3.2 Binary inputs on bay units GUID-D6989DA8-87EC-4663-9F09-7327E736720E v3
Table 5: BU general input signals
Signal Description
11105_External TRIP The tripping command received from another protection device(including
one in the remote station) which is used for the REB500 tripping contact to
trip faults, on a line or a power transformer.
11110_External TRIP BB zone Used when an external signal has to trip the entire bus zone to which the
feeder is connected (for example, an external BFP signal). Applied to all the
bay units of the bus zone and sections of busbars interconnected by
disconnector ( intertripping).
11115_Ext_Test_TRIP Activates the signal 21120_EXT_TEST_TRIP to operate several tripping
relays simultaneously.
11120_BP External TRIP Tripping signal generated by the feeder protection part. Trips faults on a line
or power transformer with the aid of the REB500 tripping contact. Tripping
thus takes account of the busbar configuration at the time.
To function correctly, the signal has to be assigned to a feeder.
The simplest arrangement corresponds to the assignment of the signal
11105_Ext. TRIP to feeders. If signal 11105_Ext. TRIP is not available, a
binary output has to be configured for 11120_BP External TRIP which is
then assigned to a feeder. The signal is activated by the feeder protection
directly and does not therefore appear as binary input signal.
11125_BP External TRIP BB zone This is a tripping signal generated by the feeder protection part which is
used to trip the entire bus zone to which the feeder is connected. The
tripping command is applied to all the bay units of the bus zone and
sections of busbars interconnected by disconnector ( intertripping).
11205_Block SP A signal applied to this input blocks the local station protection functions
(BFP, EFP, OCDT and PDF), External Trip, tripping by the busbar protection
and intertripping of the respective bay unit. The Bus Bar Protection
continues to be active as a system function. The primary injection of the
concerned bay unit can lead to a trip of the respective zone.
11210_Block output relays All the output contacts configured for a bay unit are blocked.
11215_Ext. measuring disturbed This signal is active when invalid analogue values are received from an
external device. The busbar protection (that is, the specific protection zone
of the busbar) and all the local protection functions are blocked. If the
disturbance lasts longer than 400 ms, diagnostic events are generated
(BBP Minor Error 9 and BBP Minor Error 20). This input should only be
used in special cases and only when engineering a REB500 system.
11505_Close command CB The circuit breaker close command is needed by the busbar and end fault
protection in bus-tie breaker and configured feeder bay units to control the
REB500 measuring system.
11510...11525_Supervision aux.
voltage_x
The supervision of the auxiliary supply is configured when the compliance
of the auxiliary contacts on the disconnectors with the required switching
sequence and cannot be guaranteed for this reason, the Not OPEN =
CLOSED logic has to be used. These signals ensure that the protection
responds correctly should the auxiliary supply to the disconnectors fail.
This signal is only applicable in the case of Not OPEN = CLOSED.
The supervision signals affect all switchgear objects or associated with this
BU independent of the respective supervision voltage levels.
11530_Isolator/Breaker Position The position of a circuit breaker or disconnector is signaled by one or two
auxiliary contacts.
Table continues on next page
1MRK 505 400-UUS Rev. B Section 3
Signals
Distributed busbar protection REB500 9
Technical manual