AB-6584
5
Specifications
Basic specifications
Item Specification
Rated voltage 24 V AC, 50 Hz/60 Hz
Allowable voltage range 20.4 V AC to 27.6 V AC, 50 Hz/60 Hz
Power shutdown
detection 19.2 V AC or less
Power supply
Power consumption 15 VA
Ambient temperature 0 °C to 50 °C
Ambient humidity 10 %RH to 90 %RH (non-condensing)
Altitude 2000 m or lower
Rated
operating
conditions Vibration Max. 5.9 m/s2at 10 Hz to 150 Hz
Ambient temperature -20 °C to 60 °C
Ambient humidity 5 %RH to 95 %RH (non-condensing)
Vibration for storage Max. 5.9 m/s2at 10 Hz to 150 Hz
Environmental
conditions Transport/
storage
conditions Vibration for transport Max. 9.8 m/s2at 10 Hz to 150 Hz
Repetition of 1-second ON and
1-second OFF Data being transmitting
Repetition of 0.25-second ON and
0.25-second OFF LC-bus error
ON Major failure or initializing
Repetition of 1-second ON,
0.25-second OFF, 0.25-seccond
ON, and 0.25-second OFF
Minor failure
Repetition of 0.25-second ON,
0.25-second OFF, 0.25-second ON,
and 1.25-second OFF
Engineering mode
Operation
OFF Power OFF
LED indication
LonTalk service Operation in accordance with the LonTalk specifications.
Current Typ. 5 mA
Voltage Typ. 24 V DC
Digital input
Connectable output Potential free contact
Input signal RTD Pt 100 Ω/ 0 °CTemperature
input Measuring range -20 °C to 80 °C
Input voltage range 1 V to 5 V
Input
Voltage input Input impedance 500 kΩ
Output method Relay output N.O. contact (N.O. contacts share the same common line.)
Max. 24 V AC, 0.5 A (inductive load: cos φ0.4 or more)
Contact rating Max. 24 V DC, 0.5 A
Relay output
(normally open
(N.O.) contact) Min. applicable load 5 V, 10 mA
Output method Relay output N.O./N.C. contact (N.O./N.C. contacts use a different common
line from N.O. contacts.)
Max. 24 V AC, 0.5 A (inductive load: cos φ0.4 or more)
Contact rating Max. 24 V DC, 0.5 A
Relay output
(normally
open/normally
close
(N.O./N.C.)
contact) Min. applicable load 5 V, 10 mA
Output voltage range 2 V to 10 V / 0 V to 10 V
Output
Voltage output Min. load resistance 10 kΩor higher
RAM, RTC* Lithium battery backup
Power failure backup Data file Non-volatile memory (flash memory) backup
Transmission system LonTalk protocol (TP/FT-10, transceiver)
Transmission speed 78 kbps
Transmission distance 900 m (for bus topology connection)
Communications LC-bus
Remote units Max. 50 remote units connectable
Weight 500 g
Material (housing), color Modified PPE, light gray
Power supply, ground M3 screw terminals
Inputs/outputs Quick-fit screwless terminal blocks
Terminal block
LC-bus communication Modular connectors
Note: