General
Depending on the setup, the opening of
the lock can be subject to additional
restrictions. A combination of these
restrictions is also possible:
1. Delay time → Opening is only
possible once a defined delay
time has come to the end (with
the exception of user 9).
2. Dual code → Opening is only
possible with two valid user
codes. (also the "two pairs of
eyes" principle )
The dual code / the “two pairs of eyes”
principle cannot be disabled by the user
and is set at the factory [level 25].
Code length / silent alarm
Normally each user code has a length of
6 digits (0-9) [level 5]. If a silent alarm is
configured [level 15], the number of code
digits increases to 7 digits. The 7th code
digit is therefore shown in grey in the
following description. It is triggered by
changing the last code digit.
Battery
The lock is powered by a9V block battery
(alkaline-manganese).
A warning signal is emitted after code
input if the battery charge is too low. A
warning tone is repeated several times
with an alternately flashing red LED.
In such a case, change the battery as
soon as possible. The programmed
codes are retained while the battery is
changed.
Interfaces
For locks configured to level 5, only the
interface for analogue input units is
active. The second connection can only
be used for power supply via a signal box
or power supply unit.
Locks with level 15 have the silent alarm
function preconfigured. This means the
alarm contact is routed via the second
connection with a corresponding
hardware [signal box] and a lock disable
function is available via an input.
Dual code + delay time
When the dual code is activated, the lock
is opened according to the described
opening procedure after the delay time
has elapsed.
"User 9" can open alone during the delay
time if the dual-code condition (“two pairs
of eyes” principle) [level 25] is active. A
dual-code condition arises through the
fact that user 9 alone cannot start the
delay time.
An invalid code input during the release
time means that the operation is
terminated and the delay time must be
started again.
The input of a valid code during the
opening delay is acknowledged positively
but has no effect in itself. An opening
delay time that has been started can be
aborted by pressing any key.
Penalty time
After 4 invalid code entries there is a
penalty time of 5 min. Until a valid code is entered, a penalty time is then triggered
again after each two incorrect entries.