4 Option Components
YASKAWA ELECTRIC SIEP C730600 89C YASKAWA AC Drive Option SI-EP3 Technical Manual 11
The operational states of the option LEDs after the power-up diagnostic LED sequence is completed are described in
Table 4. The states with a number in parenthesis are the number of pulses of 250 ms on, 250 ms off cycles, followed by
500 ms off, then repeating the cycle. Wait at least 2 seconds for the power-up diagnostic process to complete before
verifying LED states.
Table 4 Option LED States
Power-Up Diagnostics
An LED test is performed each time the drive is powered up. The initial boot sequence may take several seconds. After
the LEDs have completed the diagnostic LED sequence, the option is successfully initialized. The LEDs then assume
operational conditions as shown in Table 4.
Table 5 Power-Up Diagnostic LED Sequence
Name Indication Operating Status Description
Color Status
MS
(visible through
drive cover)
– OFF Power supply OFF Power is not being supplied to the drive.
Green ON Option operating The option is operating normally and
initialization is complete.
Green Flashing (1) Diagnostics Diagnostic data available.
Green Flashing (2) Configuration tool Identified by a configuration tool.
Red ON Default MAC or fatal error occurred. Default MAC address has been programmed or
the option has detected an unrecoverable error.
Red Flashing (1) Invalid Station Name programmed
Invalid Station name programmed into device.
It must be rewritten with a valid name from PLC
software or webpage.
Red Flashing (2) No IP (non-fatal) No IP address assigned.
Red Flashing (3) No station name (non-fatal) No station name assigned.
Red Flashing (4) Init failure (non-fatal) Failed to initialize module.
Green/Red Flashing Option self-test The option is in self-test mode.
NS
(visible through
drive cover)
– OFF Offline or Power supply OFF –
Green ON Connected Connection established with I/O controller and
in RUN mode.
Green Flashing Connected and stopped Connection established with I/O controller and
in STOP mode.
Red ON BUS fault Unrecoverable BUS fault.
Red Flashing (1) Lost communication Host communication is temporarily lost.
Red Flashing (2) Lost link No link detected to network.
Red Flashing (3) IP address settings bad
Use the operator or Drive Wizard to check and
change F7 parameters, then cycle power. You
can also set the PLC to assign the IP address,
which will auto-clear the fault.
10/100
(visible at
RJ45 jack)
Yellow OFF 10 Mbps is established –
Yellow ON 100 Mbps is established –
LINK/ACT
(visible at
RJ45 jack)
Green OFF Link is not established –
Green ON Link is established –
Green Flashing Link is established and there is network
activity –
Sequence Module Status (MS) Network Status (NS) Time (ms)
1GreenOFF250
2RedOFF250
3GreenOFF –
4 Green Green 250
5GreenRed250
6GreenOFF –