WIKA TR36 User manual

DE
EN
Operating instructions
Betriebsanleitung
Mode d’emploi
Manual de instrucciones
ES
FR
Threaded resistance thermometer, model TR36
Threaded resistance thermometer, model TR36
Widerstandsthermometer zum Einschrauben, Typ TR36
Sonde à résistance à raccord leté, type TR36
Termorresistencia roscada, modelo TR36

2
14331645.02 07/2021 EN/DE/FR/ES
WIKA operating instructions model TR36
DE
EN
FR
ES
Operating instructions model TR36 Page 3 - 30
Betriebsanleitung Typ TR36 Seite 31 - 58
Mode d'emploi type TR36 Page 59 - 86
Manual de instrucciones modelo TR36 Página 87 - 114
© 06/2021 WIKA Alexander Wiegand SE & Co. KG
All rights reserved. / Alle Rechte vorbehalten.
WIKA®is a registered trademark in various countries.
WIKA®ist eine geschützte Marke in verschiedenen Ländern.
Prior to starting any work, read the operating instructions!
Keep for later use!
Vor Beginn aller Arbeiten Betriebsanleitung lesen!
Zum späteren Gebrauch aufbewahren!
Lire le mode d‘emploi avant de commencer toute opération !
A conserver pour une utilisation ultérieure !
¡Leer el manual de instrucciones antes de comenzar cualquier trabajo!
¡Guardar el manual para una eventual consulta!

EN
WIKA operating instructions model TR36
14331645.02 07/2021 EN/DE/FR/ES
3
Contents
Contents
Declarations of conformity can be found online at www.wika.com.
1. General information 4
2. Design and function 5
3. Safety 8
4. Transport, packaging and storage 12
5. Commissioning, operation 13
6. Conguration 18
7. Conguration software WIKAsoft-TT 19
8. Connecting the PU-548 programming unit 21
9. Faults 22
10. Maintenance and cleaning 23
11. Dismounting, return and disposal 24
12. Specications 26

EN
14331645.02 07/2021 EN/DE/FR/ES
4WIKA operating instructions model TR36
1. General information
■
The resistance thermometer described in the operating instructions
has been designed and manufactured using state-of-the-art
technology. All components are subject to stringent quality and
environmental criteria during production. Our management systems
are certied to ISO 9001 and ISO 14001.
■
These operating instructions contain important information on handling
the instrument. Working safely requires that all safety instructions and
work instructions are observed.
■
Observe the relevant local accident prevention regulations and
general safety regulations for the instrument's range of use.
■
Skilled personnel must have carefully read and understood the
operating instructions prior to beginning any work.
■
Subject to technical modications.
■
Further information:
- Internet address: www.wika.de / www.wika.com
- Relevant data sheet: TE 60.36
- Application consultant: Tel.: +49 9372 132-0
1. General information

EN
WIKA operating instructions model TR36
14331645.02 07/2021 EN/DE/FR/ES
5
2. Design and function
2.1 Overview
Angular connector DIN EN 175301-803 form A
Process connection
Probe tube
2.2 Description
The model TR36 resistance thermometer consists of a thermowell/
protection tube with a xed process connection and is screwed directly
into the process.
If the resistance thermometer is to be operated in an additional
protection tube, a spring-loaded compression tting must be used.
They are designed to be resistant to shock and vibration and all electrical
components are protected against splash water.The vibration resistance
conforms to IEC 60751 (8 g, dependent on the instrument version). The
impact resistance of all versions meets the requirements of IEC 60751.
2. Design and function

EN
14331645.02 07/2021 EN/DE/FR/ES
6WIKA operating instructions model TR36
Ensure that mechanical loads on the connector are minimised,
especially in case of increased ambient temperatures or strong vibration
loads.
The electrical connection is made via an angular connector
DIN 175301-803, form A.
2.3 Dimensions in mm
■
Process connection with parallel thread (or without process
connection)
2. Design and function
Angular connector
DIN EN 175301-803
without process
connection
with compression
tting
with neck tube
Legend:
A Insertion length
NNeck tube length (70 mm)
Ød Probe diameter
At a process temperature of > 150 °C [302 °F], a neck tube length N of 70 mm is
necessary.
A
ca. 74 mm
[approx. 2.913 inch]
Ø27mm
[Ø1.062 inch]
SW27
Hex27
ca. 48 mm
[approx. 1.889 inch]
14352572.03
11 mm
[0.433 inch]
N
A
14 mm
[0.551 inch]
A
70 mm
[2.755 inch]
Ø6/8 mm
[Ø0.236/0.314 inch]
Ød ≥ 3mm
≥ [0.118 inch]
Ød ≥ 3mm
≥ [0.118 inch]
Ød ≥6 mm
≥ [0.236 inch]
Ød ≥6 mm
≥ [0.236 inch]
14352572.03

