Advanced MxPro4 Mx-4200 User manual

User Manual
The operation and functions described in this manual are available from Software Version Mx4200V-023 and Mx4400V-
023 onwards.
www.acornfiresecurity.com
www.acornfiresecurity.com

This page is intentionally left blank.
www.acornfiresecurity.com
www.acornfiresecurity.com

3
Contents
1INTRODUCTION 5
1.1 STANDARDS 5
1.2 CAUTIONS AND WARNINGS 6
1.3 GENERAL DESCRIPTION 6
2CONTROLS AND INDICATIONS 7
2.1 GRAPHICAL DISPLAY 7
2.2 LED STATUS INDICATORS 8
2.3 CONTROL BUTTONS 8
2.4 NAVIGATION BUTTONS 9
2.5 NUMBER AND LETTER BUTTONS 9
2.6 BUZZER 9
3OPERATION 10
3.1 ACCESS LEVELS 10
3.1.1 Changing from Access Level 1 to Level 2 10
3.1.1.1 Menu Access 10
3.1.1.2 Control Buttons at Level 1 11
3.1.2 Changing from Access Level 2 to 1 11
3.2 FIRE ALARM CONDITION 11
3.2.1 Detailed Fire Alarm Information 12
3.2.2 Investigation Delays 13
3.3 FAULT CONDITION 14
3.4 DISABLEMENT CONDITION 15
3.4.1 Disabled Inputs 15
3.4.2 Disabled Outputs 16
3.5 ALARM CONDITION 16
3.6 MENU FUNCTIONS 17
3.6.1 Using the Buttons to Navigate Menus 18
3.6.1.1 Selecting Menu Options 18
3.6.1.2 Selecting Individual Zone Numbers 18
3.7 VIEWING 19
3.7.1 View - Fires 19
3.7.2 View - Faults 19
3.7.3 View - Alarms 19
3.7.4 View - Disabled 19
3.7.5 View - Inputs 19
3.7.6 View - Outputs 20
3.7.7 View - Panel 21
3.7.8 View - Log 22
3.7.8.1 Event Log 22
3.7.8.2 Alarm Counter 22
3.7.9 View - Network 22
3.7.10 View - Logic 23
3.8 DISABLING 23
3.8.1 Disable - Zones and Inputs 23
3.8.2 Disable - Outputs 24
3.8.2.1 All Sounder Outputs 25
3.8.2.2 All Other Outputs 25
3.8.2.3 Selected Outputs 25
3.8.2.4 Fire Routing Output 25
3.8.2.5 Fault Routing Output 25
3.8.2.6 Pager 25
3.8.3 Disable - Controls 25
3.8.4Disable - Delay-Mode 26
3.8.5 Disable –User ID 27
3.8.6 Disable –Groups 27
3.9 ENABLING 28
3.9.1 Enable - Zones and Inputs 28
3.9.2 Enable - Outputs 28
3.9.3 Enable - Delay-Mode 28
3.9.3.1 Extend Delays 28
www.acornfiresecurity.com
www.acornfiresecurity.com

4
3.9.3.2 Holiday / Inhibit 28
3.9.4 Enable - Groups 29
3.9.5 Enable - Change-Time 29
3.9.6 Enable - Remote 30
3.10 TESTING 31
3.10.1 Test - Zones 31
3.10.2 Test - Display 32
3.10.3 Test - Buzzer 32
3.10.4 Test - Printer 33
3.10.5 Test - Outputs 33
3.11 PRINTING 34
3.11.1 Printer Communications Settings 34
3.11.2 Set-up Printer 34
3.11.3 Print Inputs 34
3.11.4 Print Outputs 35
3.11.5 Print Faults 35
3.11.6 Print Disabled 35
3.11.7 Print - Log 36
3.11.8 Print - Feed Paper 36
www.acornfiresecurity.com
www.acornfiresecurity.com

5
1 Introduction
1.1 Standards
Advanced Electronics Ltd declare that the products identified below conform to the essential requirements
specified in the Construction Products Directive 89/106/EEC:
0086-CPD-549125
EN54-2: 1997 +A1:2006
Control and indicating equipment for fire detection and fire
alarm systems for buildings
Provided options:
- Outputs to Fire Alarm Devices
- Output to Fire Routing Equipment
- Output to Fault Routing Equipment
- Investigation Delays to Outputs
- Dependency on more than one alarm signal
- Fault Signals from Points
- Disablement of Points
- Alarm Counter
- Test Condition
- Standardised Input / Output
EN54-4: 1997 +A1:2002 +A2:2006
Power supply equipment for fire detection and fire alarm
systems for buildings
Mx-4200V, Mx-4200V/D, Mx-4400V, Mx-4400V/D,
Mx-4400V/LE and Mx-4800V
In addition, the products comply with the following:
Low Voltage Directive 2006/95/EC
EN60950-1: 2006 Safety of information technology equipment
Electromagnetic Compatibility Directive 2004/108/EC
EN61000-6-3:2001 Emissions, Class B
EN50130-4: 1995 +A1:1998 +A2: 2003 Immunity, Product Family Standard
www.acornfiresecurity.com
www.acornfiresecurity.com

6
1.2 Cautions and Warnings
STOP
Before commencing with installation or operation of the panel, please read this
manual carefully. If you are unclear on any point DO NOT proceed. Contact the
manufacturer or supplier for clarification and guidance.
Only Trained service personnel should undertake the Installation, Programming and
maintenance of this equipment.
This product has been designed to comply with the requirements of the Low Voltage
Safety and the EMC Directives. Failure to follow the installation instructions may
compromise its adherence to these standards.
This Fire Alarm Control Panel is compliant with the requirements of EN54 parts 2
and 4 (1998).
Where appropriate, reference is made in this manual to the relevant sections of the
EN54 standard for clarification and to ensure that the installation is compliant with
the requirements of EN54.
1.3 General Description
This manual covers the use and operation of the Mx-4200, Mx-4400 and Mx-4800 Fire Alarm Control Panels.
Refer to the Installation and Commissioning Manual (Document No. 680-158) for details of how to install and
program the panel.
The Mx-4200V is a Multiple Loop, Analogue Addressable Fire Alarm Control Panel with provision for up to
two loops.
The Mx-4400V is a Multiple Loop, Analogue Addressable Fire Alarm Control Panel with provision for up to
four loops.
The Mx-4800V is a Multiple Loop, Analogue Addressable Fire Alarm Control Panel with provision for up to
eight loops.
All panels are designed for use with the ADVANCED / ARGUS VEGA ranges of fire detection devices
www.acornfiresecurity.com
www.acornfiresecurity.com

7
2 Controls and Indications
The Mx-4100, Mx-4200, Mx-4400 and Mx-4800 are provided with indications and control functions as shown in
the diagram below and described in the following text. The Mx-4800 has two such display elements, one for
loops 1-4 and the other for loops 5-8. Normal operator level indications, controls and user programming can all
be achieved using either display.
2.1 Graphical Display
The graphical display provides detailed information of the source of fire alarms, faults and warnings. It also
shows menus for use when inspecting or programming the operation of the panel.
Under normal conditions the panel display shows the access level, time, date and status: -
LEVEL 2
16:05
04 MAR 2006
NORMAL PANEL OPERATION
(Press Menu to View)
!!
E
V
A
C
U
A
T
E
S
I
L
E
N
C
E
/
R
E
S
O
U
N
D
R
E
S
E
T
M
U
T
E
E
S
C
M
E
N
U
P
Q
R
S
W
X
Y
Z
T
U
V
G
H
I
J
K
L
M
N
O
D
E
F
A
B
C
T
E
S
T
D
I
S
A
B
L
E
F
A
U
L
T
S
Y
S
T
E
M
F
A
U
L
T
S
O
U
N
D
E
R
D
I
S
A
B
L
E
D
S
O
U
N
D
E
R
S
I
L
E
N
C
E
D
S
O
U
N
D
E
R
F
A
U
L
T
P
O
W
E
R
D
E
L
A
Y
E
D
F
I
R
E
LED Status
Indicators
Control
Buttons
Number and
Letter Buttons
Graphic Liquid
Crystal Display
Navigation
Buttons
www.acornfiresecurity.com
www.acornfiresecurity.com

