Wolf R1 User manual

3061809_1210 Subjecttomodications GB
Installation and
operating instructions
Control unit R1
Wolf GmbH · Postfach 1380 · D-84048 Mainburg · Tel. +49-8751/74-0 · Fax +49-8751/741600 · Internet: www.wolf-heiztechnik.de

3061809_12102
Index
Safetyinstructions ......................................................................3
Standards/Regulations .............................................................4
Installation/Electricalwork .................................................... 5-6
Commissioning...........................................................................7
Controlunit/Function/Operation....................................... 8-10
Displaying/Modifyingcontrolparameters................................11
Contractorlevelparameters ............................................... 12-28
SettingtheeBUSaddress ........................................................29
Parametersetupreport.............................................................30
Highlimitsafetycut-outchangeover ........................................31
Sensorresistances...................................................................32
WiringdiagramboilercontrolunitR1 .......................................33
Specication .............................................................................34
Faultmessages ........................................................................35

33061809_1210
Safety instructions
Burnersupplycable
Boilersensor
Highlimitsafetycut-out
Earthterminal
Thermometer
Thefollowingsymbolsareusedinconjunctionwiththeseimportant
instructions concerning personal safety as well as operational
reliability.
"Safetyinstructions"areinstructionswithwhichyoumustcomply
exactly,topreventinjuryandmateriallosses.
Dangerthrough'live'electricalcomponents.
NBSwitchOFFtheON/OFFswitchbeforeremovingthe
casing.
NevertouchelectricalcomponentsorcontactswhentheON/OFF
switchisintheONposition.Thisbringsariskofelectrocution,
whichmayresultininjuryordeath.
The main supply terminals are 'live' even when the ON / OFF
switchisintheOFFposition.
Thisindicatestechnicalinstructionswhichyoumustobserveto
preventmateriallossesandboilermalfunctions.
NB

3061809_12104
Standards / Regulations
Warnings - Neverremove,bypassordisablesafetyandmonitoringequipment.
- Only operate the system in perfect technical condition. Immediately
remove/remedyanyfaultsanddamagewhichmayimpactonsafety.
- Alwaysensurethatcoldwaterismixedinwithhotwater,whentheDHW
temperatureis set above60 °Corwhen operatingthe pasteurisation
system(65°C)(riskofscalding).
Maintenance / Repair -Regularlychecktheperfectfunctionofallelectricalequipment.
-Onlyqualiedpersonnelmayremovefaultsorrepairdamage.
-OnlyreplacefaultycomponentsorequipmentwithoriginalWolfspare
parts.
-
Alwaysmaintainprescribedelectricalprotectionvalues(seespecication).
AnydamageorlossresultingfromtechnicalmodicationstoWolfcontrol
unitsisexcludedfromourliability.
NB
The boiler control unit complies with the following regulations:
ECDirectives
- 2006/95/EC LowVoltageDirective
- 2004/108/EC EMCGuideline
DIN/ENStandards
EN60335-1,EN60730-2-9,EN14597,
DIN3440,EN50165,EN55014-1
Regarding the installation, observe the following regulations, rules
and directives.
- Theinstallationandcommissioningoftheheatingsystem
- LocalEMCregulations
- DIN VDE 0100 Regulations regarding the installation of high voltage
systemsupto1000V
- DINVDE105Operationofelectricalsystems
- EN50156Electricalequipmentincombustionsystems
- EN12828Heatingsystemsinbuildings
Appropriate use
TheWolfR1controlunitisdesignedexclusivelyforuseinconjunctionwith
Wolfboilers.TheR1controlunitisequippedwithatemperaturecontroller/
limiterandahighlimitsafetycut-out.Thecontrolunitregulatessinglestage
burners.Thesetboilertemperaturecanbeselectedbetween38-90°C.
The R1 control unit can be extended with a BM programming unit for
weather-compensatedtemperaturecontrolwithtimeprogram.
Other applicable documents
Boilerinstallationandoperatinginstructions.
Instructionsforallaccessoriesused.
Installation / Commissioning

