4 PROFIBUS-DP Option Components
8 YASKAWA ELECTRIC SIEP C730600 23A V1000 Option PROFIBUS-DP Technical Manual
Table 3 Communication connector (9-pin D-SUB)
◆PROFIBUS-DP Option LED Display
Table 4 LED Display
Table 5 Understanding LED Display
{: On / : Flashing / ×: Off
◆Setting Node Address
Set drive parameter F6-30 to a node address (Range 0 to 125) unique to the network.
PROFIBUS Connector Pin Signal Description
1 Shield Connected to the metal-shell (no direct FG-connection)
2– –
3 RxD/TxD-P Receive/Transmit data; line B (red)
4 CNTR-P Control signal for repeaters (direction control)
5 DGND Data ground (reference voltage to VP)
6 VP Power supply output for bus termination (+5V, greater than or equal to 10 mA)
7– –
8 RxD/TxD-N Receive/Transmit data; line A (green)
9– –
LED Display Communication Status Meaning
Color Status
RUN
(Power) Green
ON Power is on Power is being properly supplied to SI-P3/V, and SI-P3/V has completed its hardware self-
diagnostics check
OFF Power is off • The drive has no power supply
• SI-P3/V and drive are not connected properly and/or there is no power supplied to the SI-P3/V
ERR
(Option Error) Red
ON SI-P3/V error Self-diagnostics error occurred in the SI-P3/V
Flashing Drive connection error Connection error between SI-P3/V and drive. This includes node address setting errors to parameter
F6-30 on the drive side
OFF No error is present No error or the power supply is off. Assuming the power is supplied, this LED will remain off
provided that there are no problems with the communication settings for the PROFIBUS-DP Option
COMM
(Communication Status) Green ON Communication connected Normal send/receive between SI-P3/V and PROFIBUS-DP master
OFF No data exchange There is a problem establishing communication between SI-P3/V and the PROFIBUS-DP master
BF
(PROFIBUS-DP Error) Red
ON Waiting for communication
procedure setting PROFIBUS-DP master is initializing parameters or is online
Flashing Communication setting error Communication parameter error from PROFIBUS-DP master
OFF No error is present
No error or the power supply is off. Assuming the power is supplied, this LED will remain off
provided that there are no problems with the communication settings from the PROFIBUS-DP
master
LED Communication Status Possible Cause Solution
RUN ERR COMM BF
×× ××No power.
The drive has no power. Check all wiring to the drive, then turn the power on.
SI-P3/V is not properly connected to the
drive, and therefore is not receiving enough
power.
Shut the drive off and see if the PROFIBUS-DP Option is
connected properly. Turn the power back on again.
{×××
• Checking connection with the
drive
• Waiting for data from the
master.
• SI-P3/V is reading the node address or
parameter configuration
• Waiting for initial input data from master
device.
–
×{××SI-P3/V Self-diagnostics error The PROFIBUS-DP Option is damaged. Cycle power to the drive. If the LED status does not change,
replace the PROFIBUS-DP Option.
×××Problem connecting to the drive.
• Problem initializing the drive and SI-P3/
V
• Incorrect node address.
• Cycle power to the drive. If the LED status does not change,
replace the PROFIBUS-DP Option
• Check the node address setting in the drive (parameter F6-10).
{××{Waiting for data from the master
device.
Waiting for data from the master device
(Set_Parm_Message or
Chk_Cfg_Message).
• Check the network settings in the master
• Make sure the master device is operating normally
• Check the terminal resistance settings on the data line
• Look for any problems with the data line, or if the connector
• See if the data line connected properly to the drive's main
circuit.
{××
Data is incorrect or PROFIBUS-
DP Option timed out waiting for
data.
The communication procedure in the
master is set incorrectly. Check the communication procedure settings in the master.
{×{×Sending or receiving data. – –
1
5
6
9
Bottom View
7
8
2
3
4