8
2.2 LED Status Indicators
The LED Status Indications show the basic operational state of the panel and whether the panel is in a fire
alarm, fault, disabled or test condition.
Function
Colour
Description
FIRE
Red
Indicates that the system has detected a fire alarm condition (flashes on
a new alarm and turns on steady when mute button is pressed).
Fault
Yellow
Indicates that the system has detected a fault condition (flashes on a
new fault and turns on steady when mute button is pressed).
Disable
Yellow
Indicates that part of the system has been disable (i.e. isolated)
Test
Yellow
Indicates that part of the system is in a test condition
Power
Green
Indicates the presence of power
Sounder Silenced
Yellow
Indicates that the sounders have been silenced
Sounder Fault
Yellow
Indicates the presence of a fault in one or more sounder wiring circuits
Sounder Disabled
Yellow
Indicates that one or more sounders have been disabled (i.e. isolated)
System Fault
Yellow
Indicates the presence of a system fault
Delayed
Yellow
Indicates that one or more output circuits are in a delayed operating
condition
Function 1
Red
Fire Brigade Output Activated
Or
Spare function LED
Function 2
Yellow
Fire Brigade Output Disabled
Or
Spare function LED
Function 3
Yellow
Fire Brigade Output Fault
Or
Spare function LED
Function 4
Yellow
Spare function LED
Function 5
Yellow
Spare function LED
The function LED Indicators are programmable and will have been configured and labelled accordingly during
installation and commissioning of the system.
2.3 Control Buttons
Reset
Press to reset the panel from a fire alarm condition.
Only available with
Level 2 Access.
!
Mute
Press to mute the internal buzzer.
Available in both
Level 1 and Level 2
Silence / Resound
Press to silence the sounders.
Press again to re-activate the sounders.
Only available with
Level 2 Access.
Evacuate
Press to initiate a manual evacuation and sound the alarms.
Only available with
Level 2 Access.
www.acornfiresecurity.com
www.acornfiresecurity.com

9
2.4 Navigation Buttons
Press to scroll through Menu Options.
Press to display more information.
Press to scroll through lists of zones or devices.
✔
Press to confirm entry of numeric or letter information entry.
Press to confirm selection of a menu option.
Press to change some of the configuration options.
2.5 Number and Letter Buttons
E
S
C
M
E
N
U
W
X
Y
Z
T
U
V
P
Q
R
S
G
H
I
J
K
L
M
N
O
D
E
F
A
B
C
Used to enter numbers or letters.
Esc
Press to return to a previous menu.
Press to exit the menu functions and return to the normal display.
Menu
Press to show or return to Menu Functions.
2.6 Buzzer
The buzzer produces two different sounds to differentiate between fire alarm conditions and fault conditions.
Condition
Operation
Fire Alarm
The buzzer operates with a continuous tone.
Fault
The buzzer operates intermittently.
www.acornfiresecurity.com
www.acornfiresecurity.com

10
3 Operation
3.1 Access Levels
The panel operation is protected from inadvertent and erroneous misuse by means of four access levels. These
levels are as follows:
Level 1 Untrained user
Level 2 Authorised User
Level 3 Service and Maintenance Engineer
Level 4 Service and Maintenance Engineer –Special Tools required
A Level 1 Untrained User can view the current operational condition of the system and may
MUTE the internal buzzer.
NOTE: Depending on the configuration settings, a Level 1 user may also be permitted to EVACUATE and/or SILENCE
and/or RESET the system by pressing the appropriate button and entering a password.
A Level 2 Authorised User can view the operational condition of the system and may MUTE the
internal buzzer. In addition, the EVACUATE, SILENCE and RESET buttons are enabled and
access to the Level 2 Menu functions is available.
NOTE: There are up to 10 User ID codes available, each with its own password, which can be configured with varying
permissions to specific menu function options.
A Level 3 User has access to program and configure the operation of the panel. This is described in
detail in the Installation and Commissioning Manual (Part Number 680-014).
3.1.1 Changing from Access Level 1 to Level 2
If the panel has an access key switch fitted, use the key in preference to the menu options shown
below.
3.1.1.1 Menu Access
Press the ‘MENU’ button. The level 1 menu will be displayed as shown below:
[ CONTROLS DISABLED ]
ENABLE CONTROLS VIEW
LED TEST STATUS
To enable the controls, ensure the “Enable Controls” option is highlighted and then press the ✔button. The
display then requests entry of the Level 2 or 3 passwords as follows:
[ CONTROLS DISABLED ]
Please Enter Your Password
Enter the password using the number buttons and then press the ✔button. As each number is entered, an
asterisk (*) is shown on the display. For example:
[ CONTROLS DISABLED ]
Please Enter Your Password
**
If the password is correct, the Level 2 Menu options will be shown.
If the password is incorrect, the display briefly shows the following message.
www.acornfiresecurity.com
www.acornfiresecurity.com