53061809_1210
Installation / Electrical work
Jointhepowersupplycabletotheplugsupplied.Inserttheplug
into the marked-up location in the plug-in connector strip, and
securethecablewithitsstrainrelief.Routethecablethroughthe
boilerbackcutout.
Power supply connection
Electrical work
Mains230V
LP=Primarypump
A1=Programmableoutput
KKP=Boilercircuitpump
eBUS
E1=Programmableinput
SF=Cylindersensor
AF=Outsidetemp.sensor
Wheninstallingthiscontrolunitensurethatsensorcapillariesare
neitherkinkednortwisted.
Never route on-site sensor and remote control leads / cables
togetherwithmainspowercables.
Implement the electrical wiring in accordance with the wiring
diagram.
Opentherearcontrolunitcoverafterreleasingbothscrews.
Burner supply cable
Guideitthroughtheapertureinthecontrolunitbracket(l.h./r.h.),
subjecttothesidetowhichtheboilerdooropens.
Boiler sensor
Insertintoanyopeningoftheboilersensorwell.
High limit safety cut-out
Insert sensor capillaries into any opening in the boiler sensor
well.
Earth terminal
Insertintothecontrolunitpanel.
Thermometer for boiler water temperature display
Insertintoanyopeningoftheboilersensorwell.
Installation
Burnersupplycable
Boilersensor
Highlimitsafety
cut-out
Earthterminal
Thermometer
Insertallplugsthatarenotusedintotheplug-instrip.Observe
thecolourcoding.
Info

3061809_12106
Pump connection WolfboilercircuitandDHWcylinderprimarypumpsarefactory-
ttedwithplugs.Routethecablethroughtheboilerbackcutout.
Inserttheplugintothemarked-uplocationsintheplug-inconnector
strip,andsecurethecableswiththeirstrainrelief.
Installation / Electrical work
Outside temperature
sensor
(accessory)
Jointheon-siteleadoftheoutsidetemperaturesensorwiththe
plugsupplied.Inserttheplugintothemarked-uplocationinthe
plug-inconnectorstrip,andsecuretheleadwithitsstrainrelief.
Route the lead through the boiler back cutout. Fit the outside
temperature sensor to the north or northeast wall, 2 to 2.5m
abovegroundlevel.
DHW sensor
(accessory)
PushtheDHWcylindersensor(accessory)intothecylindersensor
well.Routetheleadthroughtheboilerbackcutout.Inserttheplug
into the marked-up location in the plug-in connector strip, and
securetheleadwithitsstrainrelief.
E1
programmable input
JointhecableofinputE1withtheplugsupplied.Inserttheplug
into the marked-up location in the plug-in connector strip, and
securethecablewithitsstrainrelief.Routethecablethroughthe
boilerbackcutout.
eBUS accessories Remotecontrol,radioclockmodule,radioclockmodulewithoutside
temperature sensor, receiver for wireless outside temperature
sensorandwirelessanalogremotecontrol.
Join the on-site accessory cable with the green plug supplied
(designatedeBUS).Inserttheplugintothemarked-uplocation
intheplug-inconnectorstrip,andsecurethecablewithitsstrain
relief.Routethecablethroughtheboilerbackcutout.
Note:
IfseveraleBUSaccessoriesaretobeconnectedsimultaneously,
connecttheseinparallelattheeBUSterminal.
A1
programmable output
JointhecableofoutputA1totheplugsupplied.Inserttheplug
into the marked-up location in the plug-in connector strip, and
securethecablewithitsstrainrelief.Routethecablethroughthe
boilerbackcutout.

73061809_1210
Commissioning
SwitchONthesystemON/OFFswitchatthecontrolunit.
ON/OFFswitch
Theheatingsystemstartstooperatewiththefactorysettingsas
soonastheON/OFFswitchatthecontrolunitisswitchedON.
Note:
Thefactorysettingsofthecontrolunitrepresentempiricalvalues.
Subjecttosystemorequipmentlevel,controlparametersother
thanthosechosenatthefactorycanbeselected.Makechanges
viatheWolfcontrol accessoriesorviaaPC/laptop with Wolf
controlsoftware.Allfactorysettingsarestoredinanon-volatile
memory.
Duringcommissioning,thecontrolunitautomaticallyrecognises
anyconnectedcylinderand/oroutsidetemperaturesensor.
Theoutsidetemperaturesensorisloggedoffbydisconnectionand
byswitchingthesupplyvoltageOFFandONagain.
The system will not be protected against frost if no outside
temperature sensor is connected; only the boiler is frost
protected.
You can log off the cylinder sensor by disconnecting and
resetting.
Theboilersensorcannotbeloggedoff.
NB

