AKO PROCool AKO-17632 User manual

PROCool Electronic Panel
AKO-17632, AKO-17633, AKO-17634, AKO-17635, AKO-17636, AKO-17637, AKO-17520, AKO-17521
Quick guide
Maintenance
Clean the surface of the unit with a soft cloth, water and detergent. Do not use abrasive
detergents, petrol, white spirits or solvents.
Precautions
Using the equipment without following the manufacturer's instructions may affect the
device's safety requirements. To ensure that the device operates correctly, only probes
supplied by AKO should be used.
Between -40 ºC and +20 ºC, if the NTC probe is extended up to 1,000 m with minimum
0.5 mm² wire, the maximum deviation will be 0.25 ºC (Wire for probe extension ref.
AKO-15586)
IMPORTANT:
ŸThe function of the digital inputs depends on the configuration.
ŸThe recommended currents and powers are the maximum working currents
and powers.
Description
Key function
Pressing it for 5 seconds activates the Stand-By mode. Pressing it for 2 seconds the unit
returns to the normal mode. In Stand-by mode, the unit performs no action and the
display only shows the m indicator along with the temperature.
During configuration, it exits the parameter without saving changes, returns to
previous level, or exits programming.
One short press* shows the non-displayed probe reading (see P8 parameter).
Pressing it for 5 seconds starts/stops the defrost.
During configuration, it allows you to scroll through the different levels, or when
setting a parameter, to change its value.
Pressing for 5 seconds accesses the quick configuration menu.
Pressing for 10 seconds accesses the advanced configuration menu.
During configuration, it allows you to scroll through the different levels, or when
setting a parameter, to change its value.
One short press* displays the current set point value (SP).
Pressing it for 5 seconds accesses change set point.
During configuration, it accesses the level shown on the display or, when setting a
parameter, it accepts the new value.
Messages
Quick configuration
The quick configuration menu allows the unit to be configured for the most common
applications. Press the key for 5 seconds to access it. SE
SP: Set point
It sets the coldroom's working temperature
d0: Defrost frequency
Time that must elapse between the starting of each defrost.
d1: Maximum defrost duration
The defrost will end after this time has elapsed since it started.
F3: Fan status during defrost
It defines the status of the fans during defrost.
Ÿ0= Stopped
Ÿ1= Running
A1: Maximum alarm probe 1
Defines the temperature at which the maximum alarm will be triggered. Only affects probe 1.
A2: Minimum alarm probe 1
Defines the temperature at which the minimum alarm will be triggered. Only affects probe 1.
P26: Stoppage owing to pump down
It defines whether this function is active
Ÿ0= Without pump down
Ÿ1= With pump down
Stand-by active mode
Temperature
*Short press: Less than 5 seconds.
L5
Flashing 0: Access code (Password) request
You must enter the access code configured on L5 to execute the requested
function. See also parameter P2.
E1 / E2
Probe 1 or 2 faulty (open circuit, crossover or temperature outside the
probe limits; NTC: -50 To 99 ºC).
dEF
Indicates a defrost is underway. When the defrost process has finished, the
message will continue to be displayed during the time defined in
parameter d3.
AH
Alternating with temperature:
Maximum temperature in control probe alarm. Temperature set in A1 has
been reached.
AL
Alternating with temperature:
Minimum temperature in control probe alarm. Temperature set in A2 has
been reached.
AE
Alternating with temperature:
External alarm activated (by digital input).
AES
Alternating with temperature:
Severe external alarm activated (by digital input).
Adt
Alternating with temperature:
Defrost alarm time-out. Displayed when a defrost ends after the maximum
time elapsed as defined in parameter d1.
PAb
Alternating with temperature:
Door open alarm. Shown if the door remains open longer than specified in
parameter A12.
Pd
Alternating with temperature:
The maximum pump down stop time has been exceeded (P15)
LP
Alternating with temperature:
