Advanced ExGo Series User manual

Extinguishing Control Panel
User Instructions
The operation and functions described in this manual are available from Software Version Mx5000-050-02 onwards.The operation and functions described in this manual are available from Software Version Ex-3000-V2.05C onwards.
www.acornfiresecurity.com
www.acornfiresecurity.com

Table of Contents Page
1INTRODUCTION 3
1.1 STANDARDS 3
1.2 CAUTIONS AND WARNINGS 3
1.3 DESCRIPTION 3
2OPERATION 4
2.1 INTRODUCTION 4
2.1.1 Access Levels 4
2.1.2 Front Panel Controls and Indications 4
2.1.2.1 Display 4
2.1.2.2 LED Indications 5
2.1.2.3 Manual Release Button 6
2.1.2.4 Control Buttons 6
2.1.2.5 Menu and Navigation Buttons 7
2.1.2.6 Key-Switches 7
2.1.2.7 Buzzer 7
2.1.3 Enable Controls 8
2.1.4 Navigating through menus 8
2.1.5 Numeric data entry 8
2.2 OPERATING CONDITIONS 9
2.2.1 Fire Alarm Condition 9
2.2.2 Release / Activated Condition 9
2.2.3 Hold Condition 11
2.2.4 Abort Condition 11
2.2.5 Fault Condition 11
2.2.6 Warning Condition 12
2.3 LEVEL 1MENU FUNCTIONS 12
2.3.1 Enable Controls 12
2.3.2 View 12
2.3.3 LED Test 12
2.4 LEVEL 2MENU FUNCTIONS 13
2.4.1 View 13
2.4.1.1 Faults 13
2.4.1.2 Disables 13
2.4.1.3 Warnings 14
2.4.1.4 Log 14
2.4.1.5 Software Versions 15
2.4.1.6 Panel Levels 15
2.4.2 Test 15
2.4.2.1 Zones 16
2.4.2.2 Display 16
2.4.2.3 Buzzer 16
2.4.2.4 Manual Triggers 17
2.4.3 Extinguishant Modes 17
2.4.3.1 Mode 17
2.4.3.2 Extract 17
2.4.4 Disable / Enable 18
2.4.5 Date/Time 18
www.acornfiresecurity.com
www.acornfiresecurity.com

3
1 Introduction
1.1 Standards
The ExGo Gas Extinguishing Control Panel conforms to the following standards:
BS EN12094-1: 2003 Extinguishing Control Device
BS EN54-2: 1998 Control and Indicating Equipment
BS EN54-4: 1998 Power Supply Equipment
BS EN60950: 2000 Safety of information technology equipment
BS EN50130-4: 1996 Product Family Standard
Electromagnetic Compatibility Directive 89/336/EEC (and the amending directive 92/23/EEC)
Low Voltage Directive 73/23/EEC
1.2 Cautions and Warnings
Only Trained service personnel should undertake the Installation,
Programming and Maintenance of this equipment.
1.3 Description
This manual covers the use and how to operate the ExGo Extinguishing Control Panels. Refer to the Installation
Manual (Document No. 680-147) for details of installation, programming and commissioning of the panel.
The ExGo is a Single Flooding Zone Control Panel with up to three detection zone circuits.
The detection zones are compatible with conventional detectors and call points.
www.acornfiresecurity.com
www.acornfiresecurity.com