3061809_12108
Control unit / Function / Operation
Fine-wire fuse M 6.3 A High limit safety
cut-out (STB)
Operationonlyby
contractors
eBUS connection
for PC / Laptop
Thermometer
Reset button
Illuminated ring
ON / OFF switch
Heating water temp. selection
DHW temperature selection
Reset button
1. Resetsallparameterstotheirfactorysettings.
- TheoperatingmodeswitchmustbesettoO(OFF).
- Press and hold down the reset button whilst setting the
operatingmodeswitchtoI(ON).
- Keepholdingdowntheresetbuttonforatleast2seconds
afterthesystemhasstarted.
2. Forresettingtheoilcombustionunit(onlyinconjunctionwith
therelevantWolfcomponents)
- Incaseofaburnerfault,theoilcombustionunitisresetvia
aresetrelaybypressingtheresetkey.
Note: Reset gas red boilers in case of a burner fault
directlyatthegascombustionunit,i.e.throughan
openinginthesilencerhood.
ON / OFF switch
TheboilercontrolunitisOFFinposition0.Thereisnofrost
protection.
Illuminated signal ring as status indicator
Display Explanation
Flashinggreen Standby(powersupplyON,noheatdemand)
Constantgreenlight Heatdemand:pumprunning,burnerOFF
Flashingyellow Emissionstestmode
Constantyellowlight BurnerON,amesteady
Flashingred Fault

93061809_1210
Summer mode
Thewintermodeisdisabledandsummermodeisenabledbyrotating
theheatingwatertemperatureselectorintoposition .Summer
mode (heating OFF) means only DHW heating. Frost protection
fortheheatingsystemandpumpanti-seizingprotection,however,
remainenabled.
Control unit / Function / Operation
DHW temperature selection (rotary selector)
When boilers are combined with a DHW cylinder, setting 1-9
correspondstoacylindertemperatureof15-60°C.Theadjustment
madeatthe DHW temperature selectorisineffectivewhenthe
system is used in conjunction with a digital room temperature
controlleroraweather-compensatedcontroller.Thetemperature
willthenbeselectedatthecontroller(accessory).
Winter mode(position2to8)
Inwintermode,theboilerheatstothetemperatureselected at
theheatingwatertemperaturecontroller.Accordingtothepump
operatingmode,thecirculationpumpoperatesconstantly(factory
setting) or only in parallel with the burner activation / run-on
period.
Heating water temperature selection (rotary selector)
Thesettingrange2-8correspondstoaheatingwatertemperature
of38to75°C(factorysetting).
The adjustment at the heating water temperature controller is
ineffectivewhenthesystemisusedinconjunctionwithadigital
roomtemperaturecontrolleroraweather-compensatedcontroller
(exception:emissionstestmode).
Theheatingwatertemperatureiscalculatedfromthecontroller
setting.
Emissions test mode
Theemissionstestmodeisenabledbyrotatingtheheatingwater
temperatureselectorto .Anypreviousburnercycleblockwill
becancelled.Thesignalringashesyellow.Theheatingsystem
willnotoperateinweather-compensatedmode,whentheemission
testhasbeenenabled.Insteaditoperatesatmaximumoutputand
triestoholdameanconstantboilerwatertemperatureof60°C.
Onlytheburner will operate, i.e.thepumpis OFF,if theboiler
watertemperature islowerthan 60°C.Theboilercircuit pump
willbestartedwhentheboilerwatertemperatureexceeds60°C.
The DHW cylinder primary pump only runs until the set DHW
temperaturehasbeenreached.TheburnerisswitchedOFFwhen
themax.boilerwatertemperaturehasbeenreached,iftheheating
energysuppliedcannotbetransferred.
Theemissionstestmodeterminates either after 15 minutes or
automatically,ifthemaximumowtemperaturehasbeenexceeded.
Forarepeatactivation,turntheheatingwatertemperatureselector
rstanti-clockwiseandthenbackintoposition .

