manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. B.E.G.
  6. •
  7. Security Sensor
  8. •
  9. B.E.G. LUXOMAT PD4-M-DALI/DSI-C User guide

B.E.G. LUXOMAT PD4-M-DALI/DSI-C User guide

Installation and Operating Instruction for B.E.G.-Occupancy detectors PD4-M-DALI/DSI-C-SM/-FC
2a. Installation of the
LUXOMAT
®
PD4-M-DALI/DSI-C-SM
2b. Installation of the LUXOMAT®
PD4-M-DALI/DSI-C
-FC
LUXOMAT®
PD4-M-DALI/DSI-C
1b. Mounting preparations
Work on the 230 V mains supply
may only be carried out by quali-
fied professionals or by instructed
persons under the direction and
supervision of qualified skilled elec-
trical personnel in accordance with
electrotechnical regulations.
Disconnect supply before installing!
When in Master/Slave mode of
operation, the Master-appliance
must always be installed at the
location where there is least
daylight.
The
PD4-M-DALI/DSI-C
enters an
initial 60-second self-test cycle, when
the supply is first connected. The occu-
pancy detector is ready for operation.
5. Self test cycle
1a. Features
*
For connection of up to 50 lamps
* Suitable for dimmable electronic
ballasts and control modules
* DALI/DSI output
* Constant light control
* Manual switching/dimming
* Semi or completely automatic
operation
*
Luminance (brightness) set point,
switch-off delay time for LIGHT and
orientation-light adjustable
* Sensor and power sections in one
housing
* Infrared remote control
GB
68 mm
A circular opening of diameter 68 mm
must be produced in the ceiling. Having
connected up the cables in accordance
with regulations, the detector is inserted
into the opening as shown in the drawing
opposite and fixed into position with the
assistance of the spring clips.
C
The detector must be installed on a solid and level surface. The
circular cover ring must be removed prior to assembly. To do this,
twist the lens (C) anticlockwise through approximately 5° and lift
off.
Having connected up the wires in accordance with regulations,
secure the detector with two screws. After installation replace the
lens and lock (turn clockwise). Mains to be connected
.
ATTENTION: For maximum
sensitivity the corridor detec-
tor-, lens- and corridor-axis
must match.
open
close
open closed
3a. Position DIP-Switches, LEDs and potentiometers SM
ONOFF
DIP
1 I2 II3III
C
B
A
PD4-Surface
mounting
3b. Position DIP-Switches, LEDs and potentiometers FC
PD4-
False ceiling mounting
ON
OFF
DIP
1 2 3
III III
CBA
DIP 1 = Change between fully automatic and semi automatic mode
DIP 2 = Change between HVAC-function and light control*
DIP 3 = Change between DALI/DSI mode
Potentiometer A Lux channel1
Potentiometer B Time channel1
Potentiometer C Orientation lighting
LED I green
LED II red
LED IIIwhite
The DIP switch settings are overriden using the
remote control.
4. DIP switch functions
DIP-
switch
ON OFF
1 Semi automatic mode Fully automatic mode
2 Corridor mode Normal mode
3 DSI mode DALI mode
DIP
OFF ON
1
2
3
The DIP settings are enabled again by:
• Adjusting the DIP switches when closed
• Reset with test sun setting at the potentiometers
• Reset when open
Corridor function: After deactivation by an external push button,
the detector switches off and returns to automatic mode after 5sec.
6. Putting into operation / Settings
Follow-up time for light control
The time can be set infinitely variably at between
1 and 30 minutes.
Symbol TEST: Test mode
Every movement switches on the light for a period of 1 second,
switching it off for a period of 2 seconds after that regardless of
the level of brightness.
Twilight-switch for constant light control
The switch-on value for the light can be set at between 10 and
