manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ABB
  6. •
  7. Measuring Instrument
  8. •
  9. ABB LevelMaster 7100 User manual

ABB LevelMaster 7100 User manual

Other manuals for LevelMaster 7100

2

Other ABB Measuring Instrument manuals

ABB ProcessMaster FEM630 User manual

ABB

ABB ProcessMaster FEM630 User manual

ABB Navigator 600 Silica User manual

ABB

ABB Navigator 600 Silica User manual

ABB MicroGuard solution User manual

ABB

ABB MicroGuard solution User manual

ABB D1M 20 User manual

ABB

ABB D1M 20 User manual

ABB MAG-X 3000 Series User manual

ABB

ABB MAG-X 3000 Series User manual

ABB M4M 30 User manual

ABB

ABB M4M 30 User manual

ABB ReliaGear ASPMETER A 42 Installation and operation manual

ABB

ABB ReliaGear ASPMETER A 42 Installation and operation manual

ABB FSM4000-SE41F User manual

ABB

ABB FSM4000-SE41F User manual

ABB PositionMaster EDP300 User manual

ABB

ABB PositionMaster EDP300 User manual

ABB SM500F User manual

ABB

ABB SM500F User manual

ABB Aztec 600 User manual

ABB

ABB Aztec 600 User manual

ABB ICOS GLA431-MCIA User manual

ABB

ABB ICOS GLA431-MCIA User manual

ABB NGC8200 User manual

ABB

ABB NGC8200 User manual

ABB TRIO-WIRL ST4000 User manual

ABB

ABB TRIO-WIRL ST4000 User manual

ABB AquaMaster Explorer User manual

ABB

ABB AquaMaster Explorer User manual

ABB MagMaster Instruction sheet

ABB

ABB MagMaster Instruction sheet

ABB AX418 User manual

ABB

ABB AX418 User manual

ABB 2112U-101-500 User manual

ABB

ABB 2112U-101-500 User manual

ABB Aztec 600 User manual

ABB

ABB Aztec 600 User manual

ABB DELTAsingle User manual

ABB

ABB DELTAsingle User manual

ABB VSN730 User manual

ABB

ABB VSN730 User manual

ABB CoriolisMaster FCH400 Series User manual

ABB

ABB CoriolisMaster FCH400 Series User manual

ABB Comem OLI User manual

ABB

ABB Comem OLI User manual

ABB EL3000 Series User manual

ABB

ABB EL3000 Series User manual

Popular Measuring Instrument manuals by other brands

Powerfix Profi 278296 Operation and safety notes

Powerfix Profi

Powerfix Profi 278296 Operation and safety notes

Test Equipment Depot GVT-427B user manual

Test Equipment Depot

Test Equipment Depot GVT-427B user manual

Fieldpiece ACH Operator's manual

Fieldpiece

Fieldpiece ACH Operator's manual

FLYSURFER VIRON3 user manual

FLYSURFER

FLYSURFER VIRON3 user manual

GMW TG uni 1 operating manual

GMW

GMW TG uni 1 operating manual

Downeaster Wind & Weather Medallion Series instruction manual

Downeaster

Downeaster Wind & Weather Medallion Series instruction manual

Hanna Instruments HI96725C instruction manual

Hanna Instruments

Hanna Instruments HI96725C instruction manual

Nokeval KMR260 quick guide

Nokeval

Nokeval KMR260 quick guide

HOKUYO AUTOMATIC UBG-05LN instruction manual