4
2 Operation
2.1 Introduction
These instructions cover the operation and use of the panels.
2.1.1 Access Levels
The panel operation is protected from inadvertent and erroneous misuse by means of four access levels. These
levels are as follows:
Level 1 Untrained user
Level 2 Authorised User
Level 3 Commissioning, Service and Maintenance
Level 4 Commissioning, Service and Maintenance –Special Tools Required
This document covers the Level 1 and Level 2 User functions. For details on the installation, programming and
commissioning of the panel, refer to Manual 680-147. Full details are supplied with any special tools.
A Level 1 Untrained User can view the current operational condition of the system and may MUTE the
internal buzzer.
A Level 2 Authorised User can view the operational condition of the system and may MUTE the internal
buzzer. In addition, the RESOUND/SOUND ALARMS, SILENCE and RESET buttons are enabled and
access to the Level 2 Menu functions is available. This requires a password (or key-switch).
NOTES: There are up to 4 User ID codes available, each with its own password. The panel can be
configured to automatically cancel access to Level 2 functions after a specified period.
2.1.2 Front Panel Controls and Indications
Key-Switch Assembly
U
S
B
S
U
P
P
L
Y
P
S
U
C
o
m
m
s
P
R
O
G
R
U
N
u
P
M
O
D
E
R
E
B
O
O
T
R
e
l
a
y
-
1
F
I
R
E
R
e
l
a
y
R
e
l
a
y
-
2
F
A
U
L
T
R
e
l
a
y
R
S
4
8
5
A
U
X
S
u
p
p
l
y
Z
O
N
E
-
1
-
Z
O
N
E
-
2
-
Z
O
N
E
-
3
-
S
N
D
R
-
1
-
S
N
D
R
-
2
-
S
N
D
R
-
3
-
M
O
D
E
S
e
l
e
c
t
M
a
n
u
a
l
T
r
i
g
g
e
r
H
O
L
D
A
B
O
R
T
P
r
e
s
s
u
r
e
M
o
n
i
t
o
r
V
A
L
V
E
M
o
n
i
t
o
r
F
L
O
W
M
o
n
i
t
o
r
A
c
t
u
a
t
o
r
O
u
t
p
u
t
P
R
O
G
I
n
p
u
t
-
1
P
R
O
G
I
n
p
u
t
-
2
P
R
O
G
I
n
p
u
t
-
3
P
R
O
G
I
n
p
u
t
-
4
M
A
N
U
A
L
O
N
L
Y
A
U
T
O
+
M
A
N
U
A
L
V
A
LV
E
C
L
O
S
E
D
M
A
N
U
A
L
D
I
S
A
B
L
E
D
D
I
S
A
B
L
E
D
F
A
U
L
T
T
I
M
E
R
H
E
L
D
A
B
O
R
T
E
D
R
E
L
E
A
S
E
I
M
M
I
N
E
N
T
R
E
L
E
A
S
E
D
E
X
T
I
N
G
U
I
S
H
A
N
T
P
O
W
E
R
S
Y
S
T
E
M
F
A
U
L
T
T
E
S
T
S
O
U
N
D
E
R
D
E
L
A
Y
E
D
D
I
S
A
B
L
E
S
O
U
N
D
E
R
D
I
S
A
B
L
E
D
F
A
U
L
T
S
O
U
N
D
E
R
F
A
U
L
T
F
I
R
E
S
I
L
E
N
C
E
D
G
E
N
E
R
A
L
-
1
-
D
E
T
E
C
T
I
O
N
Z
O
N
E
S
F
I
R
E
F
A
U
L
T
/
T
E
S
T
/
D
I
S
A
B
L
E
-
2
-
-
3
-
E
S
C
M
E
N
U
W
X
Y
Z
T
U
V
P
Q
R
S
G
H
I
J
K
L
M
N
O
D
E
F
A
B
C
R
E
S
E
T
S
I
L
E
N
C
E
M
U
T
E
!
RESOUND /
SOUND
ALARMS
B
S
E
N
5
4
-
2
:
1
9
9
8
B
S
E
N
5
4
-
4
:
1
9
9
8
B
S
E
N
1
2
0
9
4
-
1
:
2
0
0
3
C
L
A
S
S
-
A
E
X
T
I
N
G
U
I
S
H
A
N
T
R
E
L
E
A
S
E
P
U
L
L
D
O
W
N
A
N
D
P
R
E
S
S
B
U
T
T
O
N
Extinguishant Status
Number Buttons
Control Buttons
General Status
LCD
Navigation Buttons
Detection Zone Status
Manual Release Button
2.1.2.1 Display
The LCD along with the LED Indicators shows the operating status of the system. Examples of the information
presented is shown below:
www.acornfiresecurity.com
www.acornfiresecurity.com

5
Normal Display
Non-normal Display
Typical Menu Display
SYSTEM NORMAL
22 AUG 2007 16:39:00
[System status]
1 of 1 conditions:
DETECTION ZONE3
OPEN CIRCUIT
[Level 2 Menu]
VIEW .
TEST
MODES
DISABLE / ENABLE
EXIT LEVEL 2
[Release status]
UNAFFECTED
Release Imminent
Release Activated
Release Complete
[Release status]
RELEASE IMMINENT..
-15
RELEASE ACTIVATED
00:00:05 Elapsed
RELEASE ACTIVATED
00:00:24 Elapsed
GAS RESET INHIBITED
DISCHARGE COMPLETE
(No Flow Detected)
RESET ALLOWED
The display shows a countdown
timer with the amount of time
remaining before the extinguishant
is released.
The display shows the time
elapsed since the extinguishant
release commenced.
2.1.2.2 LED Indications
The LED Status Indications show the basic operational state of the panel and whether the panel is in a fire
alarm, fault, disabled or test condition.
2.1.2.2.1 GENERAL STATUS
Function
Colour
Description
FIRE
Red
Indicates that the system has detected a fire alarm condition
FAULT
Yellow
Indicates that the system has detected a fault condition
DISABLE
Yellow
Indicates that part of the system has been disabled (i.e. isolated)
TEST
Yellow
Indicates that part of the system is in a test condition
POWER
Green
Indicates the presence of power
SILENCED
Yellow
Indicates that the geneal fire alarm sounders have been silenced
SOUNDER FAULT
Yellow
Indicates the presence of a fault in either or both of the general fire alarm sounder wiring
circuits
SOUNDER DISABLED
Yellow
Indicates that either or both of the general fire alarm sounder circuits have been disabled
(i.e. isolated)
DELAYED
Yellow
Not used
SYSTEM FAULT
Yellow
Indicates the presence of a system fault
2.1.2.2.2 DETECTION ZONE STATUS
Function
Colour
Description
FIRE
Red
Indicates that the system has detected a fire alarm condition in the respecitve zone
FAULT/TEST/DISABLE
Yellow
Indicates that the system has (flashing indication) detected a fault condition in the respecitve
zone or (steady indication) that the zone is either in a test state or in a disabled state
www.acornfiresecurity.com
www.acornfiresecurity.com