2000 Lux. Using the rotary control, the luminance set points can
be set as desired.
Symbol : Night-time operation
Symbol : Daytime/Night-time operation
Orientation lighting
The orientation lighting can be set at between 5 and 60 min.
This rotary controller serves to determine the working time of the
orientation lighting.
„ON” for permanent orientation lighting.
„OFF” for deactiviation of orientation lighting.
Pulse spacing PD-Slave
2 or 9 seconds can be set for the pause between 2 pulses sent
to the master. The setting can be made with activated ( ) or
deactivated ( ) LED indicator.
For devices with a separate slave input, 2 sec. can be set.
25 22
18
1
6
10
3
1
TEST 6
30
R1
120 6050
40
30
15
10
A
16 10 5
2
1
30
15
TEST
2000
1200
600
200
40
5
60
5
10
30
50
ON
OFF
9s 2s
LED ON
LED OFF
1
1 2
2
25 22
18
1
6
10
3
1
TEST 6
30
R1
120 6050
40
30
15
10
A
16 10 5
2
1
30
15
TEST
2000
1200
600
200
40
5
25 22
18
1
6
10
3
1
TEST 6
30
R1
2000
1200
600
200
40
7. Settings carried out using remote control (optional)
Remote control LUXOMAT®IR-PD-DALI
1. Check Battery:
open battery compartment by pressing the
plastic springs together and removing the
battery-holder.
2. IMPORTANT
Please pay attention, that the setting is potentio-
meter 1 and potentiometer 2 not at the same
time at “TEST” and at “SUN”. All values which
have been programmed using the remote control
will be deleted in the event of power failure in
the position “TEST/SUN”. Please switch potentio-
meter 2 over to “MOON” or any other value.
Caution:
Settings with remote control override the
potentiometer or DIP switch settings.
2000
1200
600
200
40
8. Option:
Wall bracket for remote control
IR-PD-DALI
IR-PD-DALI
9. Settings by remote control when open
12. Manual Dimming – Preset / User
(for IR-PD-DALI functions see page 1)
You can dim manually by pressing the pushbutton for a
long time (> 2 sec.). When the button is released, the
current dimming value is retained. Upon renewed dimming,
the dimming direction is reversed.
PRESET –the luminance set point is set during start-up
operation by the installer and remains unchanged. The
luminance set- point congured through manual dimming is
only applied for the time being.
Caution:
The constant light regulation is now deactivated!
The currently set articial light is retained independent of
the ambient/daylight brightness!
After switching off and then back on, the originally set
luminance set-point is reset = constant light regulation is
activated.
USER – can only be activated via the remote control!
The luminance set-point is changed upon each manual
dimming and re-adjusted by the user.
The constant light regulation remains activated!
11. Fully/ Semi automatic mode
(for IR-PD-DALI functions see page 1)
Toggle between fully and semiautomatic operation by switching
the button in opened state. The relevant status is shown by
ashing of the red /resp. green LED.
Fully automatic operation
In this operating mode, the lighting switches automatically on
and off for increased comfort, depending on presence and
brightness.
Semiautomatic operation
In this operating condition, in order to gain increased savings,
the lighting is energized only after being manually switched on.
Switch-off takes place automatically.
The semiautomatic mode basically behaves like the fully
automatic one. However, the difference is that switching-on must
always be carried out manually!
As many (closer-contact) buttons as desired can be wired in
parallel on the “S” button input (ON/OFF Dimm).
The switch by IR-PD-DALI acts only on the lightchannel.
13. Manual Switching
You can switch the lighting on and off manually by pressing
the pushbutton for a short time. It will stay on or off as long
as people are detected plus the congured follow up time.
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
1
2
quer zum Melder gehen
frontal zum Melder gehen
Unterkriechschutz
Walking across
Walking towards
15. PD4 -M-DALI/DSI-C – Connections
Unlocking device – Activation of the
programming mode
Locking device – Exit
programming mode
Resetting when
open: Deletes
all values set
with the remote
control, light
OFF.
Follow-up time light
Orientation lighting permanent
on/off
Automatic reading in the current
light value as new luminance
set point
Permanent protection against
sabotage
LED ashes
or Dimming of the lighting on the
desired luminance value
Adjusting of the luminance set point
+ / – small steps
+/ –big steps
1
min to 30
min
DSI/
DALI
Switching between DSI and
DALI program
or
+–
Fully automatic /semi automatic
mode => see page 2, point 11)
Preset/User mode
=> (see page 2, point 12)
max
50
Lux
1500
Lux
ON
OFF
Follow-up time orientation lighting
to
1
min
60
min
max
50
Lux
1500
Lux
ON
OFF
t < 5 sec.
optionaloptionaloptional
or
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
100 h burn-in function start/cancel
with a long button press
optional optional
or
LED ON/OFF (by holding
down the push button)
optional
10. Description of the key functions
Light on / off when closed
=> (see
point
13)
Start/cancel of the 100 h burn-in fuction in opened state to burn-in of
of the connected uorescent lamps with long button press
=> (
see
page 3, point 18)
Dimming in the closed state
Test operation in the closed condition to enable
Disable the test mode: press reset
Resetting when closed
The lighting relay is switched off, i.e. opened and the
follow-up times reset.
Permanent protection against sabotage
This function blocks the unit permanently (green LED is illuminated).
This operating mode can only be activated during the period of 5
seconds (LED flashes) after pressing the “lock“ button. This status will
only permit actuating the function “Light on/Light off”.
The procedure for leaving this mode is as follows:
1. Switch off the current
2. Apply current for 31 – 59 seconds
3. Switch of the current again
4. Apply current, wait for self test cycle
5. Open detector
Dim in the open state
To set a target value, proceed as follows (example workplace):Place
one lux meter flat on the desk. Set the light. With the help of remote
control IR-PD-DALI by pressing the buttons „max“ or „min“ as neces-
sary. Wait until the desired light level is reached.
Conrmation by the preset value
If necessary, gradually adjusting the brightness current set point.
Light during the initialization
The light is on by default in the initialization time.
On / off with the „Light“ button during Initialization. The final
condition is then active.
Adjustment of the orientation lighting in the open state
Note:
Also during the orientation phase of the light constant light control
is active: With sufficient brightness is < 20% dimmed and turned off the
lights if necessary.
max
50
Lux
1500
Lux
ON
OFF
t < 5 sec.
+–
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
1
min
60
min
14. Range of coverage
2,50 m
40 m
20 m
3 m
5 m
1
2
PD4-M-DALI/DSI-C
L
N
R
Slave
L LS N N –+R
T1 DA +
DA –
PD4-M-DALI/DSI-C-SM
T1
L
N
R
Slave
N SL
– +
R
T1
DA +
DA –
PD4-M-DALI/DSI-C-FC
16.
Wiring diagram
MAN 7123 – 150512–1
WE RECOMMEND THAT BEFORE DIMMING OF THE CONNECTED
LIGHTS A 100 hBURN IN (T5 TUBES OR 80 HOURS FOR T8 TUBES)
FUNCTION TAKES PLACE.
THE LIFESPAN OF THE LAMPS CAN BE REDUCED IF THE BURN IN
DOES NOT TAKE PLACE.
18. 100 h-function