11
[ CONTROLS DISABLED ]
Please Enter Your Password
Password Not Recognised !
3.1.1.2 Control Buttons at Level 1
If any of the control buttons (Reset, Silence / Resound or Evacuate) are pressed, the display automatically
prompts for the password. Enter the password as above
3.1.2 Changing from Access Level 2 to 1
If the panel has an access key switch fitted, use the key switch.
Alternatively, if passwords are used, select the “Disablement” menu and then select “Disable/Controls” – see
section 3.8.3 for details.
3.2 Fire Alarm Condition
When the system registers a fire alarm condition the Red Fire Indicator illuminates, the internal buzzer sounds
(continuously) and the display shows the zone in which the fire originated. The sounders, relays and other
outputs will be turned on depending on the programming in the panel. An example of the display is shown
below: -
FIRE STARTED IN ZONE 0001 .
BASEMENT WEST
KITCHEN <CALL POINT >
< Location Text for First Zone
< Location Text and Type of Device
[ 1 Zone in Fire][Last Fire in Z0001]
BASEMENT WEST
< No. of Zones in Fire & Last Zone
< Zone Description for Last Zone
The upper part of the display shows the origin of the fire. The lower part of the display shows the number of
zones in a fire alarm condition and the last zone to enter the fire alarm condition. This lower fire alarm status
display is always present when the panel has registered a fire alarm condition.
If more than one fire alarm condition occurs, the total number of zones in an alarm condition and the last zone in
an alarm condition will be updated on the display. If the sounders were silenced, they will sound again whenever
the fire spreads to a new zone.
FIRE STARTED IN ZONE 0001. More Alarms>
BASEMENT WEST
KITCHEN <CALL POINT >
< Location Text for First Zone
< Location Text and Type of Device
[ 2 Zones in Fire][Last Fire in Z0005]
BASEMENT EAST
< No. of Zones in Fire & Last Zone
< Zone Description for Last Zone
Press the ‘MUTE’ button to silence the internal buzzer (the FIRE LED will change from flashing to steady
illumination).
When the panel is enabled for Level 2 Access or, if configured, by entering a password at Level 1, the following
functions are available.
Press the ‘SILENCE / RESOUND’ button to silence the sounders.
Press the ‘SILENCE / RESOUND’ button again to re-activate the sounders.
Press the ‘RESET’ button to clear the alarm condition and restore the panel to normal operation.
Press the ‘EVACUATE’ button to initiate a manual evacuation and to activate the sounders. The display will
show this fire alarm condition. For example:
www.acornfiresecurity.com
www.acornfiresecurity.com

12
FIRE STARTED IN ZONE 0100 .
MAIN RECEPTION
Evacuation Key <SWITCH >
< Location Text for First Zone
< Confirmation of Evacuation
[ 1 Zone in Fire][Last Fire in Z0100]
MAIN RECEPTION
< No. of Zones in Fire & Last Zone
< Zone Description for Last Zone
3.2.1 Detailed Fire Alarm Information
Press the buttons to view a list of all zones in a fire alarm condition.
Zone FIRE-LOCATION Scroll More>
0001 BASEMENT WEST
0005 BASEMENT EAST
< List of Zones in Alarm including
< Zone No. and location text
If more detail regarding the source of any fires is required, press the buttons to highlight the required zone
in alarm and press the button to show further information. For example:
[ FIRES IN ZONE 001 ] More>
LP ADRS DEVICE LOCATION
1 001.0 KITCHEN
< List of devices within the Zone
< that are in Alarm
[ 2 Zones in Fire][Last Fire in Z0005]
BASEMENT EAST
< No. of Zones in Fire & Last Zone
< Zone Description for Last Zone
This shows that the device at address 1 on the loop initiated the fire in Zone 1. If there are more Zone 1 devices
in alarm, these will be shown in the list. Press the buttons to scroll through the devices.
Press the button or the ‘Esc’ button to return to the previous display. If no button is pressed within 15-
seconds, the display automatically reverts to the main display.
www.acornfiresecurity.com
www.acornfiresecurity.com