3061809_121010
Control unit / Function / Operation
Insummermode,thecirculationpumpoperatesforapprox.10
seconds after a maximum idle period of 24 hours. Then, the
cylinderprimarypumpandtheDHWcirculationpump(ifinstalled)
willrunfor20seconds.Thispreventsthepumpfromseizingup.
TheburnerwillbeswitchedOFFforapprox.twominutesifitis
operatingwhentheanti-seizingpumpprotectionisenabled.
Anti-seizing pump
protection
Thermometer
todisplaythecurrentheatingwatertemperature.
Fine-wire fuse
M6.3AtoprotectthecontrolPCB.
eBUS connection
fordatatransferbetweenthecontrolunitandthePC/laptop
withthesoftwaresetforboilercontrolunits(accessory).
High limit safety cut-out STB
factory-setto110°C;adjustableto100°C,ifrequired.

113061809_1210
Displaying / Modifying control parameters
The control parameters can only be modi ed or displayed via Wolf control accessories
with eBUS capability. For procedures, check the operating instructions of the relevant
accessories.
Modicationsmustonlythecarriedoutbyarecognisedheatingcontractor
orbytheWolfcustomerservice.
Incorrectoperationcanleadtosystemfaults.
Please note when adjusting parameterA09 (frost protection / outside
temperature), that frost protection is no longer safeguarded if you set
temperatureslowerthan 0°C.Thiscan resultindamage totheheating
systemandallitscomponents(e.g.pipes,radiators,etc.).
NB
NB
Parameter overview
(Settingsandfunctionsonthefollowingpages)
Parameter Setting range Factory setting
A09 Frostprotectionlevel -20to+10°C +2°C
A10 ParallelDHWoperation 0/1 0
A14 MaximumDHWtemperature 60to80°C 65°C
HG01 Burnerswitchingdifferential(dynamic) 5 to 30 K 15 K
HG06 Pumpoperatingmode 0/1/2 0
HG07 Boilercircuitpumprun-ontime 0to30min 3min
HG08 MaximumlimitboilercircuitTV-max 40to90°C 75°C
HG09 Burnercycleblock 1to30min 4min
HG13 ProgrammableinputE1 1 to 11 1
HG14 ProgrammableoutputA1 0 to 14 0
HG15 Cylinderhysteresis 1 to 30 K 5 K
HG19 Cylinderprimarypumprun-ontime 0to10min 3min
HG20 Max.cylinderheatingtime 0to5h 2h
HG21 MinimumboilerwatertemperatureTK-min.* 38to90°C 38°C
HG22 MaximumboilerwatertemperatureTK-max. 50to90°C 80°C
HG24 DHWsensoroperatingmode 1/2/3 1
HG25 BoilerexcesstemperatureduringDHWcylinder
heating
0 to 40 K 10 K
HG26 Boilersoftstart 0/1 1
HG32 Returntemperatureraising** 0to70°C 30°C
HG33 Hysteresistime 1to30min 10min
HG34 eBUSfeed 0/1/2 2
HG35 0-5Vinputfortelecontrolsystem 0/1 0
HG50 Testfunctions 1 to 5 -
HG70 Display
Multifunction
inputE1
-50sensorshortcircuitorcontactclosed
-60sensorleadbreakorcontactopen
ActualtemperatureheadersensorHG13=7
ActualtemperaturereturnsensorHG13=11
* setto50°Cforpressurejetgasburners
** setto40°Cforpressurejetgasburners