 



 




   

 



Standard mode with Master-DALI occupancy detectors





 



 




   

 



Type SM FC FM
PD4-M-DALI/DSI-C-Master 92530 92328 –
PD4-Slave-C 92536 92444 92445
LUXOMAT®Remote control:
IR-PD-DALI (incl. wall bracket) 92094
Accessory:
BSK Ball basket guard 92199
Wall bracket for remote control as replacement
92100
SM-Socket IP54 92161
19. Article / Part nr. / Accessory
20. LED-Funktionsanzeigen
LED function indicators
Process Standard
mode Double-locked
Initialisation time
unprogrammed Red flashes Green
flashes
Initialisation time
programmed
Red flashes
quickly
Green flashes
quickly
Motion detection
Red flashes
on each
detected
movement
Green flashes
on each
detected
movement
Too bright detected
Red flashes
2x each
second
Green flashes
2x each
second
Too bright / too dark /
undefined in opened state
Red flashes
very quickly
Green flashes
very quickly
Switching DALI/DSI
DSI active
Red shines
3 sec.
Switching DALI/DSI
DALI active
Green shines
3 sec.
Switching HA/VA
VA active
Red shines
3 sec.
Switching HA/VA
HA active
Green shines
3 sec.
Switching Preset/User
Preset active
Red shines
3 sec.
Switching Preset/User
User active
Green shines
3 sec.
IR signal valid received Red shines
3 sec.
IR signal invalid received Red shines
0,5 sec.
100 h burn-in function
active
Red and
green flashes
alternate
Sensor and power supply in one case
Power supply: 230 V~ ±10 %
Power consumption: < 1W
Ambient temperature: -25°C to +50°C
Degree of protection/class:
IP20 (with accessory IP54) / II
Settings:
locally and by remote control
Light values - IR-PD-DALI:
50 - 1500 Lux
Parallel operation:
Master/Slave
Area of coverage:
circular 360°
Range of coverage Ø H 2,5 m / T = 18°C:
max. 40m (tangential)
Recommended height:
2 - 3 m
Light measurement:
Mixed light, daylight + artificial
light, suitably for constant light
control
Lux values-Potentiometer:
10 - 2000 Lux
• DALI/DSI
digital BUS control wire, 2-core, no polarity (broadcast only)
Max. no. of series-connected electronic ballasts: up to 50
Time-settings:
1 - 30min. / test
Dimensions H x Ø [mm]
SM FC FM
73 x 101 97 x 103 97 x 84
Visible part when built into ceiling
H x Ø [mm]
:34x103
Technical data PD4-Slave
Power supply: 230 V~ ±10 %
Impulse output: Optocoupler max. 2 W
Impulse pause: 2 sec. or 9 sec.
Dimensions
H x Ø [mm]
SM FC FM
73 x 101 97 x 103 97 x 84
Declaration of Conformity:
The product complies with the
low voltage recommendation 2006/95/EC and the EMV
recommendation 2004/108/EC.
17.
Technical data
PD4-M-DALI/DSI-C

This manual suits for next models

2

Other B.E.G. Security Sensor manuals

B.E.G. LUXOMAT BL2 User manual

B.E.G.

B.E.G. LUXOMAT BL2 User manual

B.E.G. LUXOMAT PD4-S Series User guide

B.E.G.

B.E.G. LUXOMAT PD4-S Series User guide

B.E.G. LUXOMAT Indoor 180-R User manual

B.E.G.

B.E.G. LUXOMAT Indoor 180-R User manual

B.E.G. LUXOMAT PD4-M-3C-TRIO Series User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-3C-TRIO Series User guide

B.E.G. LUXOMAT BL2 User manual

B.E.G.

B.E.G. LUXOMAT BL2 User manual

B.E.G. LUXOMAT PD4-M-1C-C-SM User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-1C-C-SM User guide

B.E.G. LUXOMAT PD4-M-2C-C Series User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-2C-C Series User guide

B.E.G. LUXOMAT net PD11-KNX-FLAT-ST User manual

B.E.G.

B.E.G. LUXOMAT net PD11-KNX-FLAT-ST User manual

B.E.G. LUXOMAT net PD4-M-DAA4G User guide

B.E.G.

B.E.G. LUXOMAT net PD4-M-DAA4G User guide

B.E.G. LUXOMAT PD4-M-2C-DUO User manual

B.E.G.

B.E.G. LUXOMAT PD4-M-2C-DUO User manual

B.E.G. LUXOMAT PD9-M-DIM User guide

B.E.G.

B.E.G. LUXOMAT PD9-M-DIM User guide

B.E.G. LUXOMAT PD2-M-1C User guide

B.E.G.

