition. Furthermore, electrical interference in an operator interface can lead to
equipment start-up, which could result in property damage and/or physical injury to the operator.
If you use any programmable control systems that require an operator, be aware that this potential
safety hazard exists and take appropriate precautions. Although the specific design steps depend on
your particular application, the following precautions generally apply to installation of solid-state
programmable control devices, and conform to the guidelines for installation of Controllers
recommended in NEMA ICS 3-304 Control Standards.
Programming
Considerations
To conform with ICS Safety Recommendations, checks should be placed in the controller to ensure
that all writable registers that control critical parts of plant or machinery have limit checks built into
the program, with an out-of-limit safe shut down procedure to ensure safety of personnel.
GME607611_MT607_610iE_Installation_140314
DANGER

This manual suits for next models

1

Other weintek Control Panel manuals

weintek MT6072 Series User manual

weintek

weintek MT6072 Series User manual

weintek MT-8080T User manual

weintek

weintek MT-8080T User manual

weintek cMT-SVR Series User manual

weintek

weintek cMT-SVR Series User manual

weintek MT-6050iV3 Series User manual

weintek

weintek MT-6050iV3 Series User manual

weintek MT6071 Series User manual

weintek

weintek MT6071 Series User manual

weintek cMT3072XH2 Series User manual

weintek

weintek cMT3072XH2 Series User manual

weintek cMT3108XH Series User manual

weintek

weintek cMT3108XH Series User manual

weintek cMT-iPC10 series User manual

weintek

weintek cMT-iPC10 series User manual

weintek MT600iWP Series User manual

weintek

weintek MT600iWP Series User manual

weintek MT8071iER1 Series User manual

weintek

weintek MT8071iER1 Series User manual

weintek cMT3090 Series User manual

weintek

weintek cMT3090 Series User manual

weintek MT6071iE Series User manual

weintek

weintek MT6071iE Series User manual

weintek MT8103iE Series User manual

weintek

weintek MT8103iE Series User manual

weintek cMT3162X Series User manual

weintek

weintek cMT3162X Series User manual

weintek M02 User guide

weintek

weintek M02 User guide

weintek HMIVT8071iE Series User manual

weintek

weintek HMIVT8071iE Series User manual

weintek cMT3108XP Series User manual

weintek

weintek cMT3108XP Series User manual

weintek MT6071iP Series User manual

weintek

weintek MT6071iP Series User manual

weintek MT8073iE Series User manual

weintek

weintek MT8073iE Series User manual

weintek MT-8000 Series User manual

weintek

weintek MT-8000 Series User manual

weintek cMT-FHDX User manual

weintek

weintek cMT-FHDX User manual

weintek cMT3072X2 Series User manual

weintek

weintek cMT3072X2 Series User manual

weintek cMT-FHDX User manual

weintek

weintek cMT-FHDX User manual

weintek cMT2166X Series User manual

weintek

weintek cMT2166X Series User manual

Popular Control Panel manuals by other brands

GESTRA SPECTORcontrol user manual

GESTRA

GESTRA SPECTORcontrol user manual

SALUPO EVO 3 MULTI Instruction and installation manual

SALUPO

SALUPO EVO 3 MULTI Instruction and installation manual

tau D750M installation guide

tau

tau D750M installation guide

Kramer RC-712M user manual

Kramer

Kramer RC-712M user manual

SJE Rhombus 123 Installation Instructions and Operation/Troubleshooting Manual

SJE Rhombus

SJE Rhombus 123 Installation Instructions and Operation/Troubleshooting Manual

FAAC 460-P manual

FAAC

FAAC 460-P manual

Miranda iMC-Panel-300 Operator's guide

Miranda

Miranda iMC-Panel-300 Operator's guide

AERMEC PXA I Use and installation  manual

AERMEC

AERMEC PXA I Use and installation manual

Carel MCH200TP00 instructions

Carel

Carel MCH200TP00 instructions

iO HVAC Controls ZP2-HC-ESP Installation and operation instructions

iO HVAC Controls

iO HVAC Controls ZP2-HC-ESP Installation and operation instructions

Advanced ExGo Series manual

Advanced

Advanced ExGo Series manual

AES EPIC 1D Installation and use manual

AES

AES EPIC 1D Installation and use manual

Teuco 613 user manual

Teuco

Teuco 613 user manual

Honeywell Gent Viglion EN54 Generic Commissioning Instructions

Honeywell

Honeywell Gent Viglion EN54 Generic Commissioning Instructions

Ross Ultrix Acuity Operation manual

Ross

Ross Ultrix Acuity Operation manual

Xylem FLYGT EOP1 Installation, operation and maintenance manual

Xylem

Xylem FLYGT EOP1 Installation, operation and maintenance manual

Simplex MINIPLEX 4100ES Series quick start guide

Simplex

Simplex MINIPLEX 4100ES Series quick start guide

Aksa DSE 6020 AMF operating manual

Aksa

Aksa DSE 6020 AMF operating manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.