3 Electrical Installation
YASKAWA Europe TOEP_C710606_97A - AC Drive A1000 IP54READY - Quick Start Guide EN 17
NOTICE: The terminals HC, H1, H2 are used for the Safe Disable function. Do not remove the wire link between HC, H1, or H2 unless
the Safe Disable function is used. Refer to Safe Disable Input Function on page 34 when using this function.
NOTICE: The wiring length to the terminals HC, H1 and H2 should not exceed 30 m.
Analog Inputs /
Pulse Train
Input
RP Multi-function pulse train input (Frequency
reference)
Input frequency range: 0 to 32 kHz
Signal Duty Cycle: 30 to 70%
High level: 3.5 to 13.2 Vdc, low level: 0.0 to 0.8 Vdc
Input impedance: 3 kΩ
+V Power supply for analog inputs 10.5 Vdc (max allowable current 20 mA)
-V Power supply for analog inputs -10.5 Vdc (max allowable current 20 mA)
A1 Multi-function analog input 1 (Frequency
reference bias) -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
A2 Multi-function analog input 2 (Frequency
reference bias)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
Voltage or current input must be selected by DIP switch S1 and H3-09
A3 Multi-function analog input 3 / PTC Input
(Auxiliary frequency reference)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
Use switch S4 on the control terminal board to select between analog
input or PTC input. If PTC is selected, set H3-06 = E.
AC Frequency reference common 0 V
E (G) Ground for shielded lines and option cards –
Fault Relay
MA N.O.
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
MB N.C. output
MC Fault output common
Multi-Function
Digital Output
M1 Multi-function digital output (During run) 30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
M2
M3 Multi-function digital output (Zero speed) 30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
M4
M5 Multi-function digital output (Speed agree 1) 30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
M6
Monitor Output
MP Pulse train output (Output frequency) 32 kHz (max)
FM Analog monitor output 1 (Output frequency) -10 to +10 Vdc, 0 to +10 Vdc, or 4 to 20 mA
Use jumper S5 on the control terminal board to select between voltage
or current output at terminals AM and FM. Set parameters H4-07 and
H4-08 accordingly when changing the jumper setting.
AM Analog monitor output 2 (Output current)
AC Monitor common 0 V
Safety Monitor
Output
DM+ Safety monitor output Outputs status of Safe Disable function. Closed when both Safe
Disable channels are closed. Up to +48 Vdc 50 mA
DM- Safety monitor output common
Type No. Terminal Name (Function) Function (Signal Level) Default Setting