6
2.1.2.2.3 EXTINGUISHANT
Function
Colour
Description
RELEASE IMMINENT
Red
Indicates (flashing) that the release of extinguishant is imminent. The indication will turn to
steady when the signal to release the extinguishant has been activated.
RELEASED
Red
Indicates that the release of extinguishant has occurred and the panel has detected the flow
of the extinguishant released.
TIMER HELD
Yellow
Indicates that the imminent release of extinguishant is temproraily suspended.
ABORTED
Yellow
Indicates that the imminent release of the extinguishant has been aborted.
DISABLED
Yellow
Indicates that the extinguishant release control signal has been disabled. The release of
extinguishant is prevented even if a fire alarm or manual release are present.
FAULT
Yellow
Indicates that the system has detected a fault condition within part of the extinguishing
control device (ECD) circuits. The General Fault LED will also be illuminated.
MANUAL DISABLED
Yellow
Indicates that one or more buttons for manual release have been disabled.
VALVE CLOSED
Yellow
Indicates that the extinguishant is blocked by a manual shut-off valve and that there may be
no extinguishant available to suppress a fire –Ensure immediate remedial action is taken to
address the problem.
MANUAL ONLY
Yellow
Indicates that the extinguishant can only be released by means of a manual release button.
AUTO + MANUAL
Yellow
Indicates that the extinguishant can be released by both the automatic detection of a fire
alarm and by means of a manual release button.
2.1.2.3 Manual Release Button
To manually release the extinguishant, pull down the flap and press the button marked with the circle.
2.1.2.4 Control Buttons
Reset
Press to reset the panel from a fire alarm condition and/ or a
gas release sequence.
Only available with
Level 2 Access.
!
Mute
Press to mute the internal buzzer.
Available in both
Level 1 and Level 2
Silence 1
Press to silence the sounders.
Only available with
Level 2 Access.
Resound / Sound Alarms
Press again to re-activate the sounders.
Press to initiate a manual evacuation and sound the alarms.
Only available with
Level 2 Access.
1
SILENCE will silence all sounders except for the flooding zone (protected area) sounders when the system is in the activated state. Once
the extinguishant has been released, it is possible to silence the flooding zone sounders.
www.acornfiresecurity.com
www.acornfiresecurity.com

7
2.1.2.5 Menu and Navigation Buttons
Press to scroll through Menu Options.
Press to display more information.
Press to scroll through menu Options.
Press to scroll through lists of zones or devices.
Press to confirm entry of numeric information entry.
Press to confirm selection of a menu option.
Press to change some of the configuration options.
E
S
C
M
E
N
U
W
X
Y
Z
T
U
V
P
Q
R
S
G
H
I
J
K
L
M
N
O
D
E
F
A
B
C
W
X
Y
Z
Used to enter numbers.
E
S
C
Press to exit the menu functions and return to the
normal display.
M
E
N
U
Press to show or return to Menu Functions.
2.1.2.6 Key-Switches
One or two key-switches can be fitted to the panel.
The functions of these are programmable and the installer
will have inserted a label to indicate their use.
Typical uses are:
AUTO + MANUAL / MANUAL ONLY Selection
LEVEL 1 / LEVEL 2 ACCESS Selection
Depending on the key-switch mechanism fitted, the key
may be removable in only one position or removable in
both operating positions.
2.1.2.7 Buzzer
The buzzer produces two different sounds to differentiate between fire alarm conditions and fault / warning
conditions.
Condition
Operation
Fire Alarm
The buzzer operates with a continuous tone.
Fault
The buzzer operates intermittently.
www.acornfiresecurity.com
www.acornfiresecurity.com