The maximum pump down start-up time has been exceeded (P14).
ASC
It indicates that a component in the compressor's safety chain has
triggered (compressor motor guard, thermistors or high pressure
controller).
Display
Stand-by key
Menu key
Set Point key
Defrost key
Alarm active
Compressor active (If P26=1)
Condenser fans
active
Defrosting in progress
Evaporator fans active
Solenoid active
ESC
SET
1
1763H202 Ed.02
GB
Advanced configuration
The parameters are grouped into 6 sections depending on their function. To access it, press the key for 10 seconds. The Def. column shows factory-set default parameters. SE
Temperature values are expressed in ºC. (Equivalent temperature in ºF)
If the access code is activated, a 2 digit code is requested, if the code entered is incorrect the unit will not enter programming mode.
After 20 seconds with no key being pressed, the equipment will return to the previous level. If you are on level 3, the changes will not be saved.
REGULATION AND CONTROL
Description
Value
Min.
Def.
Max.
rE
SP
Temperature Adjustment (Set Point)
ºC / ºF
-45
0.0
99
C0
Calibrating probe 1 (Offset)
ºC / ºF
-20.0
0.0
20.0
C1
Probe 1 differential (Histeresis)
ºC / ºF
0.1
2.0
20.0
C2
Upper blocking of the set point
(cannot be set above this value)
ºC / ºF
C3
99
99
C3
Lower blocking of the set point
(cannot be set below this value)
ºC / ºF
-45
-45
C2
C4
Type of delay for protection of the compressor
0=OFF/ON (since the last disconnection);
1=OFF-ON/ON-OFF (since the last shut-down /start-up)
0
0
1
C5
Protection delay time
(value of the option selected in parameter C4)
min.
0
0
120
C6
Status of COOL relay with probe fault
0=OFF; 1=ON; 2=Average based on last 24 hours prior to probe fault;
3=ON-OFF as prog. C7 and C8
0
2
3
C7
Time relay ON in case of faulty probe
(If C7=0 and C8¹0, the relay will always be OFF deenergised)
min.
0
10
120
C8
Time relay OFF in case of fault of probe 1
(If C8=0 y C7¹0, the relay will always be ON energised)
min.
0
5
120
C11
Idle time of the digital input for the change Set Point function to be
activated (Only if P10 or P11 =1) (0=OFF)
h.
0
0
24
C12
Variation of the set point (SP) when the change set point function
is active. (SP+C12 £ C2) (0= disabled)
ºC / ºF
C3-SP
0.0
C2-SP
EP
Exit to Level 1
DEFROST CONTROL
Description
Value
Min.
Def.
Max.
dEF
d0
Defrost frequency (Time between two starts)
0
6
96
d1
Maximum defrost duration (0=defrost deactivated)
min.
0
15
255
d2
Type of message during defrost:
0=Current temperature; 1=Temperature at start of defrost;
2=Display dEF message
0
2
2
d3
Maximum duration of message
(Time added at the end of the defrost process)
min.
0
5
255
d4
Defrost end temperature (probe 2) (If P4 ¹ 1)
ºC / ºF
-45
8.0
99.0
d5
Defrost on equipment start-up
0=NO, First defrost as per d0
1=YES, First defrost as per d6
0
0
1
d6
Defrost start delay on equipment start-up
min.
0
0
255
d8
Calculated time between defrost period :
0=Total actual time; 1 =Sum of times the compressor is on
0
0
1
d9
Drip time at end of defrost
(compressor and fans off) (if P4 ¹ 1)
min.
0
1
255
EP
Exit to Level 1
FAN CONTROL
Description
Value
Min.
Def.
Max.
FAn
F0
Fan shut-down temperature as per probe 2 (if P4 ¹ 1)
(ºC/ºF)
-45
45
99.0
F1
Probe 2 differential (If P4 ¹ 1)
(ºC/ºF)
0.1
2.0
20.0
F2
Stop fans when stopping compressor 0=No, 1=Yes
0
1
1
F3
Fan status during defrost: 0=Parados; 1=En marcha
0
0
1
F4
Starting delay after defrost (if F3=0)
Will only operate if it is higher than d9
(min.)
0
3
99
EP
Exit to Level 1
Level 1
Level 2
ALARM CONTROL
Description
Value
Min.
Def.
Max.
AL
A0
Configuration of temperature alarms : 0=Relative to
0
1
1
A1
Maximum alarm probe 1 (must be greater than SP)
(ºC/ºF)
A2
99,0
99,0
A2
Minimum alarm probe 1 (must be greater than SP)
(ºC/ºF)
-45
-45
A1
A3
Temperature alarm delay during start-up
(min.)
0
0
120
A4
Temperature alarm delay after completion of a defrost
(min.)
0
0
99
A5
Temperature alarm delay after reaching the value of A1 or A2
(min.)
0
30
99
A6
External alarm delay when receiving digital input signal (P10 or P11=2 or 3)
(min.)
0
0
120
A7