HOKUYO AUTOMATIC

HOKUYO AUTOMATIC UBG-05LN instruction manual

Fluke 96000 Series Operator's manual

Fluke

Fluke 96000 Series Operator's manual

Test Products International SP565 user manual

Test Products International

Test Products International SP565 user manual

General Sleep Zmachine Insight+ DT-200 Service manual

General Sleep

General Sleep Zmachine Insight+ DT-200 Service manual

Sensa Core Lacto Spark user manual

Sensa Core

Sensa Core Lacto Spark user manual

VOLTCRAFT UTS-1980 operating instructions

VOLTCRAFT

VOLTCRAFT UTS-1980 operating instructions

EBCHQ 94915 Operation manual

EBCHQ

EBCHQ 94915 Operation manual

Balluff BIP LD2-T017-01-EP-S4 Series user guide

Balluff

Balluff BIP LD2-T017-01-EP-S4 Series user guide

Pulsar IMP Lite Series instruction manual

Pulsar

Pulsar IMP Lite Series instruction manual

ETCR 6800 user manual

ETCR

ETCR 6800 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

  2105836-001 (AB)| LEVELMASTER 7100 | 8/2019

Figure 1: Slide components into the LevelMaster casing
Legend: # Name
1 Oil float
2 Water float
3 Top of LevelMaster
Figure 2: Local connection cable for 2018546-001 boards

Legend: # Name
1 Connect to computer with serial or USB (using
additional adapter)
2 RS-232/RS-485 converter, P/N 2100241-005
3 Cable Adapter, P/N 2100250-002
4 Connect to Level Master board, P/N 2104836-001
5 See the Notice below

NOTICE – Equipment damage. Disconnect the red wire
connector on the battery assembly when power to the
LevelMaster is turned off. Failure to do so will result in a
constant battery drain.


RS-485termination(2018546-005boardsonly)
Figure 3: Intermediate
sensor
Figure 4: Last or only
sensor

Figure 5: Wiring (2018546-001 boards)

Legend: # Name
1 To flow computer/remote controller or through barrier
2 First sensor
3 Last sensor

Figure 6: Wiring (Mixed board types)
Single port legacy board (2018546-005) on left. Separate port new
board (2104836-001) on right.

Contact us
ABB Inc., Measurement & Analytics
Quotes: totalflow.in[email protected]m
Orders: [email protected]m
Training: totalf[email protected].com
Support: upstream.su[email protected]b.com
+1 800 442 3097 (opt. 2) www.abb.com/upstream
2105836MNAA
Copyright© 2019 ABB all rights reserved

ABB MEASUREMENT & ANALYTICS
LevelMaster 7100
Quick Start with batteryless floats


Safety and compliance information is included with the device
in the shipping packaging.
We reserve the right to make technical changes or modify the
contents of this document without prior notice. Regarding
purchase orders, the agreed upon shall prevail. ABB does not
accept any responsibility whatsoever for potential errors or
possible lack of information in this document.
Additional information
Scan the code below for product publications:
LevelMaster 7100