8
2.1.3 Enable Controls
Controls are normally disabled. If a level 2 Access key-switch is fitted use this in preference to passwords.
To enable the control keys or gain access to the Level 2, press the Menu button. The display shows the
following:
[CONTROLS DISABLED]
ENABLE CONTROLS
VIEW
LED TEST
Enter Your Password
Enter Your Password
**
Press the ✔button to select the
‘Enable Controls’ option.
The display prompts for entry of
the password.
Enter the password. As each
number is pressed, an *
character is displayed. Finally,
press the ✔button to confirm.
[Level 2 Menu]
VIEW .
TEST
EXTINGUISH MODES
DISABLE / ENABLE
EXIT LEVEL 2
Enter Your Password
Not Recognized!
The display then shows the Level 2
Menu options.
If the password is incorrect (or if
not entered in time) the above
message is shown.
If a control button is pressed at Level 1, the display prompts for password entry. To continue, enter the
password. If the password is valid, the relevant control function will be activated and the display will remain at
Level 1.
2.1.4 Navigating through menus
When a menu is displayed, use the buttons to highlight the required menu option and then press the ✔
button to select it.
Press the ESC button from within a menu option to return to the previous menu.
The display will revert to the status mode display after 60 seconds on no activity (15 seconds in a fire alarm
condition). Press the Menu button again to return to the menu option.
A programmable timer can be configured to automatically cancel Level 2 access. This time can be between 1
and 5 minutes. If no buttons are pressed for the timeout period, then Level 2 access will be cancelled. It will be
necessary to re-enter the password to regain access to control and Level 2 Menu functions.
2.1.5 Numeric data entry
Numbers are entered by moving to the required field, and then typing in the required number, followed by the ✔
button. The display returns to the previous menu.
If the number is entered incorrectly, press the button to clear the entry and then re-enter the required
number. Alternatively, press the ESC button to cancel the number entry and return to the previous menu.
www.acornfiresecurity.com
www.acornfiresecurity.com

9
2.2 Operating Conditions
2.2.1 Fire Alarm Condition
[Fire Detected]
FIRE STARTED: ZONE 1
TOTAL FIRES: 1
The display shows location / origin of the fire alarm and the total
number of zones in a fire alarm condition.
If two or more zones enter the fire alarm condition, the display also
shows the location of the last zone to enter a fire alarm condition.
In addition, the General Fire LED and the respective Zone Fire
LED will be illuminated.
[Release Status]
STAGE-1
[Fire Detected]
FIRE STARTED: ZONE 1
LAST FIRE : ZONE 3
TOTAL FIRES : 2
The status of the extinguishant release is also indicated. If a fire
alarm occurs in a zone that has no effect on the extinguishant
control then the display shows UNAFFECTED.
[Release Status]
STAGE-1
The fire alarm bells / sounders will activate (depending on how they are programmed to respond).
To silence the internal buzzer, press the MUTE button.
To silence the bells, press the SILENCE button (the SILENCED LED will illuminate)
2
.
To reset the panel, press the RESET button. If a ‘Reset Control’ menu is presented, use the buttons to
highlight the ‘RESET FIRE & GAS’ option, then press the ✔button to select.
[RESET Control]
RESET FIRE & GAS
RESET GAS ONLY
CANCEL RESET
The Reset Control menu may be presented when the reset control
key is pressed (this is dependent on how the control panel has
been configured by the installer).
Use the buttons to highlight the required option, then use the
✔button to select the highlighted option.
NOTE: If the programming of the panel is such that the release condition is immediately invoked on detection of
a single fire alarm, then the display will immediately show the release status information.
2.2.2 Release / Activated Condition
The activated condition is established when one or more fire alarms have occurred or when the manual release
button is pressed.
The number of zones, and which zones, that must be in a fire alarm condition before the activated condition is
invoked depends on the installation programming of the panel.
[Release status]
RELEASE IMMINENT..
-15
When the activated condition is established, the display indicates
that the release is imminent and also shows a countdown timer
with the number of seconds remaining before the extinguishant is
released.
In addition, the Release Imminent LED flashes.
If programmed, the bells / sounders will ring with pulsed alert tone.
2
SILENCE will silence all sounders except for the flooding zone (protected area) sounders when the system is in the activated state. Once
the extinguishant has been released, it is possible to silence the flooding zone sounders by pressing the silence button again.
www.acornfiresecurity.com
www.acornfiresecurity.com