Deactivation delay of the external alarm when the signal of the digital input
disappears (P10 or P11=2 or 3)
(min.)
0
0
120
A8
Show warning if defrost is terminated by time-out 0=No, 1=Yes
0
0
1
A10
Temperature Alarm Differential (A1 and A2)
(ºC/ºF)
0,1
1,0
20,0
A12
Door open alarm delay (if P10 or P11=1)
(min.)
0
10
120
EP
Exit to Level 1
GENERAL STATUS
Description
Value
Min.
Def.
Max.
CnF
P1
Delay of all functions on receiving electrical power
(min.)
0
0
255
P2
Función del código de acceso (password)
0= Inactivo; 1= Bloqueo acceso a parámetros; 2= Bloqueo del teclado
0
0
2
P3
Configures the default factory settings
0= No changes 1=Return to default settings
0
0
1
P4
Selection of type of inputs 1=Sonda S1 2=Sondas S1 + S2
1
1
2
P7
Temperature display mode
0=Integers in ºC 1=One decimal in ºC
2=Integers in ºF 3=One decimal in ºF
0
1
3
P8
Probe to be displayed (as per parameter P4)
0=visualization of all the probes in sequence; 1=Probe 1 2=Probe
0
1
2
P10
Configuring digital input 1 0=
Off 1= Door contact
2= External alarm 3= Severe external alarm
0
0
5
P11
Configuring digital input 2 0=
Off 1= Door contact
2= External alarm 3= Severe external alarm
0
0
5
P12
Digital input polarity 1
0=Energised on closed contact, 1=Energised on open contact
0
1
1
P13
Digital input polarity 2
0=Energised on closed contact, 1=Energised on open contact
0
1
1
P14
Maximum start-up time after pump down
(Values between 1 and 9 seconds are not accepted) (0=Disabled)
(seg.)
0
0
120
P15
Maximum pump down time (0=Disabled)
(min.)
0
0
15
P23
Stop evaporator fans and compressor on opening door 0=No 1=Yes
0
0
1
P24
Start up delay for fans and compressor with door open
(min.)
0
0
999
P26
Pump Down 0=Without pump down 1=With pump down
0
1
1
EP
Exit to Level 1
ACCESS CONTROL AND INFORMATION (tid)
Description
Value
Min.
Def.
Max.
tid
L5
Access code (Password)
0
0
99
PU
Control board software version(Information)
-
Pr
Control board software review (Information)
-
PUd
Display board software (Information)
-
Prd
Display board software review (Information)
-
EP
Exit to Level 1
Level 1
Level 2
Rated voltage Un .............................................................400 V~ ±10 % 50/60 Hz ±5 %
Rated voltage Ue .............................................................230 V~ ±10 % 50/60 Hz ±5 %
Maximum nominal input current................................................................................32 A
Short-circuit current at the connection point ..............................................................6 kV
Probe temperature range ...................................................................–45.0 ºC to 99.9 ºC
Resolution, setting and differential..........................................................................0.1 ºC
Thermometric precision ..........................................................................................± 1 ºC
Precision of the NTC probe at 25 ºC ....................................................................± 0.4 ºC
Input for NTC probe .......................................................................................AKO-14901
Maximum input power in the operation...................................................................30 VA
Working ambient temperature ....................................................................-5 ºC to 40 ºC
Storage ambient temperature...................................................................–30 ºC to 70 ºC
Overvoltage category ..............................................................................II s/ EN 61439-1
Degree of pollution .................................................................................II s/ EN 61439-1
Degree of protection .................................................................................................IP65
Dimensions AKO-17632 / 17635 / 15720 / 15721......400(An) x 300(Al) x 165(P) mm
AKO-17633 / 17634 / 17636 / 17637......500(An) x 400(Al) x 175(P) mm
Double isolation between power supply, secondary circuit and relay output.
Type of assembly .........................................................................................Fixed internal
