
AB-6584 
5 
Specifications 
Basic specifications 
Item Specification 
Rated voltage 24 V AC, 50 Hz/60 Hz 
Allowable voltage range 20.4 V AC to 27.6 V AC, 50 Hz/60 Hz 
Power shutdown 
detection 19.2 V AC or less 
Power supply 
Power consumption 15 VA 
Ambient temperature 0 °C to 50 °C 
Ambient humidity 10 %RH to 90 %RH (non-condensing) 
Altitude 2000 m or lower 
Rated 
operating 
conditions Vibration Max. 5.9 m/s2at 10 Hz to 150 Hz 
Ambient temperature -20 °C to 60 °C 
Ambient humidity 5 %RH to 95 %RH (non-condensing) 
Vibration for storage Max. 5.9 m/s2at 10 Hz to 150 Hz 
Environmental 
conditions Transport/ 
storage 
conditions Vibration for transport Max. 9.8 m/s2at 10 Hz to 150 Hz 
Repetition of 1-second ON and 
1-second OFF Data being transmitting 
Repetition of 0.25-second ON and 
0.25-second OFF LC-bus error 
ON Major failure or initializing 
Repetition of 1-second ON, 
0.25-second OFF, 0.25-seccond 
ON, and 0.25-second OFF 
Minor failure 
Repetition of 0.25-second ON, 
0.25-second OFF, 0.25-second ON, 
and 1.25-second OFF 
Engineering mode 
Operation 
OFF Power OFF 
LED indication 
LonTalk service Operation in accordance with the LonTalk specifications. 
Current Typ. 5 mA 
Voltage Typ. 24 V DC 
Digital input 
Connectable output Potential free contact 
Input signal RTD Pt 100 Ω/ 0 °CTemperature 
input Measuring range -20 °C to 80 °C 
Input voltage range 1 V to 5 V 
Input 
Voltage input Input impedance 500 kΩ
Output method Relay output N.O. contact (N.O. contacts share the same common line.) 
Max. 24 V AC, 0.5 A (inductive load: cos φ0.4 or more) 
Contact rating Max. 24 V DC, 0.5 A 
Relay output 
(normally open 
(N.O.) contact) Min. applicable load 5 V, 10 mA 
Output method Relay output N.O./N.C. contact (N.O./N.C. contacts use a different common 
line from N.O. contacts.) 
Max. 24 V AC, 0.5 A (inductive load: cos φ0.4 or more) 
Contact rating Max. 24 V DC, 0.5 A 
Relay output 
(normally 
open/normally 
close 
(N.O./N.C.) 
contact) Min. applicable load 5 V, 10 mA 
Output voltage range 2 V to 10 V / 0 V to 10 V 
Output 
Voltage output Min. load resistance 10 kΩor higher 
RAM, RTC* Lithium battery backup 
Power failure backup Data file Non-volatile memory (flash memory) backup 
Transmission system LonTalk protocol (TP/FT-10, transceiver) 
Transmission speed 78 kbps 
Transmission distance 900 m (for bus topology connection) 
Communications LC-bus 
Remote units Max. 50 remote units connectable 
Weight 500 g 
Material (housing), color Modified PPE, light gray 
Power supply, ground M3 screw terminals 
Inputs/outputs Quick-fit screwless terminal blocks 
Terminal block 
LC-bus communication Modular connectors 
Note: 
∗RTC: Real Time Clock. RTC is backed up by a lithium battery to ensure accurate clocking while the power is OFF