10
RELEASE ACTIVATED
00:00:05 Elapsed
When the countdown timer has elapsed, the actuating output is
activated to start the release of the extinguishant.
The display now shows the time elapsed since the release of
extinguishant commenced.
In addition, the Release Imminent LED turns ON steady.
GAS RESET INHIBITED
RELEASE ACTIVATED
10 Seconds Elapsed
When the discharge is complete (either time elapsed or flow
detected) the display indicates the discharge is complete.
It is now possible to silence the flooding zone sounders.
DISCHARGE COMPLETE
(No Flow Detected)
GAS RESET INHIBITED
RELEASE ACTIVATED
10 Seconds Elapsed
If confirmed by the detection of the flow of the extinguishant, the
display shows RELEASE CONFIRMED (Released Condition) and
the RELEASED LED turns ON steady.
If previously silenced, the internal buzzer will re-sound. Press the
MUTE button to silence the buzzer.
RELEASE CONFIRMED
DISCHARGE COMPLETE
GAS RESET INHIBITED
RELEASE ACTIVATED
20 Seconds Elapsed
When the extinguishant has been fully released (and if
programmed), the panel will either automatically, or will prompt for
manual confirmation, activate the output to control the extract fan.
This is indicated on the display as EXTRACT RUNNING or
PRESS ✔to EXTRACT).
When the discharge is complete, the display prompts that the
panel can be reset.
DISCHARGE COMPLETE
EXTRACT RUNNING
RESET ALLOWED
To reset the panel, press the RESET button. A Reset Control menu may appear –use the buttons to
highlight the appropriate option, then press the ✔button to select.
Section 4.12.2
Reset of the Activated Condition / Release Signal.
NOTE: In accordance with EN 12094-1, the ECD shall not permit a reset until
either the RELEASED condition has been established (flow detected) or until
after a programmable time following activation of the mechanism to release the
extinguishant.
NOTE: Depending on programming, the EXTRACT condition may persist after the panel is reset for up to 120
minutes. This will be indicated on the normal status display (Extract Running).
Section 4.11
Released Condition.
NOTE: In accordance with EN 12094-1, the activated / release condition may be
established without the detection of a fire alarm or manual release. If the panel
detects the release of extinguishant, it will immediately indicate the released
condition.
www.acornfiresecurity.com
www.acornfiresecurity.com

11
2.2.3 Hold Condition
COUNTDOWN ON HOLD
(Remove HOLD resume)
-15
If any hold button is activated, the imminent release countdown is
held for as long as the button is pressed.
The display shows the HOLD condition and the TIMER HELD LED
is illuminated.
When the hold button is released, the panel will resume the imminent release countdown either from the time
remaining or from the maximum time programmed.
2.2.4 Abort Condition
RELEASE ABORTED!
PRESS RESET TO REARM
If an abort button is activated, the imminent release countdown is
aborted.
The display prompts for the panel to be reset and the ABORTED
LED is illuminated.
Ensure that the abort button is de-activated and then press the
RESET button. A Reset Control menu may appear –use the
buttons to highlight the appropriate option, then press the ✔button
to select.
2.2.5 Fault Condition
[System status]
1 of 1 conditions:
DETECTION ZONE3
OPEN CIRCUIT
If the panel detects a fault condition, the display will indicate the
number and nature of the faults. The internal buzzer will sound with
an intermittent tone and the GENERAL FAULT LED and any other
specific FAULT LED indications will be illuminated.
Press the buttons to scroll through the list of faults.
Press the MUTE button to silence the internal buzzer.
[Release status]
UNAFFECTED
NOTE: The fault condition is non-latching (except System Fault) and the indications will automatically be cleared
when the fault is remedied. Press the RESET key to clear a System Fault - a Reset Control menu may appear –
use the buttons to highlight the ‘RESET GAS & FIRE’ option, then press the ✔button to select.
NOTE: If silenced, the buzzer will re-sound when a new fault occurs.
[System status]
1 of 1 conditions:
DETECTION ZONE3
OPEN CIRCUIT
When the MUTE button is pressed, the bottom two lines of the
display will show the telephone number to call for service (if
programmed) for four seconds.
For service call:
01234 567 890
www.acornfiresecurity.com
www.acornfiresecurity.com

12
2.2.6 Warning Condition
[System status]
1 of 1 conditions:
PRESSURE MONITOR
OPEN CIRCUIT
If the panel detects an extinguishant warning condition, the display
will indicate the number and nature of the warnings. The internal
buzzer will sound with an intermittent tone and the GENERAL
FAULT LED and any other specific FAULT LED indications will be
illuminated.
Press the buttons to scroll through the list of faults.
Press the MUTE button to silence the internal buzzer.
[Release status]
UNAFFECTED
2.3 Level 1 Menu Functions
2.3.1 Enable Controls
Controls and User Level-2 Menu functions are normally disabled. Refer to Section 2.1.3 for further details.
2.3.2 View
On selection, the current status of any Faults, Disablements and Warnings along with the history Log can be
shown. These are the same as the Level-2 View function. Refer to Section 2.4.1 for further details.
2.3.3 LED Test
On selection, the front panel LED Indicators will be illuminated for a short period of time.
www.acornfiresecurity.com
www.acornfiresecurity.com