B.E.G. LUXOMAT PD2-M-1C User guide

B.E.G. LUXOMAT PD4-S Series User guide

B.E.G.

B.E.G. LUXOMAT PD4-S Series User guide

B.E.G. LUXOMAT net PD4N-LTMS-RR User guide

B.E.G.

B.E.G. LUXOMAT net PD4N-LTMS-RR User guide

B.E.G. LUXOMAT PD4-S Series User manual

B.E.G.

B.E.G. LUXOMAT PD4-S Series User manual

B.E.G. LUXOMAT PD4-M-1C-SM User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-1C-SM User guide

B.E.G. LUXOMAT PD2-M-2C User manual

B.E.G.

B.E.G. LUXOMAT PD2-M-2C User manual

B.E.G. LUXOMAT PD4-S-DAA4G User guide

B.E.G.

B.E.G. LUXOMAT PD4-S-DAA4G User guide

B.E.G. LUXOMAT PD2-M-DALI/DSI User guide

B.E.G.

B.E.G. LUXOMAT PD2-M-DALI/DSI User guide

B.E.G. LUXOMAT PD4-M-1C-GH-AP User manual

B.E.G.

B.E.G. LUXOMAT PD4-M-1C-GH-AP User manual

B.E.G. LUXOMAT PD4-M-DIM-Corridor User guide

B.E.G.

B.E.G. LUXOMAT PD4-M-DIM-Corridor User guide

B.E.G. LUXOMAT ALC-K-360 User guide

B.E.G.

B.E.G. LUXOMAT ALC-K-360 User guide

B.E.G. LUXOMAT PD9-M-DALI/DSI-FC User guide

B.E.G.

B.E.G. LUXOMAT PD9-M-DALI/DSI-FC User guide

B.E.G. LUXOMAT PD9-M-1C+HVAC User guide

B.E.G.

B.E.G. LUXOMAT PD9-M-1C+HVAC User guide

Popular Security Sensor manuals by other brands

Sekotech GCU-OCD15 operating manual

Sekotech

Sekotech GCU-OCD15 operating manual

yellow jacket AccuProbe 69320 Operation and maintenance manual

yellow jacket

yellow jacket AccuProbe 69320 Operation and maintenance manual

Agilent Technologies 85025A User's and service guide

Agilent Technologies

Agilent Technologies 85025A User's and service guide

SUTO S531 Instruction and operation manual

SUTO

SUTO S531 Instruction and operation manual

Eldat Easywave SM01 quick start guide

Eldat

Eldat Easywave SM01 quick start guide

Tractel Blocfor B10 AES Operating and maintenance instructions

Tractel

Tractel Blocfor B10 AES Operating and maintenance instructions

Nice LP21 quick start guide

Nice

Nice LP21 quick start guide

Evikon PluraSens E2638-CO2 user manual

Evikon

Evikon PluraSens E2638-CO2 user manual

WERTHER INTERNATIONAL OMA 547SPF manual

WERTHER INTERNATIONAL

WERTHER INTERNATIONAL OMA 547SPF manual

IME Milesight WS303 user guide

IME

IME Milesight WS303 user guide

Aritech ST400 Installation sheet

Aritech

Aritech ST400 Installation sheet

Dräger Flame 5000 Instructions for use

Dräger

Dräger Flame 5000 Instructions for use

DBI SALA EZ Stop User instruction manual

DBI SALA

DBI SALA EZ Stop User instruction manual

Forney IDD-II manual

Forney

Forney IDD-II manual

Acustek SWORD-24s Operational manual

Acustek

Acustek SWORD-24s Operational manual

RDT FloodMaster RS-094 manual

RDT

RDT FloodMaster RS-094 manual

ITALIANA SENSORI 8010-ISR007 Technical manual

ITALIANA SENSORI

ITALIANA SENSORI 8010-ISR007 Technical manual

Ekinex EK-SN2-TP-GAA Applications manual

Ekinex

Ekinex EK-SN2-TP-GAA Applications manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.