13
3.2.2 Investigation Delays
The Investigation Delay Function can be disabled or enabled as required by EN54: 2.
Refer to Section 3.8.4.
If the Investigation Delay Function (Stage 1 / Stage 2 Investigation Delay) is enabled, a fire alarm is registered
at the panel but does not immediately activate the sounders. On registering the alarm, the display shows:
FIRE STARTED IN ZONE 0001 .
BASEMENT WEST
KITCHEN <TEMPERATURE>
OUTPUT DELAY 30 s (Press 0 to extend)
< Location Text for First Zone
< Location Text and Type of Device
< Delay Timer (Stage 1)
[ 1 Zone in Fire][Last Fire in Z0001]
BASEMENT WEST
The Output Delay Timer shows the amount of time left for investigation.
If the alarm is not acknowledged before the Stage 1 timer elapses, the panel will enter a full alarm condition and
will activate the sounders.
Pressing the ‘0’ button acknowledges the alarm. This extends the time allowed to investigate the source of the
fire.
FIRE STARTED IN ZONE 0001 .
BASEMENT WEST
KITCHEN <TEMPERATURE>
OUTPUT DELAY 120 s
< Location Text for First Zone
< Location Text and Type of Device
< Delay Timer (Stage 2)
[ 1 Zone in Fire][Last Fire in Z0001]
BASEMENT WEST
The cause of the alarm can now be investigated. If the alarm is a false alarm, pressing the ‘RESET’ button will
clear the alarm condition. This must be done before the Stage 2 timer has elapsed or the panel will enter a full
alarm condition and will activate the sounders.
Note: The EVACUATION button will terminate the investigation delays and activate all programmed sounders.
www.acornfiresecurity.com
www.acornfiresecurity.com

14
3.3 Fault Condition
When the system registers a fault condition the Yellow Fault Indicator is illuminated, the internal buzzer sounds
intermittently and the display shows the cause of the fault in more detail.
An example of the display is shown below:
ZONE 0001 DEVICE MISSING
BASEMENT WEST
RESTAURANT (MULTI.SENSOR)
< Location Text for First Zone
< Location Text and Type of Device
1 Zone In Fault More>
< No. of Zones in FAULT
If more than one fault condition occurs, these will be shown on the display. If the internal buzzer was muted, it
will sound again when a new fault condition is registered.
When the fault condition is corrected, the panel automatically clears the appropriate fault Status Indicators and
Display information.
Press the ‘MUTE’ button to silence the internal buzzer (the general FAULT LED will change from flashing to
steady illumination). The display then shows the current time and date and service centre telephone number
along with the indication of the fault.
FOR SERVICE CALL
01234 567890
LEVEL 2
16:05
04 MAR 2006
< Panel access level
< Service Call Number
< and Time / Date
1 Zone In Fault More>
< No. of Zones in FAULT
To obtain more detailed information about the faults, press the button. The display then presents a list of all
of the zones in a fault condition with the first fault highlighted. For example:
[ 2 Zones in Fault] More>
ZONE LOCATION
1 BASEMENT
100 RECEPTION
< Number of zones in fault
< Zone #, Location Text for each
< zone
Press the buttons to highlight the required fault and then press the button to show further information.
For example:
[ Faults in Zone 0001 ] More>
LP ADRS STATE
1 004.0 DEVICE MISSING
< Address, fault condition
Press the button to show further information on device location, type analogue/digital values etc.
Press the ‘ESC’ key to return to the previous display.
If no button is pressed within a minute, the display automatically reverts to the main display.
www.acornfiresecurity.com
www.acornfiresecurity.com