2105836-001 (AB)| LEVELMASTER 7100 | 8/2019
Figure 7: Totalflow CSA-certified barrier board (hazardous
locations)
LevelMaster 7100 Quick Start
This guide includes basic steps for a new general-purpose
installation and setup in an unclassified area. For hazardous
location installations refer to online publications.
IMPORTANT NOTE: Installations may involve single or multiple
interconnected units and mixed board types. For multi-unit
installations, determine intermediate and last units in the
connecting bus to terminate the RS-485 bus correctly.
Setup requirements
Table 1: Requirements per board type below.
Board number 2104836-001 2018546-005
RS-485 termination Through software Through onboard
termination pins
Float types
All types including
batteryless floats
(kit 2018392-017)
All types except
batteryless floats
MasterLink
version
2.0 (required for
batteryless floats) 2.0 or earlier
For setup (not for permanent connection)
RS-485 cable adapter 2100250-002 2100250-001
RS-485-to-RS-232
bl
2100241-005 2100241-002
RS-232-to-USB
converter
Digi
®
Edgeport/1 USB Converter
for laptops without RS-232 ports. Software drivers
are required (1801382-001).
DANGER – Bodily injury: Configure the LevelMaster before
inserting into the tank. Follow your company policies and safety
guidelines to complete installation.
Install LevelMaster components
With the sensor positioned and supported horizontally:
Wrap Teflon
®
tape, or another sealing material, around cord
connector and tank port bushing threads.
Slide the components into the bottom of the LevelMaster in the
following order: Cord connector, tank port bushing, floats. If using
two floats, slide the oil float on first (see Figure 1.)
Slide and tighten the float clamp at 1 inch above the bottom of
the casing.
Assemble local communication cable
Connect the converter cable and adapters based on board type
and ports available on the laptop (see Figure 2.)
Connect the RS-485 cable adapter to the RS-485-to-RS-232
converter cable.
If using a laptop without RS-232 ports, connect the RS-485-to-
RS-232 converter cable to the RS-232-to-USB converter.
Connect to the LevelMaster
IMPORTANT NOTE: Ensure MasterLink 2.0 is already installed in
the PC or laptop. MasterLink has context-sensitive online help.
Click Help on the screen of interest for details.
To configure the LevelMaster, connect to the electronic board:
Remove cover from the electronic enclosure and pull the
electronic board up gently without disconnecting it from the
sensor assembly.
With a small slotted screw driver, remove the connectors from the
onboard communication and power terminals. Save these
connectors for wiring.
Use the local communication cable to connect the
laptop to the electronic board.
Insert the red wire connector to the cable assembly battery.
Start MasterLink on the laptop.
At the main screen, add a location for the new unit:
a. Right-click inside the screen (white area) and select Add
New Location.
b. Enter up to 25 characters for a location name.
c. Click OK to save the name. Verify that the location displays.
d. Select the new location (ensure it is highlighted).
Click the Comm. Port drop-down list.
Select the laptop communication port used.
Leave the Baud Rate at 9600 (factory default).
Verify communication
Click Setup LevelMaster. The New LevelMaster Setup window
displays.
Select I have only one LevelMaster connected to
communication port and I want to set it up.
Click Setup LevelMaster.
When prompted to add the LevelMaster to the list, click Yes.
When prompted for the LevelMaster name, type a unique name of
up to 15 characters and click OK.
Observe the messages displayed on the monitor screen. Verify
that communication is successful (100% success).
Set up unit with generic configuration
MasterLink 2.0 includes generic configuration files for different
sensor lengths. To load one of these files to the LevelMaster:
Click the Upload/Download tab.
Under Send data to the LevelMaster, click Browse […].
In the browser, navigate to the applicable default files folder. For
example, C:\Program Files (x86)\ABB\MasterLink\DefaultDat\7.0
Head board.
Locate the file for the correct length of sensor and click Open. For
example, for a 20 ft sensor, select the "Dual_20ft_batteryless.dat"
file.
Click Download Data to LevelMaster.
Click OK when the download is complete.
Click the Setup tab.
Type a unique ID in the New LevelMaster ID field and click Set
New ID.
Configure the baud rate for communications. Baud rates for all
connecting units, including the controller, must match.
Configure termination if the LevelMaster is the only unit installed
or is the last unit on an RS-485 bus. Leave intermediate units with
factory default configuration.
Configure RS-485 bus termination
Perform this procedure only for boards with part number
2104836-001. For legacy boards, set termination jumpers
onboard (see Figure 3.)
Click the Monitor tab and select the Add Advanced Setup tabs.
Additional tabs display.
Click the More items tab.
Select Show memory map.
Scroll down, locate, and double-click the 844-memory address
or "RS-485 bus termination". The default value is 0.
When the edit box displays, change the value to 1.
Click Send New Value.
Install the LevelMaster into the tank
Remove the local connection cable from the board. Position the
board inside the enclosure.
Reinstall and secure the enclosure cover.
Slide components to the bottom.
Lift and insert the LevelMaster into the tank.
Wire the LevelMaster electronic board
Refer to Figure 4 or Figure 5 for wiring.
Remove enclosure cover to expose the board again for wiring
Wire units and controller for communication and power.
Insert wired connectors on units, reinstall, and secure cover.