EN
WIKA operating instructions model TR36
14331645.02 07/2021 EN/DE/FR/ES
7
A
Ød
1/4NPT - ca.15mm [0.590 inch]
1/2NPT - ca.20mm [0.787 inch]
Ød>=6mm [0.236 inch]
A65 mm
[2.559 inch]
ca. 74 mm
[2.913 inch]
Ø27 mm
[Ø1.062 inch]
ca. 48 mm
[approx.1.889 inch]
ca. 60 mm
[approx. 2.362 inch]
20 mm
[0.787 inch]
Ød
N
11318708.03
A
Ød
1/4NPT - ca.15mm [0.590 inch]
1/2NPT - ca.20mm [0.787 inch]
Ød>=6mm [0.236 inch]
A65 mm
[2.559 inch]
ca. 74 mm
[2.913 inch]
Ø27 mm
[Ø1.062 inch]
ca. 48 mm
[approx.1.889 inch]
ca. 60 mm
[approx. 2.362 inch]
20 mm
[0.787 inch]
Ød
N
11318708.03
■
Process connection with tapered thread
2. Design and function
Legend:
A Insertion length
NNeck tube length (70 mm)
Ød Probe diameter
At a process temperature of > 150 °C [302 °F], a neck tube length N of 70 mm is
necessary.
11318708.03
2.4 Scope of delivery
Cross-check scope of delivery with delivery note.
Angular connector
DIN EN 175301-803
with compression
tting
with neck tube

EN
14331645.02 07/2021 EN/DE/FR/ES
8WIKA operating instructions model TR36
3. Safety
3.1 Explanation of symbols
WARNING!
... indicates a potentially dangerous situation that can result
in serious injury or death, if not avoided.
CAUTION!
... indicates a potentially dangerous situation that can result in
light injuries or damage to property or the environment, if not
avoided.
DANGER!
... identies hazards caused by electric power. Should the
safety instructions not be observed, there is a risk of serious
or fatal injury.
WARNING!
... indicates a potentially dangerous situation that can result
in burns, caused by hot surfaces or liquids, if not avoided.
Information
... points out useful tips, recommendations and information
for ecient and trouble-free operation.
3.2 Intended use
The model TR36 resistance thermometer is used as universal
thermometer for the measurement of liquid and gaseous media in
the range -50 … +150 °C [-58 ... +302 °F] (without neck tube) and
-50 … +250 °C [-58 ... +482 °F] (with neck tube). It can be used for
pressures up to 140 bar [2,030 psi], 270 bar [3,916 psi] or 400 bar
[5,801 psi] - depending on the protection tube diameters.
3. Safety

EN
WIKA operating instructions model TR36
14331645.02 07/2021 EN/DE/FR/ES
9
The instrument has been designed and built solely for the intended use
described here, and may only be used accordingly.
The technical specications contained in these operating instructions
must be observed. Improper handling or operation of the instrument
outside of its technical specications requires the instrument to be taken
out of service immediately and inspected by an authorised WIKA service
engineer.
The manufacturer shall not be liable for claims of any type based on
operation contrary to the intended use.
3.3 Improper use
WARNING!
Injuries through improper use
Improper use of the instrument can lead to hazardous
situations and injuries.
▶Refrain from unauthorised modications to the instrument.
▶Do not use the instrument within hazardous areas.
▶Do not use the instrument with abrasive or viscous media.
Any use beyond or dierent to the intended use is considered as
improper use.
Do not use this instrument in safety or emergency stop devices.
3.4 Responsibility of the operator
The instrument is used in the industrial sector. The operator is therefore
responsible for legal obligations regarding safety at work.
The safety instructions within these operating instructions, as well as the
safety, accident prevention and environmental protection regulations for
the application area must be maintained.
The operator is obliged to maintain the product label in a legible
condition.
3. Safety