15
3.4 Disablement Condition
If any zones, input devices or output devices have been disabled, the DISABLE Indicator is illuminated. In
addition, the SOUNDER DISABLE Indicator is illuminated if one or more sounder circuits or devices have been
disabled. The display indicates the presence of zone disablement conditions in the lower half of the display as
follows:
LEVEL 2
16:05
04 MAR 2006
1 Zone With Disablements More>
When the disablement conditions are removed, the appropriate indications are cleared from the display and
from the Indicators. When all disablement conditions are removed, the DISABLE Indicator is also turned off.
To obtain more detailed information about the disablement conditions, press the button. The display will then
present the disablement conditions in the following sequence:
Zone / Individual Inputs.
Outputs
3.4.1 Disabled Inputs
The display presents a list of all of the zones in a disabled condition with the first disablement highlighted. For
example:
[ 2 Zones with Inputs Disabled] More>
ZONE MODE LOCATION
0001 PART DISABLED BASEMENT WEST
0002 ALL DISABLED BASEMENT EAST
< Zone, disablement condition and
< location text
The display shows the status as ALL DISABLED if every input device within the zone has been disabled and
shows the status as PART DISABLED if there is at least one input device within the zone still active.
Press the buttons to highlight the required zone and then press the button to view the location text
assigned to the zone in full. For example:
Press the button again to view the inputs within the zone and their status. For example:
[ Inputs in Zone 0001 ] <More>
Mode Lp Adrs State
Enabled 1 001.0 Normal
Disabled 1 002.0 Normal
Enabled 1 003.0 Normal
Enabled 1 004.0 Normal
The display shows the current disablement condition (mode) for each input as either enabled or disabled. In
addition, the detection loop (LP), address (ADRS) and type of input are shown. Press the buttons to scroll
through the inputs.
Press the button to show further information on device location, type analogue/digital values etc.
Press the ‘ESC’ key to return.
If there are Outputs also disabled, these will now be shown.
www.acornfiresecurity.com
www.acornfiresecurity.com

16
3.4.2 Disabled Outputs
The display presents a list of all of the zones in a disabled condition with the first disablement highlighted. For
example:
[ 2 Zones with Outputs Disabled] More>
Zone Mode Location
0001 DISABLED BASEMENT WEST
0100 DISABLED RECEPTION
< Zones with location text where
< outputs are disabled
Press the buttons to highlight the required zone and then press the button to view the individual outputs
and their disablement condition. For example:
[ Outputs in Zone 0100] More>
Mode Lp Adrs State
Disabled 0 001.0 Off Sounder A
Disabled 0 001.1 Off Sounder B
Enabled 0 011.0 *Off Relay 1
Enabled 0 004.0 Off Relay 2
The above example shows that the panel sounder circuits are disabled.
A * symbol preceding the state (e.g. *Off) indicates the device has been configured as an inverted output (e.g. a
fault relay that is designed to de-energise when a fault occurs).
Press the buttons to scroll through the list of individual outputs within the selected zone. Press the ‘Esc’
button to return to previous views and the main display.
3.5 Alarm Condition
When the system registers a pre-alarm or plant alarm condition, the internal buzzer sounds intermittently and
the display shows the cause of the fault in more detail. An example of the display is shown below:
ZONE 0001 PRE-ALARM
BASEMENT WEST
RESTAURANT (MULTI.SENSOR)
< Location Text for First Zone
< Location Text and Type of Device
1 Zone In Alarm More>
< No. of Zones in Alarm
To obtain more detailed information about the alarms, press the button. The display then presents a list of all
zones in an alarm condition.
www.acornfiresecurity.com
www.acornfiresecurity.com