Programming key compatible .....................................................................AKO-D14918
Encapsulated assembly
Technical specifications
2
1763H202 Ed.02
GB
Combine high-low
pressure controller
Separate Low pressure
controller per AC input
Pressure controller equivalence
HIGH / LOW FAN CONTROL
Recommendations
Disconnect the voltage before carrying out any operations inside the electrical panel. All wiring should be according to current standards and should be carried out by authorised staff. Only carry
out the wiring foreseen in the wiring diagrams. Using the electrical panel not observing the manufacturer's instructions may alter the appliance's safety requirements. A tool is needed to remove
any fixed part.
Panel installation:
It is advisable to leave a clean safety space without obstacles around the panel.
Do not knock or make sudden movements on the panel.
Carry out the wiring according to the installation manual.
The probes and their cables should NEVER be installed in a conduit together with power, control or feeder cables.
The earth terminals that the panels contain are installed to guarantee the continuity of earthing, however, earthing is not carried out by the terminal and should be carried out outside the panel.
The neutral ratings are of the TT type. The IT rating should not be used.
Circuit breakers (protective switches) are of the phase/s + neutral, curve C type, guaranteeing switching and protection against overcurrents.
Close the panel when your are not working on it.
Residual current protection outside the electrical panel according to low voltage electrotechnical regulations.
The panels comply with European Standards EN 61439-1 and EN-61439-3 for the electrical panel and EN-60730 for the control board.
Terminals for copper external conductors.
Checks before starting the panel up:
Power supply voltages and frequencies will be the ones that figure in the "Technical specifications" section.
Check that there are no loose parts or foreign bodies on connections or switchgear.
Check that there is no dust or damp inside the panel.
Check the correct fastening of the switchgear and components.
Check the correct tightening of the screws and power connections.
Check the correct connection of the power conductors.
Check the correct insulation of the outer lines and that they do not mechanically force the inner connections of the panel.
Check that the maximum current of the FK1, FK2 and FK3 motor guards has been set correctly (depending on the model).
Before starting the installation up, we recommend preheating the compressor's housing.
Checks during the panel start-up:
Check that no electric arcs occur.
Check that the relays or contactors do not produce ratios.
Check that there is no overheating in cables, controllers and the rest of the switchgear.
Checks after the first 24 hours of operation:
Check that no overheating occurs.
Retighten screws and power connections.
Periodical preventive maintenance:
The panel should remain closed using its lock.
Retighten the power connections once a year.
Check the wear of the switchgear once a year.
Clean the outer surface of the panel with a soft cloth, water and detergent. Do not use abrasive detergents, petrol, white spirits or solvents.
Technical data:
Working ambient temperature: –5 ºC to 40 ºC
Rated isolation voltage Ui = 440 V~
Electrical panels with degree of protection: IP 65
CEM B environment
Terminals for copper conductors
Resistance to short-circuits Icc=6 kA
Rated pulse voltage (Vimp) 2,5 KV
Cable isolation voltage:
Operation: 500V (Halogen free)
Power: 750V (Halogen free)
Pressure switch wiring options
1
PE
4
3
LP HP
LP
HP
1
PE
4
3
4 C1 A 21 22 1
14B 12 11 2
AC
17 1718 18 4 431 1 14 3 3
DANFOS
/ ALCO / RANCO PENN ALCO RANCO
DANFOS
/ PENN
AA(1) A(1)
B(2) B(2)
B
C
4
3
1763H202 Ed.02
GB
351763202 Rev 01 2022
We reserve the right to supply materials that might vary slightly to those described in our Technical Sheets. Updated information is available on our website.
AKO ELECTROMECÁNICA , S.A.L.
Avda. Roquetes, 30-38
08812 • Sant Pere de Ribes.
Barcelona • Spain.
www.ako.com

