Advanced configuration
The parameters are grouped into 6 sections depending on their function. To access it, press the key for 10 seconds. The Def. column shows factory-set default parameters. SE
Temperature values are expressed in ºC. (Equivalent temperature in ºF)
If the access code is activated, a 2 digit code is requested, if the code entered is incorrect the unit will not enter programming mode.
After 20 seconds with no key being pressed, the equipment will return to the previous level. If you are on level 3, the changes will not be saved.
Temperature Adjustment (Set Point)
Calibrating probe 1 (Offset)
Probe 1 differential (Histeresis)
Upper blocking of the set point
(cannot be set above this value)
Lower blocking of the set point
(cannot be set below this value)
Type of delay for protection of the compressor
0=OFF/ON (since the last disconnection);
1=OFF-ON/ON-OFF (since the last shut-down /start-up)
Protection delay time
(value of the option selected in parameter C4)
Status of COOL relay with probe fault
0=OFF; 1=ON; 2=Average based on last 24 hours prior to probe fault;
3=ON-OFF as prog. C7 and C8
Time relay ON in case of faulty probe
(If C7=0 and C8¹0, the relay will always be OFF deenergised)
Time relay OFF in case of fault of probe 1
(If C8=0 y C7¹0, the relay will always be ON energised)
Idle time of the digital input for the change Set Point function to be
activated (Only if P10 or P11 =1) (0=OFF)
Variation of the set point (SP) when the change set point function
is active. (SP+C12 £ C2) (0= disabled)
Defrost frequency (Time between two starts)
Maximum defrost duration (0=defrost deactivated)
Type of message during defrost:
0=Current temperature; 1=Temperature at start of defrost;
2=Display dEF message
Maximum duration of message
(Time added at the end of the defrost process)
Defrost end temperature (probe 2) (If P4 ¹ 1)
Defrost on equipment start-up
0=NO, First defrost as per d0
1=YES, First defrost as per d6
Defrost start delay on equipment start-up
Calculated time between defrost period :
0=Total actual time; 1 =Sum of times the compressor is on
Drip time at end of defrost
(compressor and fans off) (if P4 ¹ 1)
Fan shut-down temperature as per probe 2 (if P4 ¹ 1)
Probe 2 differential (If P4 ¹ 1)
Stop fans when stopping compressor 0=No, 1=Yes
Fan status during defrost: 0=Parados; 1=En marcha
Starting delay after defrost (if F3=0)
Will only operate if it is higher than d9
Level 1
Level 2
Configuration of temperature alarms : 0=Relative to
Maximum alarm probe 1 (must be greater than SP)
Minimum alarm probe 1 (must be greater than SP)
Temperature alarm delay during start-up
Temperature alarm delay after completion of a defrost
Temperature alarm delay after reaching the value of A1 or A2
External alarm delay when receiving digital input signal (P10 or P11=2 or 3)
Deactivation delay of the external alarm when the signal of the digital input
disappears (P10 or P11=2 or 3)
Show warning if defrost is terminated by time-out 0=No, 1=Yes
Temperature Alarm Differential (A1 and A2)
Door open alarm delay (if P10 or P11=1)
Delay of all functions on receiving electrical power
Función del código de acceso (password)
0= Inactivo; 1= Bloqueo acceso a parámetros; 2= Bloqueo del teclado
Configures the default factory settings
0= No changes 1=Return to default settings
Selection of type of inputs 1=Sonda S1 2=Sondas S1 + S2
Temperature display mode
0=Integers in ºC 1=One decimal in ºC
2=Integers in ºF 3=One decimal in ºF
Probe to be displayed (as per parameter P4)
0=visualization of all the probes in sequence; 1=Probe 1 2=Probe
Configuring digital input 1 0=
Off 1= Door contact
2= External alarm 3= Severe external alarm
Configuring digital input 2 0=
Off 1= Door contact
2= External alarm 3= Severe external alarm
Digital input polarity 1
0=Energised on closed contact, 1=Energised on open contact
Digital input polarity 2
0=Energised on closed contact, 1=Energised on open contact
Maximum start-up time after pump down
(Values between 1 and 9 seconds are not accepted) (0=Disabled)
Maximum pump down time (0=Disabled)
Stop evaporator fans and compressor on opening door 0=No 1=Yes
Start up delay for fans and compressor with door open
Pump Down 0=Without pump down 1=With pump down
ACCESS CONTROL AND INFORMATION (tid)
Control board software version(Information)
Control board software review (Information)
Display board software (Information)
Display board software review (Information)
Level 1
Level 2
Rated voltage Un .............................................................400 V~ ±10 % 50/60 Hz ±5 %
Rated voltage Ue .............................................................230 V~ ±10 % 50/60 Hz ±5 %
Maximum nominal input current................................................................................32 A
Short-circuit current at the connection point ..............................................................6 kV
Probe temperature range ...................................................................–45.0 ºC to 99.9 ºC
Resolution, setting and differential..........................................................................0.1 ºC
Thermometric precision ..........................................................................................± 1 ºC
Precision of the NTC probe at 25 ºC ....................................................................± 0.4 ºC
Input for NTC probe .......................................................................................AKO-14901
Maximum input power in the operation...................................................................30 VA
Working ambient temperature ....................................................................-5 ºC to 40 ºC
Storage ambient temperature...................................................................–30 ºC to 70 ºC
Overvoltage category ..............................................................................II s/ EN 61439-1
Degree of pollution .................................................................................II s/ EN 61439-1
Degree of protection .................................................................................................IP65
Dimensions AKO-17632 / 17635 / 15720 / 15721......400(An) x 300(Al) x 165(P) mm
AKO-17633 / 17634 / 17636 / 17637......500(An) x 400(Al) x 175(P) mm
Double isolation between power supply, secondary circuit and relay output.
Type of assembly .........................................................................................Fixed internal
Programming key compatible .....................................................................AKO-D14918
Encapsulated assembly
Technical specifications
2