3061809_121012
Contractor level parameters
The boiler circuit pump operates constantly if the outside
temperaturestaysbelowtheselectedvalue.Theburnerstartsand
heatstheboilertoamin.of38°C,iftheboilerwatertemperature
fallsbelow+5°C.
Note:
Onlychangethefactorysettingifyoucanensurethattheheating
system and its components will not freeze up at low outside
temperatures.
Frost protection limit
Parameter A09
A09
2.0
Factorysetting:2°C
Settingrange:-20to+10°C
Individual setting: ______
Parallel DHW operation
Parameter A10
A10
0
Factorysetting:0
Settingrange:0/1
Individual setting: ______
The boiler circuit pump is switched OFF during DHW cylinder
heating with DHW priority (0). The boiler energy will then be
used exclusively for heating the DHW cylinder. The cylinder
primary pump will only start, if the boiler water temperature is
5 °C higher than the actual cylinder temperature. The burner
shutsdownandtheheatingcircuitpumpisstarted,assoonas
thecylinderhasreacheditssettemperature.Thecylinderprimary
pumprunsonforthemaximumperiodselectedunderparameter
HG19(cylinderprimarypumprun-ontime).
Theheatingcircuitpumpcontinuestooperateinparallel DHW
mode (1).Thecylinderprimarypumpstarts,iftheboilerwater
temperatureis5°Cwarmerthanthecylindertemperature.The
cylinder is fully heated up when the cylinder has reached the
selectedwatertemperature.Thecylinderprimarypumprunson
forthemaximumperiodselectedunderparameterHG19(cylinder
primarypumprun-ontime).
IntheparallelDHWmode(1),theheatingcircuitcantemporarily
beoperatedatahighertemperature.
NB
Maximum DHW
temperature
Parameter A14
A14
65.0°C
Factorysetting:65°C
Settingrange:60to80°C
Individual settings: _________
This temperature can be enabled at 80 °C, if for commercial
reasonsahigherDHWtemperatureisrequired.
Ifpasteurisationhasbeenactivated(BM),theDHWcylinderwill
beheatedtotheselectedmaximumDHWtemperatureduringthe
rstcylinderheatingoftheday.
Takeadequatemeasurestopreventscalding.ParameterHG22
(maximumboilerwatertemperature)shouldbesetatleast5K
higherthantheselectedmaximumDHWtemperature.
NB

133061809_1210
Contractor level parameters
Fig.:
Timesequenceofthedynamicburnerswitchingdifferentialfora
user-denedburnerswitchingdifferentialof15Kandaselected
hysteresistime(parameterHG33)of10minutes.
Burnerruntime(min.)
Switchingdifferential(K)
Selectedswitchingdifferential15K
Hysteresistime10minutes
Theburnerswitchingdifferentialregulatestheburnertemperature
withinasetrangebyswitchingtheburnerONandOFF.Thehigher
theON/OFFtemperaturedifferential,thehighertheboilerwater
temperatureuctuationaroundthesetvalue,resultinginlonger
burnerruntimesandviceversa.Longerburnerruntimesprotect
theenvironmentandextendtheservicelifeofwearingparts
Burner switching differential
(dynamic)
Parameter HG01
HG01
15
Factorysetting:15K
Settingrange:5to30K
Individual setting: ______

3061809_121014
Feed pump for heating systems with cascade control and /
or low loss header
Heatingcircuitpumpbecomesthefeedpump.
Theheadersensoraffectstheheatingoperationaswellascylinder
heating.Thefeedpumprunsonlywhenthereisaburnerdemand.
Pumprun-oninaccordancewithparameterHG07.
Softstarting:AtTKIst < TKmin(38°C)feedpump"OFF".
MKP and cylinder primary pump continue to run with soft
starting.
Note: Increase the pump run-on time from 3 min to 15 min.
SettheparameterHG13to7.
Pump operating mode 1:
Pump operating mode 0:
Heating circuit pump for heating systems without cascade
control and without low loss header
Theheatingcircuitpumprunsconstantlywhenthereisaheat
demand.TheheatingcircuitpumpwillbeswitchedOFFduring
DHWheating,ifDHWpriorityhasbeenselected.
Pump operating mode
Parameter HG06
HG06
0
Factorysetting:0
Settingrange:0/1
Individual setting: ______
ZUP = Feedpump
SPL = Cylinderprimarypump
PLP = Bufferprimarypump
SF = Cylindersensor
SAF = Headersensor
MK1 = Mixercircuit
MKP= Mixercircuitpump
Oil/gasboiler
SAF
ZUP
MKP
MK1
SPL
Cylinder
Lowloss
header
orbuffer
cylinder
SF
Hydraulicscheme:
Contractor level parameters