This manual suits for next models

7

Other AKO Control Panel manuals

AKO PROPlus 3PH Series User manual

AKO

AKO PROPlus 3PH Series User manual

AKO AKO-17630 User manual

AKO

AKO AKO-17630 User manual

AKO PROPlus AKO-1565 Series User manual

AKO

AKO PROPlus AKO-1565 Series User manual

AKO PROPlus User manual

AKO

AKO PROPlus User manual

AKO AKO-15690 User manual

AKO

AKO AKO-15690 User manual

AKO 15640 User manual

AKO

AKO 15640 User manual

AKO PROPlus 3PH Series User manual

AKO

AKO PROPlus 3PH Series User manual

AKO PROCool AKO-17635-2 User manual

AKO

AKO PROCool AKO-17635-2 User manual

AKO PROCool AKO-17635-1 User manual

AKO

AKO PROCool AKO-17635-1 User manual

AKO PROPlus User manual

AKO

AKO PROPlus User manual

AKO PROPlus 3PH Series User manual

AKO

AKO PROPlus 3PH Series User manual

Popular Control Panel manuals by other brands

BFT PERSEO CBD 230.P SD installation manual

BFT

BFT PERSEO CBD 230.P SD installation manual

GE NX-1308E - Caddx 8 Zone LED Keypad Installation and startup guide

GE

GE NX-1308E - Caddx 8 Zone LED Keypad Installation and startup guide

Galletti MCA 10 M manual

Galletti

Galletti MCA 10 M manual

CAME Z Series manual

CAME

CAME Z Series manual

GAS Gasmaster Installation, operation and maintenance manual

GAS

GAS Gasmaster Installation, operation and maintenance manual

Aprilaire 6302 Safety & installation instructions

Aprilaire

Aprilaire 6302 Safety & installation instructions

Lince GOLD 869 MST Series Installation, operation and maintenance manual

Lince

Lince GOLD 869 MST Series Installation, operation and maintenance manual

Halma SENSITRON MULTISCAN++ PK-32 manual

Halma

Halma SENSITRON MULTISCAN++ PK-32 manual

AV-GAD EasyLoader AV-4044 Installation and Operation Large Manual

AV-GAD

AV-GAD EasyLoader AV-4044 Installation and Operation Large Manual

Honeywell MS-10UD Series manual

Honeywell

Honeywell MS-10UD Series manual

Velux INTEGRA KLR 200 user manual

Velux

Velux INTEGRA KLR 200 user manual

Erreka CLEVER01 Installer manual

Erreka

Erreka CLEVER01 Installer manual

Haes MZAOV-1001 Installation, commissioning & operating  manual

Haes

Haes MZAOV-1001 Installation, commissioning & operating manual

Carrier Aritech Reliance XR Series Installation and programming guide

Carrier

Carrier Aritech Reliance XR Series Installation and programming guide

DSC CFP-102 instruction manual

DSC

DSC CFP-102 instruction manual

Galletti AREO TD quick start guide

Galletti

Galletti AREO TD quick start guide

Siemens MICROMASTER 4 Getting started guide

Siemens

Siemens MICROMASTER 4 Getting started guide

D+H RZN 4416-M manual

D+H

D+H RZN 4416-M manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.