17
3.6 Menu Functions
The following Menu Functions are available at Level 2. The display shows the primary Level 2 Menu and the
Level 2 User as follows:
[Level 2 Menu] User 1 Node 1
VIEW DISABLE ENABLE
TEST PRINT COMMISSION
STATUS
The following table gives a list of the Level 2 Menu Functions, the sub-functions available within each main
function and a brief description for each function.
Main Menu Option
Sub Menus
Comments
VIEW
Fires
View Zones and Inputs that are reporting a fire alarm condition.
Faults
View Zones and Inputs that are reporting a fault condition.
Alarms
View Zones and Inputs that are reporting an alarm condition.
Disabled
View Zones, Inputs and Outputs that are disabled.
Inputs
View the current state of Inputs.
Outputs
View the current operational condition of all output circuits / devices.
Log
View the Event Log / Alarm Counter
Panel
View the operational state, voltage and current loading of the panel input and
output circuits.
Network
View Network diagnostics
DISABLE
Zone / Inputs 1
Disable a complete zone or an individual input.
Outputs 1
Disable sounder outputs or other devices.
Controls 2
Cancel Level 2 access.
Delay-Mode
Turn off the Stage 1 / Stage 2 Investigation Delay Operation
User ID 2
Return Level 2 access to the default User 1
Groups
Disable a user-defined disablement group
ENABLE
Zone / Inputs
Enable a complete zone or an individual input.
Outputs
Enable sounder outputs or other devices.
Groups
Enable a user-defined disablement group
Delay-Mode
Turn on the Stage 1 / Stage 2 Investigation Delay Operation
Change-Time 1
Allows authorised level 2 users to change time.
Remote
Permits remote access controls
TEST
Zones 1
Configure one or more zones for walk test.
Display
Test the Graphics Display, Status Indicators and Keyboard.
Buzzer
Test the Internal Buzzer
Printer
Test the connection to the Printer
Outputs
Test Output Devices
PRINT
Inputs
Print the status of inputs
Ouputs
Print the status of outputs
Faults
Print the fault conditions
Disabled
Print the disabled conditions
Log
Print the Event Log. (All Events of Fire Only Events Selectable).
Feed Paper
Advance the paper in the printer
Set-up 1
Configure the printer connection and automatic print options
STATUS
--
Returns the display to the normal operating display without wating for the timeout
COMMISSION
---
Enter the Level 3 Commissioning and Panel Programming Functions
1
This option can be configured per Level 2 User ID. User 1 does not have permission to change these options.
2
Not required if a key switch is fitted to change access levels.
www.acornfiresecurity.com
www.acornfiresecurity.com

18
3.6.1 Using the Buttons to Navigate Menus
Press the ‘Menu’ button to bring up the display menu.
3.6.1.1 Selecting Menu Options
The Level 2 Menu is shown below:
[Level 2 Menu] User 1 Node 1
VIEW DISABLE ENABLE
TEST PRINT COMMISSION
STATUS
Press the buttons to highlight the required menu option and then press the ✔button to select it.
For example, press the button followed by the button to highlight the PRINT option (as shown below) and
then press the ✔button to select this option.
[Level 2 Menu] User 1 Node 1
VIEW DISABLE ENABLE
TEST PRINT COMMISSION
STATUS
Press the ‘Esc’ button from within a menu option to return to the previous menu.
Press the ‘Esc’ button from the Main Level 2 Menu (shown above) to return to the normal operating display.
If a button is not pressed for one minute (15-seconds if the panel is in a fire alarm condition) the display will
automatically revert to the normal operating display. Press the ‘Menu’ button to return directly to the Level 2
Menu display previously shown.
3.6.1.2 Selecting Individual Zone Numbers
When the display is showing a list of Zone Numbers, it is possible to select a specific zone number by using the
number keys. For example, if the display is showing a list of zones:
[ Inputs] More>
Zone Mode Location
0001 Enabled BASEMENT WEST
0002 Enabled BASEMENT EAST
0008 Enabled GROUND FLOOR
0009 Enabled MAIN RECEPTION AREA
To select a particular Zone, move to the zone number column. The existing zone number will then be
highlighted.
Enter the required Zone Number using the number buttons, for example 12.
[ Inputs] More>
Zone Mode Location
# 12 Enabled BASEMENT WEST
0002 Enabled BASEMENT EAST
0008 Enabled GROUND FLOOR
0009 Enabled MAIN RECEPTION AREA
Finally press the ✔button to confirm. The display will then show a new list of Zones with the selected Zone
highlighted at the top of the list.
If the number is entered incorrectly, press the ‘Esc’ button.
www.acornfiresecurity.com
www.acornfiresecurity.com