13
2.4 Level 2 Menu Functions
The following table gives a list of the Level 2 Menu Functions and a brief description for each function.
Menu Option
Sub Menu /
Item
Comments / Description
VIEW
FAULTS
View any current fault conditions recorded.
DISABLES
View any current disablement conditions.
WARNINGS
View any current extinguishant warnings conditions.
LOG
View the history log.
SW VERSIONS
View the software version installed in the extinguishant control panel
and in remote status indicator panels.
PANEL
View real-time power supply related information.
TEST
ZONES
Test the Detection Zone inputs with/without sounders.
DISPLAY
Test the Display, LED Indicators and Buttons.
BUZZER
Test the Buzzer
EXTINGUISH MODES
MANUAL
Select Manual Only mode / Auto + Manual mode
EXTRACT
Turn on the extract output (if configured)
DISABLE / ENABLE
--
Disable Zone, Sounder, Input and Output circuits and disable
functions. Enable any current disablement conditions
EXIT LEVEL 2
--
Cancels access to Level 2 menu functions and control key functions.
DATE / TIME
--
Allows entry of the current date and time.
COMMISSION
--
Engineer use only –requires separate password.
2.4.1 View
[View Menu]
FAULTS .
DISABLES
WARNINGS
LOG
SW VERSIONS
Press the buttons to scroll through the list and press the ✔
button to select the required view option.
[Fault Status]
Nothing to Report
If there are no conditions present, the display will show “Nothing to
Report”.
2.4.1.1 Faults
[Fault Status]
1 of 3
DETECTION ZONE 1 .
>SHORT CIRCUIT .
DETECTION ZONE 2
>OPEN CIRCUIT
If there are fault conditions present, the display will show the
number of conditions and a list of the fault conditions.
Press the buttons to scroll through the list of faults.
Press the ESC button to return to the previous menu.
2.4.1.2 Disables
[Disable List]
Zone 1 DISABLED
Man Release DISABLED
If there are disablement conditions present, the display will show
the number of conditions and a list of the disablements.
Press the buttons to scroll through the list of disablements.
Press the ESC button to return to the previous menu.
www.acornfiresecurity.com
www.acornfiresecurity.com

14
2.4.1.3 Warnings
[Warning Status]
1 of 2
VALVE MONITOR INPUT.
>VALVE CLOSED .
PRESSURE MONITOR
>LOW PRESSURE
If there are warning conditions in the extinguishant system present,
the display will show the number of conditions and a list of the
warning conditions.
Press the buttons to scroll through the list of warnings.
Press the ESC button to return to the previous menu.
2.4.1.4 Log
The panel contains a history log of fires, faults and other conditions. This can be filtered to show only the fire
alarm and trigger events that could result in the release of the extinguishant. In addition, a total fire alarm count
is also available.
[Event Log Menu]
ALL EVENTS .
FIRES & TRIGGERS
ALARM COUNT
On selection, a menu is presented to select the required view.
Press the buttons to scroll through the list and press the ✔
button to select the required view option.
Press the ESC button to return to the previous menu.
2.4.1.4.1 View Events
Select either the ALL EVENTS or the FIRES + TRIGGERS option. On selection, the latest recorded entry is
shown. For example:
[Event Log Viewer]
EVENT: 55/55
The upper two lines show the menu option and the number of the
entry currently being viewed.
Press the buttons to scroll through the list of entries.
Press the ESC button to return to the previous menu.
The next four lines show the details of the log entry.
20/09/2007 10:21:15
CONTROL PANEL
DETECTION ZONE 3
>OPEN CIRCUIT
[Event Log Viewer]
EVENT: 41/58
Line 1 –shows the date and time the entry was recorded
Line 2 –shows the origin
Line 3 –shows the circuit / function affected
Line 4 –shows specific details
20/09/2007 09:22:18
USER4
DETECTION ZONE 3
>DISABLE
[Event Log Viewer]
EVENT: 11/58
Line 1 –shows the date and time the entry was recorded
Line 2 –shows the origin
Line 3 –shows the circuit / function affected
Line 4 –shows specific details
19/09/2007 12:25:11
CONTROL PANEL
DETECTION ZONE 3
>FIRE ALARM
www.acornfiresecurity.com
www.acornfiresecurity.com