153061809_1210
Pump operating mode 2:
Buffer primary pump for BSP cylinder
Theheadersensor(buffer)onlyaffectstheheatingoperation.In
caseofcylinderheating,thereferencetemperatureisprovided
bytheinternalboilersensor.Inheatingmode,thebufferprimary
pumprunsonlywhenthereisaburnerdemand.Pumprun-onin
accordancewithparameterHG07.
Soft starting: At TKIst < TKmin (38 °C) buffer primary pump and
cylinder primary pump "OFF". MKP continues to run with soft
starting.
Note: Increasethepumprun-ontimefrom3minto15min.
SettheparameterHG13to7.
ZUP = Feedpump
SPLP= Cylinderprimarypump
PLP = Bufferprimarypump
SF = Cylindersensor
SAF = Headersensor
MK1 = Mixercircuit
MKP = Mixercircuitpump
MKP
MK1
Wood
boiler Buffercylinder Oil/gasboiler
SAF
SF
PLP
SPLP
Solarthermalsystem
integration
Hydraulicscheme:
Contractor level parameters

3061809_121016
Contractor level parameters
Each time the burner is shut down in heating mode, it will be
blockedforthedurationoftheburnercycleblock.
TheburnercycleblockisresetbyswitchingtheON/OFFswitch
OFFandONorbybrieypressingtheresetbutton.
Individual setting: ______
Burner cycle block
Parameter HG09
HG09
4
Factorysetting:4min
Settingrange:1to30min
Thisfunctionlimitstheboilerwatertemperatureupwardsinheating
mode,andtheburnershutsdown.Thisparameterhasnofunction
duringcylinderheating,andtheboilerwatertemperaturemayalso
behigherduringthistime."Re-heatingeffects"canresultinthe
temperaturebeingexceededalittle.
Individual setting: ______
Maximum limit
Boiler circuit TV-max.
Parameter HG08
HG08
75
Factorysetting:75°C
Settingrange:30to90°C
Subjecttotherebeingnoheatdemandfromtheheatingcircuits,
theboilercircuitpumpwillrun-oninaccordancewiththesettime,
topreventaboilersafetyshutdownathightemperatures.
Individual setting: ______
Run-on time
Boiler circuit pump
Parameter HG07
HG07
3
Factorysetting:3min
Settingrange:0to30min
Programmable input E1
Parameter HG13
HG13
1
Factorysetting:1
Settingrange:1to11
ThefunctionsofinputE1canonlybescannedandadjustedwith
WolfcontrolaccessorieswitheBUScapability.
ThefollowingfunctionscanbeallocatedtoinputE1:
No. Explanation
1Roomthermostat
WithopeninputE1,heatingoperationwillbeblocked
(summermode),independentofanydigitalWolf
controlaccessories.
Exception:Remotecontrolledheatingcircuits

173061809_1210
Contractor level parameters
No. Explanation
2Maximumthermostat
Toenabletheburner,inputE1mustbeclosed.The
burnerwillremainblockedforaslongasthecontactis
open,eveninemissionstestmode,cascademodeand
forDHWandcentralheatingfrostprotectionmode.
3N/A
4N/A
5Fluegasdamper/ventilationairdamper
Functionmonitoringoftheuegasdamper/
ventilationairdamperwithoatingcontact.Closed
contactConditionforburnerenableincentral
heating,DHW,cascadeandemissionstestmode.
Important: A1 (HG 14 = 7) must be programmed for
fl ue gas damper / ventilation air damper
function.
6DHWcirculationpushbutton(onsite)
Afteractivatingthisbutton,theDHWcirculationpump
isoperatedfor5minutes,independentof
thetimeprogramorthepositionoftheprogram
selector(BM).
Important: In any case, output A1 must be
programmed to setting 13.