19
3.7 Viewing
[View Menu] User 1 Node 1
FIRES FAULTS ALARMS DISABLED LOG
INPUTS OUTPUTS PANEL NETWORK LOGIC
Note that Fires, Faults, Alarms and Disablements are all normally shown without having to select the view
menu. If, however, you wish to manually View any of these, they can be selected from this menu as required.
3.7.1 View - Fires
This function shows the Zones and Inputs that are currently in a Fire Alarm condition.
The operation of the panel and the information that can be shown is identical to the views available from the
main operating display. Refer to Section 3.2 for further information.
If there are no Zones or Inputs in a Fire Alarm condition, the display automatically reverts to the Main View
Menu.
3.7.2 View - Faults
This function shows the Zones, Inputs and Outputs that are currently in a Fault condition.
The operation of the panel and the information that can be shown is identical to the views available from the
main operating display. Refer to Section 3.3 for further information.
3.7.3 View - Alarms
This function shows the Zones and Inputs that are currently in an Alarm condition. These may occur if:
The Zone or Input is currently in a Fire Test condition and / or
Inputs that are configured to generate an alarm or pre-alarm condition when operated are active.
The operation of the panel and the information that can be shown is identical to the views available from the
main operating display.
3.7.4 View - Disabled
This function shows only Inputs and Outputs that are currently in a Disabled condition.
The operation of the panel and the information that can be shown is identical to the views available from the
main operating display. Refer to Section 3.4 for further information.
If there are both Inputs and Outputs in a Disabled condition, the display presents the inputs first, followed by the
outputs.
If there are no Inputs or Outputs in a Disabled condition, the display does not change and continues to show the
Main View Menu.
3.7.5 View - Inputs
This function shows the current operational condition for all Zones and Individual Inputs. The display presents a
list of all of the zones containing input devices, with the first zone highlighted. For example:
www.acornfiresecurity.com
www.acornfiresecurity.com

20
[ Inputs] More>
Zone Mode Location
0001 Enabled BASEMENT WEST
0002 ALL DISABLED BASEMENT EAST
0008 Enabled GROUND FLOOR
0009 Enabled MAIN RECEPTION AREA
Press the buttons to highlight the required zone and then press the button to view the full location text
Press the button again to view the inputs within the zone and their status. For example:
[ Inputs in Zone 0008] <More>
Mode Lp Adrs State
Enabled 1 001.0 Normal
Disabled 1 002.0 Normal
Enabled 1 003.0 Normal
Enabled 1 004.0 Normal
The display shows the current disablement condition (mode) for each input as either enabled or disabled. In
addition, the detection loop (Lp), address (Adrs) and input state are shown.
Press the buttons to scroll through the inputs.
Press the button to show further information on device location, type analogue/digital values etc.
Press the ‘Esc’ button to return to previous view.
3.7.6 View - Outputs
This function shows the current operational condition for all Outputs.
[Outputs]
More>
Zone Mode Location
0008 ENABLED GROUND FLOOR
0100 ENABLED MAIN RECEPTION
Press the buttons to highlight the required zone and then press the button to view the individual outputs.
For example:
[ Outputs In Zone 0008] More>
Mode Lp Adrs State
Enabled 1 032.0 Off SOUNDER
Enabled 1 056.0 Off SOUNDER
Enabled 2 011.1 *On RELAY
Enabled 3 026.1 Off RELAY
A * symbol preceding the state (e.g. *On) indicates the device has been configured as an inverted output (e.g. a
fault relay that is designed to de-energise when a fault occurs).
www.acornfiresecurity.com
www.acornfiresecurity.com
This manual suits for next models
12
Table of contents
Other Advanced Control Panel manuals

Advanced
Advanced LIFELINE Px-100 User manual

Advanced
Advanced Lux Intelligent LX-9400 User manual

Advanced
Advanced MxPro4 Series User manual

Advanced
Advanced Quick Zone XL Guide

Advanced
Advanced Mx Pro 4 User manual

Advanced
Advanced Mx-5101xR User manual

Advanced
Advanced MxPro4 Series User manual

Advanced
Advanced MxPro 4 4100S User manual

Advanced
Advanced MxPro 5 Installation and operating instructions

Advanced
Advanced Ex-3001 User manual