15
In the above examples:
[1] The control panel recognised and recorded an open-circuit fault condition on the wiring of Detection Zone 3.
[2] User 4 disabled the operation of, and fault reporting from, Detection Zone 3.
[3] The control panel recognised and recorded a fire alarm condition on Detection Zone 3.
2.4.1.4.2 Alarm Counter
Section 7.13
Alarm Counter.
The Panel records the number of times that the fire alarm condition has
occurred at the panel.
ALARM COUNT
0000000004
On selection, the display shows the alarm count.
In the example the panel has entered the fire alarm condition 4
times since it was installed.
Press the ESC button to return to the previous menu.
The panel increments the count by one each time it changes from the normal condition to indicate a fire alarm
condition. Whilst in the fire alarm condition, and until it is reset, further fire alarm events do not increment the
counter.
2.4.1.5 Software Versions
[Software Versions]
PANEL : 99.00
RSI-1 : 99.00
RSI-2 : 99.00
RSI-3 : 99.00
RSI-4 : 99.00
On selection, the display shows a list containing the panel and any
configured remote status indicators along with the version of
software installed in each device.
Press the buttons to scroll through the list of entries.
Press the ESC button to return to the previous menu.
2.4.1.6 Panel Levels
[Panel Levels]
SYSTEM VOLTS 27.08V
BATTERY (V) 27.42V
CHARGER (V) 27.55V
Temperature 21deg
On selection, the display shows a list containing key information
about power supply related levels.
Press the buttons to highlight the list of entries.
Press the ESC button to return to the previous menu.
System Volts relates to the supply voltage present on the main card all other values are measured at the power
supply module. Where the communication link to the power supply module is broken the values are replaced by
a ‘-‘ character.
2.4.2 Test
[Test Menu]
ZONES .
DISPLAY
BUZZER
MANUAL TRIGGERS
Press the buttons to scroll through the list and press the ✔
button to select the required test option.
www.acornfiresecurity.com
www.acornfiresecurity.com

16
2.4.2.1 Zones
The Test Zones function provides the means to implement a one-person walk test in order to test specific call
points or detectors in one or more zones.
To test the detection zone circuits in accordance with the recommended weekly, monthly and annual test
requirements, select the Test –Zones option. The devices connected to the circuit can then be tested without
activating the extinguishing system and release.
Use the test key supplied for testing manual call points and either a heat source or smoke test aerosol for
testing heat detectors / smoke detectors.
[Zone Test Select]
WITHOUT SOUNDERS .
WITH SOUNDERS
On selection, the display prompts for whether the sounders / bells
should ring for a short period (about 10 seconds) when the
detection zone enters a test fire alarm condition.
Press the buttons to scroll through the list and press the ✔
button to select the required test option.
The display then shows a list of the detection zone circuits.
[Zone Test Select]
ZONE 1 TEST OFF.
ZONE 2 TEST OFF
ZONE 3 TEST OFF
Press the buttons to scroll through the list and highlight the
required zone circuit.
Press the ✔button to select between TEST OFF and TEST ON.
To leave the Zone Test menu, press the ESC button. If there are still any zones in a test condition, the display
will show the following options: -
[Zones in Test!]
CANCEL ALL TESTS .
CONTINUE TESTS
Selecting the CANCEL ALL TESTS option will cancel all zone
tests. The Test LED will then extinguish.
Alternatively, it is possible to leave the Zone Test Function with
one or more Zones still in Test by selecting the CONTINUE
TESTS option. This will enable the inspection or use of other menu
functions and return the display to the normal operating mode.
The Test LED will stay illuminated if this option is selected.
2.4.2.2 Display
The Test Display option checks the operation of all the Indicators and the Graphic Display. All of the Indicators
are turned on and the entire display is shown in reverse.
LCD & KEY TEST
1
During this test, it is possible to test the operation of the
,,,,✔and 0-9 buttons. When a button is pressed, it is
indicated on the display. For example:
Press the ESC button to cancel the test and return to the previous
menu.
2.4.2.3 Buzzer
On selection, the buzzer will sound for approximately 10 seconds.
www.acornfiresecurity.com
www.acornfiresecurity.com

