AB-6567
6
Specifications
Basic specifications
Item Specification
Power Rated voltage 100 V AC to 240 V AC at 50 Hz/60 Hz
Operating voltage 85 V AC to 264 V AC
Power consumption Valve ON/OFF control type: 6 VA or less
Valve proportional control type: 7 VA or less
Environmental
conditions
Operating
conditions
Ambient temperature 0 °C to 50 °C
Ambient humidity 10 %RH to 90 %RH (non-condensing)
Altitude Max. 2,000 m
Vibration Max. 3.2 m/s² (at 10 Hz to 150 Hz)
Transport
/storage
conditions
Ambient temperature -20 °C to 60 °C
Ambient humidity 5 %RH to 95 %RH (non-condensing)
Vibration Max. 9.8 m/s² (at 10 Hz to 150 Hz) for transport
Max. 3.2 m/s² (at 10 Hz to 150 Hz) for storage
Mounting location Side surface of FCU, inside of the ceiling, inside of control panel, inside of a box
Mounting With two M4 x 10 mm long screws
Address setting Rotary switch setting
Weight Valve ON/OFF control type: 270 g (main unit only)
Valve proportional control type: 480 g (main unit only)
Materials Modified PPE, equivalent to UL 94 V-0
PPE: Polyphenylene ether
Input/output specifications (1/2)
Unit to be connected Input/output description Input/output specification
Temperature sensor Temperature input Measuring range 0 °C to 50 °C
Input signal RTD (Pt100)
RTD (Pt1000)*1
Temperature sensor for pipe
surface*2
(Part No. 81301851-001 /
81301851-002)
Pipe surface temperature input
(for cooling/heating changeover)
Measuring range 0 °C to 50 °C
External relay, etc.*2 Contact input
(for cooling/heating changeover)
Connectable output type Potential free contact (maintained)
* Min. applicable load: 0.1 mA or lower
Control valve*3 ON/OFF output
(for valve ON/OFF control type)
Floating proportional output
(for valve proportional control type)
Connectable output type Voltage N.O. contact
Contact capacity 0.8 A / 125 V AC or less
0.4A / 250 V AC or less
Min. applicable load 10 mA AC
* For the power of valve ON/OFF control
type, the power of the fan is used. Select
ON/OFF valve with the rated power equal
to the FCU power.
Fan Fan ON/OFF output
Fan speed changeover output
Valve ON/OFF control, valve proportional control types (M/H output)
Connectable output
type
Potential free N.O. contact
Contact capacity 3 A / 125 V AC or less
1.5 A / 250 V AC or less
Min. applicable load 10 mA AC
Valve proportional control type (L output)
Connectable output
type
Potential free N.O. contact
Contact capacity 6 A / 125 V AC or less
3 A / 250 V AC or less
Min. applicable load 10 mA AC
Neopanel
(digital user terminal)
Temperature setting
FCU ON/OFF, etc.
Transmission system Serial voltage transmission
Transmission speed 100 bps
RTD: Resistance temperature detector
Notes:
*1 Because the Pt1000 temperature sensor is a two-wire type sensor, the wire resistance will cause measuring error. For instance,
1.25 mm2 size wire causes approx. 0.1 °C measuring error every 10 m. Correct the measuring error by setting Infilex FC.
*2 Either the pipe surface temperature input by the temperature sensor for pipe surface or the contact input by the external relay is used for
cooling/heating changeover of Infilex FC for standalone use.
*3 Proportional control valve with less than 30-second operating time (for full stroke) is not connectable. Ask our salesperson for details.