
ASSA ABLOY motor locks installation guide
15
Indications on start-up
Green LED
Flashes at one-second intervals: unit waits for lock
to be paired
Glows steadily: HI-O units detected on Hi-O bus
Red LED
Does not light up
on start-up
Unit is not set up on Hi-O bus
Red LED
Lights up on
start-up
Units are locked to a specific Hi-O bus; red
indicates that lock case is paired and encrypted.
About I/O Box 350
I/O Box 350 is a terminal that is compatible with 813C, 815C, 820,
825 and 835.
Hi-O installation
Hi-O units are easy to install; all units are connected in parallel
using four wires. Units on the Hi-O bus recieve their supply
voltage from I/O Box 350.
Indications on I/O Box 350
The unit has one green and one red LED. The operation of these is
described in the table below for ther various configuration stages
and during operation.
Technical specifications
Part number S55665710085
Supply voltage 12-24 V DC (min 11V, max 27.8 V DC)
Current
consumption at
12 V: Mean 40 mA, max 30 mA
27.8 V: Mean 20 mA, max 30 mA
Use a low-voltage (SELV) compatible power source (LPS) with a
current rating ≤ 2A
Cable 3 m AWG26
Hi-O cable length Total: Max 50 m
Cable branch length: Max 10 m
Operating temperature
range
-30°C to +70°C
Below -30°C the reader must be heated
externally
Operating humidity
range 5% to 95%
Dimensions 9 x 12 x 4 cm
IP 34
Storage and transport
Temperature: -50°C to +70°C
(-58°F to +158°F)
White CAN-H
Connection to Hi-O bus
Brown CAN-L
Green +12-24 VDC
Supply to lock via fused unit
Yellow 0 V
Description of pairing sequence
Pairing lock with I/O Box 350 on Hi-O bus
1Set the function DIP switches on the lock case to the desired settings.
2Connect the Hi-O lock to I/O Box 350.
3Turn on the power to I/O Box 350, flashing green and red LEDs indicate that
power is on.
4Set DIP switch 1 to the ON position. Set configuration.
DIP switch 2 to suit the desired position. See the table.
5The green LED will start flashing when set-up begins.
6The red LED will glow steadily when set-up is complete.
7When the green LED turns off and the red LED glows steadily the Hi-O bus is
secure and encrypted.
At the top edge of the lock next to the DIP switches is a red LED which lights up
when the lock is unpaired and turns off when the lock is paired and encrypted.
Inputs
Unlock Opens when input is closed.
Door monitor Door is registered as closed when input is closed.
NOTE! To activate this input, move the jumper from Dis to En.
The external motor and lock case door position sensor operate in series.
Both must be triggered in order for the door to be registered as closed.
Unlock fire
Thisinput is controlled by an external voltage of 12-28 V DC.
When voltage is applied to the input it unlocks the lock in the same way
as closing the Unlock input.
The Unlock and Unlock fire inputs operate in parallel. This means that the door will only
lock if both inputs are not activated.
DIP
1Used when Hi-O units are to be paired or unpaired. For more
information see Description of pairing sequence.
2Used to deactivate door monitor in lock during pairing:
Set DIP switch to ON if door position sensor in lock should be
deactivated, and connect external sensor to I/O Box.
Must be set before lock case is paired with I/O Box.
3DIP = OFF, normal mode:
DIP = ON, outputs operate according to requirements of
SSF3522.
4DIP = OFF: Door forced output will remain active after door
has been forced. Output is reset via Unlock input.
DIP = ON: Door forced output will be deactivated when door
is closed.