EN
14331645.02 07/2021 EN/DE/FR/ES
10 WIKA operating instructions model TR36
To ensure safe working on the instrument, the operating company must
ensure
■
that suitable rst-aid equipment is available and aid is provided
whenever required.
■
that the operating personnel are regularly instructed in all topics
regarding work safety, rst aid and environmental protection
and know the operating instructions and, in particular, the safety
instructions contained therein.
■
that the instrument is suitable for the particular application in
accordance with its intended use.
■
that personal protective equipment is available.
3.5 Personnel qualication
WARNING!
Risk of injury should qualication be insucient!
Improper handling can result in considerable injury and
damage to property.
▶The activities described in these operating instructions
may only be carried out by skilled personnel who have the
qualications described below.
▶Keep unqualied personnel away from hazardous areas.
Skilled electrical personnel
Skilled electrical personnel are understood to be personnel who,
based on their technical training, know-how and experience as well
as their knowledge of country-specic regulations, current standards
and directives, are capable of carrying out work on electrical systems
and independently recognising and avoiding potential hazards.The
skilled electrical personnel have been specically trained for the work
environment they are working in and know the relevant standards and
regulations.The skilled electrical personnel must comply with current
legal accident prevention regulations.
Special operating conditions require further appropriate knowledge, e.g.
of aggressive media.
3. Safety

EN
WIKA operating instructions model TR36
14331645.02 07/2021 EN/DE/FR/ES
11
3.6 Labelling, safety marks
Product labels (example)
Model
Date of manufacture (year-month)
Approval logos
Information on version (measuring element, output signal, measuring range ...)
Serial number, Tag number
Before mounting and commissioning the instrument,
ensure you read the operating instructions!
3. Safety

EN
14331645.02 07/2021 EN/DE/FR/ES
12 WIKA operating instructions model TR36
4. Transport, packaging and storage
4.1 Transport
Check the instrument for any damage that may have been caused by
transport.
Obvious damage must be reported immediately and damaged
instruments must not be used.
CAUTION!
Damage through improper transport
With improper transport, a high level of damage to property
can occur.
▶When unloading packed goods upon delivery as well as
during internal transport, proceed carefully and observe
the symbols on the packaging.
▶With internal transport, observe the instructions in chapter
4.2 “Packaging and storage”.
If the instrument is transported from a cold into a warm environment, the
formation of condensation may result in instrument malfunction. Before
putting it back into operation, wait for the instrument temperature and the
room temperature to equalise.
4.2 Packaging and storage
Do not remove packaging until just before mounting.
Keep the packaging as it will provide optimum protection during transport
(e.g. change in installation site, sending for repair).
Permissible conditions at the place of storage:
■
Storage temperature: -40 ... +85 °C [-40 ... +185 °F]
■
Humidity: 5 ... 95 % r. h. (non-condensing)
Avoid exposure to the following factors:
■
Direct sunlight or proximity to hot objects
■
Mechanical vibration, mechanical shock (putting it down hard)
■
Soot, vapour, dust and corrosive gases
■
Hazardous environments, ammable atmospheres
4. Transport, packaging and storage

EN
WIKA operating instructions model TR36
14331645.02 07/2021 EN/DE/FR/ES
13
Store the instrument in its original packaging in a location that fulls the
conditions listed above. If the original packaging is not available, pack
and store the instrument as described below:
1. Wrap the instrument in an antistatic plastic lm.
2. Place the instrument, along with shock-absorbent material, in the
packaging.
3. If stored for a prolonged period of time (more than 30 days), place a
bag containing a desiccant inside the packaging.
Before storing the instrument (following operation), remove
any residual media.This is of particular importance if
the medium is hazardous to health, e.g. caustic, toxic,
carcinogenic, radioactive, etc.
5. Commissioning, operation
WARNING!
Avoid putting any mechanical loading on the electrical
connections and on the cases. Connections must only be
opened once the instrument has been depressurised and
has cooled down.
Maximum permissible temperatures:
■
At the case with transmitter: 85 °C [185 °F]
■
Class A:
Without neck tube -30 ... +150 °C [-22 ... +302 °F]
With neck tube -30 ... +250 °C [-22 ... +482 °F]
■
Class B:
Without neck tube -50 ... +150 °C [-58 ... +302 °F]
With neck tube -50 ... +250 °C [-58 ... +482 °F]
DANGER!
Danger to life caused by electric current
Upon contact with live parts, there is a direct danger to life.
▶The instrument may only be installed and mounted by
skilled personnel.
4. Transport ... / 5. Commissioning, operation