17
2.4.2.4 Manual Triggers
3
On selection, the display shows:
Manual Trigger Test
MANUAL TRIGGER
OFF
Activate any manual trigger device (on the ExGo 3001 Control
Panel, on the ExGo 3030/3031 Remote Status Indicator or other
external manual trigger. The buzzer will sound and the display will
change from OFF to ACTIVE to show the operation of the manual
trigger.
Restore any manual trigger to normal (if required).
! When the display indicates OFF, press the ESC button to cancel
the test and return to the previous menu.
2.4.3 Extinguishant Modes
[Mode Select]
MODE MANUAL ONLY.
EXTRACT START?
Press the buttons to scroll through the list and highlight the
required option.
2.4.3.1 Mode
The methods for initiating the release of extinguishant can be selected.
Press the ✔button to select between MANUAL ONLY and AUTO + MANUAL.
In AUTO + MANUAL, the release of extinguishant can be established if
either a manual release button is pressed or if the one or more of the
detection zone circuits is activated due to detection of smoke.
In MANUAL ONLY, the release of extinguishant can only be established if
one of the manual release buttons is pressed.
NOTE: If a key-switch is provided on the front panel, or separately, for this function, then use the key-switch in
preference to the menu option.
2.4.3.2 Extract
If the panel is configured and programmed to provide control of an extract fan then the operation of the extract
fan can be manually controlled via the menu option.
The display is context sensitive and will present different options depending on whether the fan is on (running)
or off.
If the fan is off, the display shows EXTRACT START? –Press the ✔button to start the extract fan for the pre-
programmed time.
If the fan is on, the display shows EXTRACT STOP? –Press the ✔button to stop (turn off) the extract fan.
NOTE: If a key-switch is provided on the front panel, or separately, for this function, then use the key-switch in
preference to the menu option.
3
Available from Software version 2.06
SYSTEM NORMAL
22 AUG 2007 16:39:00
SYSTEM NORMAL
(Manual Only Mode)
22 AUG 2007 16:39:00
www.acornfiresecurity.com
www.acornfiresecurity.com

18
2.4.4 Disable / Enable
[Disabled List]
ZONE1 ENABLED.
ZONE2 ENABLED
ZONE3 ENABLED
Man Release ENABLED
Extinguish ENABLED
Press the buttons to scroll through the list and highlight the
required option.
Press the ✔button to select between ENABLED and DISABLED
conditions. If a circuit or function is disabled, then the General
Disabled LED is illuminated along with any specific circuit /
function disablement LED indicators.
The table below lists all of the items that can be disabled.
Item
Description
Comments
ZONE 1
ZONE 2
ZONE 3
Detection Zones, Zone 1, 2 and 3
Disables any fault reporting on these circuits.
The zone will not enter the fire alarm condition even
if there is smoke present.
Man Release
Manual Release of the extinguishant.
Prevents the release of extinguishant due to the
activation of any manual release button.
Extinguish
The Output to activate the release of
the extinguishant and Sounder
Circuit 3 (Flooding zone sounders).
Disables any fault reporting on the extinguishing
output circuit and flooding zone sounder circuit.
Prevents the operation of the extinguishing output
and flooding zone sounder circuit even if the release
condition is established.
Sounder 1
General Fire Alarm Sounder Output
(circuit 1).
Disables any fault reporting on the sounder-1
circuit.
General fire alarm sounder circuit 1 will remain off
irrespective of the operating condition of the panel.
Sounder 2
General Fire Alarm Sounder Output
(circuit 2).
Disables any fault reporting on the sounder-2
circuit.
General fire alarm sounder circuit 2 will remain off
irrespective of the operating condition of the panel.
Fault Relay
The Fault Relay Output
Prevents the fault relay output from operating.
Fire Relay
The Fire Relay Output
Prevents the fire relay output from operating.
Prog Relays
All other relay control outputs
Prevents all other relay output circuits from
operating.
2.4.5 Date/Time
[Set TIME/DATE]
TIME = 13:25
DATE = 29/09/07
Press the buttons to scroll through the list and highlight the
required option.
Enter the required time or date using the number buttons. Enter all
digits including zeros (i.e. 09 then 09 for 9:09 AM).
After all digits are entered, the time or date is set (if it is a valid time or date).
www.acornfiresecurity.com
www.acornfiresecurity.com

19
This page is intentionally left blank
www.acornfiresecurity.com
www.acornfiresecurity.com

20
This page is intentionally left blank
www.acornfiresecurity.com
www.acornfiresecurity.com
Other manuals for ExGo Series
1
This manual suits for next models
1
Table of contents
Other Advanced Control Panel manuals

Advanced
Advanced MxPro 4 4100S User manual

Advanced
Advanced LIFELINE Px-100 User manual

Advanced
Advanced Lux Intelligent LX-9400 User manual

Advanced
Advanced MxPro4 Mx-4200 User manual

Advanced
Advanced LIFELINE Px-100 User manual

Advanced
Advanced Mx Pro 4 User manual

Advanced
Advanced MxPro 5 Installation and operating instructions

Advanced
Advanced Ex-3001 User manual

Advanced
Advanced MxPro4 Series User manual

Advanced
Advanced Quick Zone XL Guide