3061809_121018
7Centralsensor(lowlossheaderorbuffer)
Inheatingmode,theboilerwatertemperature
controlisnolongergovernedbytheactualboiler
sensortemperature,butinsteadbythecentralsensor.
Theboilerwatertemperaturesensorcontinuesto
monitortheminimumandmaximumboilerwater
temperatures.
8Burnerblock
Contactclosed,burnerblocked.
Theheatingcircuitandcylinderprimarypumpsoperate
instandardmode,butwithoutsoftstart.
Theburnerisenabledinemissionstestandinfrost
protectionmode.
(Switchingoutput1ifHG14=12,divertervalvehas
beenprogrammed).
9N/A
10 Externalburnerdemand,inputE1closed
(e.g.airheater,swimmingpooldemand,
secondcylinderheatingviathermostat)
Thesetboilerwatertemperatureissettothemaximum
boilerwatertemperatureminus5K
limitedbythemaximumowtemperature.Heating
circuitandcylinderprimarypumpinstandardmode.
Important: In any case, output A1 must be
programmed to setting 14.
11 Returnsensor
OnlyinconjunctionwithparameterHG32(return
temperatureraising).
Important: In any case, output A1 must be
programmed to setting 12.
NB NeveruseinputE1fortheconnectionofsafetyequipment
(e.g.secondhighlimitsafetycut-out,lowwaterindicator,safety
pressurelimiter).Inthisconnection,seetheboilerinstallation
instructions.
Contractor level parameters

193061809_1210
Contractor level parameters
ThefunctionsofoutputA1canonlybescannedandadjustedwith
WolfcontrolaccessorieswitheBUScapability.
ThefollowingfunctionscanbeallocatedtooutputA1:
Programmable
output A1
Parameter HG14
HG14
0
Factorysetting:0
Settingrange:0to14
Individual setting: ______
No. Explanation
0N/A
NocontrolofoutputA1.
1DHWcirculationpump100%
TheoutputA1iscontrolledbycontrolaccessories(BM),if
DHWcirculationhasbeenenabled.OutputA1isconstantly
enabledwhennoaccessorycontrollerisinstalled.
2DHWcirculationpump50%
TheoutputA1iscontrolledbycontrolaccessories(BM)
incyclesof5minutesONand5minutesOFF,ifDHW
circulationhasbeenenabled.OutputA1isconstantly
cycledin5minutecycleswhennoaccessorycontrolleris
installed.
3DHWcirculationpump20%
TheoutputA1iscontrolledbycontrolaccessories(BM)
incyclesof2minutesONand8minutesOFF,ifDHW
circulationhasbeenenabled.OutputA1cyclesconstantly
whennoaccessorycontrollerisinstalled.
4Alarmoutput
OutputA1iscontrolledafterafaultandexpiryof4minutes.
5Flamedetector
OutputA1iscontrolledafteraamehasbeenrecognised.
6N/A
7Fluegasdamper/ventilationairdamper
OutputA1isclosedbeforetheburnerstarts.Feedback
ischeckedviainputE1(HG13=5).IfinputE1does
notclose,theburnerwillnotstart,andaftertwo
minutesFC8willbegenerated.
Important: Input E1 must be programmed as fl ue gas/
ventilation air damper.
8Externalventing
OutputA1iscontrolledinvertedtotheburner.
SwitchingOFFexternalventilation(e.g.extractorfan)
duringburneroperationisonlyrequired,iftheboileris
operatedasopenuesystem.
9Supplyvalve
OutputA1iscontrolledafteraamehasbeenrecognised.
10 N/A
11 Feedpump
OutputA1iscontrolledateveryheatdemand(heating
circuitorcylinderheating).

3061809_121020
Contractor level parameters
The cylinder hysteresis regulates the start and stop points for
cylinderheating.ThehighertheON/OFFtemperaturedifferential,
the higher the cylinder temperature uctuation around the set
cylindertemperature.
Example: Setcylindertemperature60°C
Cylinderhysteresis5K
Cylinderheatingcommencesat55°Candendsat60°C.
Cylinder hysteresis
Parameter HG15
HG15
5
Factorysetting:5K
Settingrange:1to30K
Individual setting: ______
No. Explanation
12 Bypasspumpforreturntemperatureraising
OutputA1iscontrolledifthereturntemperatureislower
thantheselectedreturntemperatureraisingvalue
(parameterHG32).
Important: Input E1 must, in any case, be
programmed to setting 11 or if an external
burner block input E1
(HG13 = 8) has been programmed.
13 DHWcirculationpump
OutputA1iscontrolledfor5minutesafterapushbuttonhas
beenactivated(pulseinputE1).
Important: In any case, input E1 must be
programmed to setting 6.
14 OutputA1ON
OutputA1iscontrolledifinputE1isclosed
(externalburnerdemand).
Important: In any case, input E1 must be
programmed to setting 10.