EN
14331645.02 07/2021 EN/DE/FR/ES
14 WIKA operating instructions model TR36
5.1 Installation
These resistance thermometers are designed for screw-tting directly
into the process. The insertion length, along with the ow rate and
viscosity of the process media, may reduce the max. loading on the
protection tube.
If the resistance thermometer is to be operated in an additional
protection tube, a spring-loaded compression tting must be used.
The case must be grounded against electromagnetic elds and
electrostatic charge. It is not necessary to connect the case separately to
the equipotential bonding system, provided that it has a xed and secure
contact to the metal vessel, its components or pipes, and that these are
connected to the equipotential bonding system.
When there is a non-metal contact with the vessel, or with its
structural components or piping, the instrument must be provided with
equipotential bonding.
WARNING!
Neither repairs nor structural modications are permitted,
and any would void the guarantee.
5. Commissioning, operation

EN
WIKA operating instructions model TR36
14331645.02 07/2021 EN/DE/FR/ES
15
Installation examples
For information on tapped holes, refer to DIN 3852 or for NPT threads to
ANSI B 1.20.
5.1.1 Tightening torques for compression ttings
Sealing Turns Max. pressure in bar
Stainless steel ferrule 1 ¼ ... 1 ½ 100
Stainless steel bite-type ferrule 1 ¼ ... 1 ½ 100
PTFE ferrule 1 ¼ ... 1 ½ 8
5.2 Electrical connection
Installation on pipes
a on elbows
b in smaller pipe, inclined
cperpendicular to ow direction
Insertion length A
Output signal 4 ... 20 mA
Angular connector DIN EN 175301-803
With direct sensor output
Angular connector DIN EN 175301-803
5. Commissioning, operation

EN
14331645.02 07/2021 EN/DE/FR/ES
16 WIKA operating instructions model TR36
Version with angular connector (DIN EN 175301-803):
For the cable leads we recommend the use of crimped end splices.
To ensure IP65 ingress protection:
■
Always use the silicon seals
■
Tighten the locking screw
■
Ensure the cables are inserted carefully
This is protection class 3 equipment for connection at low voltages,
which are separated from the mains voltage or voltages of greater than
AC 50 V or DC 120 V. Preferably, a connection to an SELV or PELV circuit
is recommended; alternatively protective measures from HD 60346-4-41
(DIN VDE 0100-410).
Alternatively for North America
The connection can be made in line with “Class 2 Circuits” or “Class 2
Power Units” in accordance with CEC (Canadian Electrical Code) or
NEC (National Electrical Code).
Load diagram
The permissible load depends on the loop supply voltage. For
communication with the instrument, with programming unit PU-548, a
max. load of 350 Ω is admissible.
0 10 24 30
833
583
Load RA in Ω
2363156.02
Voltage UBin V
5. Commissioning, operation

EN
WIKA operating instructions model TR36
14331645.02 07/2021 EN/DE/FR/ES
17
5. Commissioning, operation
5.3 Behaviour of the 4 ... 20 mA electrical output signal
■
Sensor break and short-circuit
Sensor break or short-circuit are signalled after positive detection
(after approx. 1 second). If this fault condition has been caused by a
malfunction, then a relevant measuring signal must exist for approx.
1 second in order to return to measuring mode. From the time of the
error detection up to the error signalling, the last relevant measured
value will be delivered on the current loop.
Therefore, in the event of a “true” sensor break or short-circuit, this
is also signalled permanently. In the event of a “false” sensor break
or short-circuit, the transmitter has the possibility of reverting to
measuring mode.
■
Medium temperature outside the span
If the medium temperature exceeds that congured within the
transmitter, the transmitter will operate in a linear fashion within the
following limits: 3.8 mA (MRS); 20.5 mA (MRE). If these limits are
exceeded, then an error will be signalled.
■
Hysteresis on return to the measuring span
After the linear error limits have been exceeded, on return to the
measuring span, a hysteresis of 0.1 mA must be passed.This
hysteresis prevents the transmitter from jumping back and forth
between error signalling and measuring mode.
Error
signalling
Error signalling Error signalling
3.8 ...
4 mA 20 ... 20.5 mA
4 ... 20 mA
3.8 mA 4 mA 20 mA 20.5 mA
3.9 mA 20.4 mA
Error
signalling
Measuring mode
Error limits and permissible measuring range

EN
14331645.02 07/2021 EN/DE/FR/ES
18 WIKA operating instructions model TR36
6. Conguration
Conguration is carried out using a USB interface with a PC via the
model PU-548 programming unit (accessories, order number: 14231581).
The connection with the thermometer is made via the appropriate adapter
cable (accessories: DIN connector, order number: 14005324).
Measuring range, dampening, error signalling, Tag no. and other
parameters can be adjusted (see conguration software).
The measuring range is congurable between -50 ... +250 °C
[-58 ... +482 °F]. The conguration software checks the required
measuring range and will only accept permissible values. Intermediate
values are congurable - the smallest increment is 0.1 °C or 0.1 °F. The
thermometers are delivered congured to customer specications within
the congurable limits.
Please note:
The measuring range of the thermometer is limited by the application
range of the measuring element, not by the setting range of the
transmitter.
Maximum permissible temperatures:
■
At the case with transmitter: 85 °C [185 °F]
■
Class A:
Without neck tube -30 ... +150 °C [-22 ... +302 °F]
With neck tube -30 ... +250 °C [-22 ... +482 °F]
■
Class B:
Without neck tube -50 ... +150 °C [-58 ... +302 °F]
With neck tube -50 ... +250 °C [-58 ... +482 °F]
■
Easy to use
■
LED status display
■
Compact design
■
No further voltage supply is needed for either
the programming unit or for the transmitter
(replaces programming unit model PU-448)
6. Conguration

EN
WIKA operating instructions model TR36
14331645.02 07/2021 EN/DE/FR/ES
19
7. Conguration software WIKAsoft-TT
For installation please follow the instructions of the installation routine.
7.1 Starting the software
Start the conguration software by double-clicking on the WIKAsoft-TT
icon.
After starting the software, the
language can be changed by
selecting the ag of the country in
question.
The selection of the COM port is
made automatically.
After the connection of a transmitter (using the PU-548), on pressing the
“Start” button, the conguration interface is loaded.
The conguration interface can only be loaded when an
instrument is connected.
7. Conguration software WIKAsoft-TT

EN
14331645.02 07/2021 EN/DE/FR/ES
20 WIKA operating instructions model TR36
7.2 Conguration procedure
Steps 1 and 2 are carried out automatically when starting the software.
1. “Loading instrument data”
2. “Loading conguration”
3. [optional] Cancel write protection (“key” symbol at the bottom right)
4. Change the required parameters
→ Sensor/Measuring range/Error signalling etc.
5. “Save to the instrument”
6. [optional] Activate write protection
7. [optional] Print conguration history
8. [optional] Test: “Loading conguration” → Check conguration
7.3 Fault diagnosis
Here, in the event of an “error detected by the transmitter”, the error
message is displayed.
Examples: Sensor break, permitted highest temperature exceeded, etc.
In normal operation, “No fault - No maintenance requirement” is
displayed here.
7.4 Measured values
Line recorder - Here the measured value progression is represented in
the format of a chart recorder with a constant sampling rate in a dened
time interval (180 seconds) and a variable temperature axis.
The display purely serves as a functional check and for information.
An export of the data is not possible.
7.5 Conguring several instruments identically
■
First instrument
1. “Loading conguration”
2. [optional] Cancel write protection (“key” symbol at the bottom
right)
3. Change the required parameters
4. “Save to the instrument”
5. [optional] Activate write protection
7. Conguration software WIKAsoft-TT
Table of contents
Languages: