Bender COMTRAXX CP9 Series User manual

Kurzanleitung DE
Quick-start guide EN
CP9xx_D00349_09_Q_DEEN/01.2024
COMTRAXX® CP9xx – Control Panel
Melde- und Bedientableau für medizinische und andere Bereiche
Remote alarm indicator and operator panel for medical locations and other areas

2 CP9xx_D00349_09_Q_DEEN/01.2024
COMTRAXX® CP9xx – Control Panel
COMTRAXX®CP9xx
Remote alarm indicator and operator
Graphical interface for operation and monitoring of
medical and other technical installations.
This quick-start guide does not replace the manual!
Quick-start guide for the following devices
Scope of delivery
• CP9xx
• Safety instructions
• Quick-start guide DE/EN
For CP915 and CP924 additionally
• Connecting cable
• Ethernet-Keystone coupler
• USB cable
• RJ45 flat patch cable
Intended use
The device CP9xx is used wherever complex informa-
tion needs to be displayed easily and clearly for a user.
Due to its touch-sensitive surface, it can also be used as
a control option for installations.
Any other use than that described in this manual is re-
garded as improper.
Installation and connection
I Danger! Risk of fatal injury due to electric
shock!
Touching live parts of the system carries the risk of
electric shock. Before installing and connecting
the device, make sure that the installation has
been de-energised. Observe the rules for working
on electrical installations.
Manual
COMTRAXX®CP9xx
Melde- und Bedientableau
Grafikschnittstelle zur Bedienung und Überwachung
von medizinischen und anderen technischen Anlagen.
Diese Kurzanleitung ersetzt nicht das Handbuch!
Kurzanleitung für folgende Geräte
Typ/Type Display UsB x H x T /W x H x D Gewicht/
Weight Art.-Nr./Art.-No. Handbuch Nr.
Manual No.
CP907 7“ (17,6 cm) DC 24V , < 15 W; 226 x 144 x 78 mm 1.2 kg B95061080 (Front weiß/white)
D00349
CP915 15,6“ (38,6 cm) AC 100…240V, < 30 W 505 x 350 x 95 mm 6.1 kg B95061081 (Front weiß/white)
95061085 (Front grau/grey)
CP924 24“ (61,0 cm) AC 100…240 V, < 55W 654 x 441 x 100 mm 9.1 kg B95061183 (Front weiß/white)
B95061184 (Front grau/grey)
Lieferumfang
• CP9xx
• Sicherheitshinweise
• Kurzanleitung DE/EN
Für CP915 und CP924 zusätzlich
• Anschlusskabel
• Ethernet-Keystone Kuppler
• USB-Kabel
• RJ45- Patchkabel flach
Bestimmungsgemäße Verwendung
Das Gerät CP9xx findet überall Einsatz, wo komplexe
Informationen für einen Anwender einfach und über-
schaubar dargestellt werden sollen. Durch die berüh-
rungsempfindliche Fläche dient es auch als Steuerungs-
möglichkeit von Anlagen.
Eine andere oder darüber hinausgehende Benutzung
gilt als nicht bestimmungsgemäß.
Montage und Anschluss
I gefahr! Lebensgefahr durch Stromschlag!
Bei Berühren von unter Spannung stehender
Anlagenteile besteht die Gefahr eines elektrischen
Schlages. Stellen Sie vor Einbau des Gerätes und
vor Arbeiten an den Anschlüssen des Gerätes sicher,
dass die Anlage spannungsfrei ist. Beachten Sie die
Regeln für das Arbeiten an elektrischen Anlagen.
Handbuch

CP9xx_D00349_09_Q_DEEN/01.2024 3
COMTRAXX® CP9xx – Control Panel
I Caution!
Functional ground. The device must be earthed.
Without connection of the functional earth, the
device function is not guaranteed.
Electrostatic sensitive devices.
Observe precautions for handling electrostatic
sensitive devices.
Damage to components. Do not remove the de-
vice from the enclosure during ongoing operati-
on. First, disconnect the device from the supply
voltage and from the network (Ethernet).
Incorrect connector plugs. Connector plugs of
another devices may have a different polarity.
Please only use the supplied connector plug
(A1+/A/2-/PE).
Safe separation. The supply shall be properly se-
parated from hazardous voltages and meet the
limits of UL/CSA 61010-1, Clause 6.3.
Dimensions (mm)
Gerätemaße / Device dimensions ±1
Typ / Type a b c
CP907 226 144 176 (7”)
CP915 505 350 386 (15,6”)
CP924 654 441 610 (24”)
Einbaumaße / Installation dimensions ±1
Typ / Type a b Einbautiefe /
Installation depth
CP907 Unterputz/Flush-mounting 212 124 75
CP915 Unterputz/Flush-mounting 464 309 92
CP924 Unterputz/Flush-mounting 613 399 95
Gehäusemaße / Enclosure dimensions ±1
Typ / Type A B C
CP907 Unterputz/Flush-mounting 212 124 75
CP915 Unterputz/Flush-mounting 461 306 92
CP924 Unterputz/Flush-mounting 610 396 95
COMTRAXX®
a
cb
I VorsiCht!
Funktionserde. Das Gerät ist zwingend zu erden.
Ohne Anschluss der Funktionserde ist die Geräte-
funktion nicht gewährleistet.
Elektrostatisch gefährdete Bauelemente.
Beachten Sie die Vorsichtsmaßnahmen für den
Umgang mit elektrostatisch gefährdeten Geräten.
Beschädigung von Bauteilen.
Nehmen Sie das Gerät nicht im laufenden Betrieb
aus dem Gehäuse. Trennen Sie vorher das Gerät
von der Versorgungsspannung und vom Netz-
werk (Ethernet).
Falsche Anschlussstecker. Anschlussstecker an-
derer Geräts können eine abweichende Polung
aufweisen. Verwenden Sie nur den beigelegten
Anschlussstecker (A1+/A2–/PE).
Sichere Trennung. Die Stromversorgung muss
ordnungsgemäß von gefährlichen Spannungen
getrennt sein und die Grenzwerte der
UL/CSA 6101010-1, Klausel 6.3 erfüllen.
Abmessungen (mm)
A
B
C

4 CP9xx_D00349_09_Q_DEEN/01.2024
COMTRAXX® CP9xx – Control Panel
I Caution! Damage to the display front
Placing the suction lifter in the middle and pulling
only at this point may damage the front plate.
Always place the suction lifter on the edges of the
display.
Connections on the mainboard CP9xx
* The CP907 can also be supplied via Power-over-Ethernet (PoE).
In this case the PoE switch must be earthed.
i
Use at least 75 °C copper conductors for UL appli-
cations!
Use at least 80 °C copper conductors for PoE.
I Vorsicht! Beschädigung der Displayfront
Durch mittiges Aufsetzen des Saughebers und
Herausziehen der Frontplatte kann diese beschädigt
werden. Setzen Sie den Saugheber stets an den
Rändern des Displays an.
Anschlüsse an die Hauptplatine CP9xx
Steckbuchse für digitale Eingänge 1Connector for digital Inputs
I²C-Schnittstelle 2I²C-interface
Steckbuchse zur Energiespeicherplatine 3Connector to energy storage board
Spannungsversorgung A1/+, A2/–, PE 4Voltage supply A1/+, A2/–, PE
Ethernet (RJ45 PoE)*; HTTP; ModbusTCP, BCOM 5Ethernet (RJ45 PoE)*; HTTP; ModbusTCP, BCOM
X1-Stecker für Modbus RTU und BMS-Bus 6X1 plug for Modbus RTU and BMS-Bus
Terminierung von Modbus RTU und BMS-Bus 7Termination of Modbus RTU and BMS-Bus
USB-Anschlüsse (fürTouch Sensor) / CP907 nicht bestückt 8USB ports (for Touch Sensor) / CP907 unloaded
DVI-Eingang / CP907 nicht bestückt 9DVI-Port / CP907 unloaded
Audio Ausgang / CP907 nicht bestückt 10 Audio Output / CP907 unloaded
Audio Eingang/ nicht bestückt 11 Audio Inputs / CP907 unloaded
Anschluss Steuerrelais 12 Connection to control relay
* Die Versorgung des CP907 ist auch über Powerover-Ethernet möglich
(PoE). Hier muss zwingend der PoE-Switch geerdet sein.
i
Für UL-Anwendungen mind.
75°C-Kupferleitungen verwenden!
Für PoE mind. 80 °C-Kupferleitungen verwenden.
3
2
1
456
7
89
10 11
12

CP9xx_D00349_09_Q_DEEN/01.2024 5
COMTRAXX® CP9xx – Control Panel
Belegung X1-Stecker (7)
X1 plug connector (7)
Belegung digitale Eingänge (1)
Assignment of digital inputs (1)
Terminierung Modbus RTU und BMS-Bus (8)
Termination of Modbus RTU and BMS-bus (8)
Steuerrelais / Control relay (13)
SBMS
ABMS
BBMS
AMB BMB
SMB
SBMS
ABMS
BBMS
AMB BMB
SMB
1 2
3
4 5
6
7 8
9
10 11
12
LL
1 2
3
4 5
6
7 8
9
10 11
12
KK
Kx
Lx
N/O
Ky
Ly
N/C
x, y: 1...12
+24 V+24 V
0 V0 V
141211
Connection overview
Connections on the mainboard CP915 / CP924
Anschlussübersicht
Belegung der Steckanschlüsse
COMTRAXX®
1 2 12
...
11 12 14
Digital I/O
COMTRAXX®
Switch
+
–
~
LTE
Relais / Relay
USB
BMS-Bus
Modbus RTU
Ethernet
Ethernet (1:1)
US

6 CP9xx_D00349_09_Q_DEEN/01.2024
COMTRAXX® CP9xx – Control Panel
Commissioning
Required information before commissioning:
• DHCP server available for CP9xx and other
BCOM devices?
• Fixed IP addresses for Modbus devices
(e.g. IOM750-xxx)
• Subnet mask
• IP address of the standard gateway
• IP address of the DNS server
If a DHCP server is available in the network, the device
address can be assigned automatically.
Initial commissioning of screen
Entering a manual address:
• Switch on the supply voltage
• Enter the desired IP address for the CP9xx
• Enter the subnet mask of the LAN
• Enter the gateway address of the LAN
• Press the “Save” button to store the entries
• Wait 8…10 seconds
Activating address reception via a DHCP server
• Activate “DCHP?” checkbox
• Press the “Save” button to store the entries
• Wait 8…10 seconds
Login to the device
From a local network LAN
• Open a browser on a device (computer/laptop)
that is integrated into the network
• Enter the address indicated in line 1 of the CP9xx
into the address field of the browser
From a peer to peer network (1:1 connection)
It is possible to connect the CP9xx directly to a comput-
er/laptop. In this case, the CP9xx can be controlled with
a second fixed IP address.
• Open browser on the connected device
• Enter the following address into the address line
of the browser: 169.254.0.1
Inbetriebnahme
Benötigte Informationen vor einer Inbetriebnahme:
• DHCP-Server verfügbar für CP9xx und andere
BCOM- Geräte?
• Feste IP-Adressen für Modbus-Geräte
(z. B. IOM750-xxx)
• Subnetz-Maske
• IP-Adresse vom Standard-Gateway
• IP-Adresse vom DNS-Server
Ist ein DHCP-Server im Netzwerk vorhanden, kann die
Adressierung des Geräts automatisch vorgenommen
werden.
Bildschirm Erstinbetriebnahme
Eingabe einer manuellen Adresse:
• Spannungsversorgung einschalten
• IP-Adresse für das CP9xx eingeben
• Subnetzmaske des LAN eingeben
• Gatewayadresse des LAN eingeben
• Eingaben speichern mit der „Save“-Taste
• Warten Sie 8…10 Sekunden
Aktivierung des Adressempfangs von einem
DHCP-Server
• Aktivieren Sie „DHCP?“
• Eingaben speichern mit der „Save“-Taste
• Warten Sie 8…10 Sekunden
Anmeldung am Gerät
Aus einem lokalen Netzwerk LAN
• Öffnen Sie einen Browser auf einem im Netzwerk
eingebundenen Gerät (Computer/Laptop)
• Geben Sie im Adressfeld des Browsers die Adresse
der 1. Zeile des CP9xx ein
Mittels direkt verbundenem PC (1:1-Verbindung)
Es ist möglich, das CP9xx direkt mit einem Computer/
Laptop zu verbinden. In diesem Falle lässt sich das
CP9xx über eine zweite feste IP-Adresse ansteuern.
• Browser auf verbundenem Gerät öffnen
• Geben Sie in der Adresszeile des Browsers folgen-
de Adresse ein: 169.254.0.1

CP9xx_D00349_09_Q_DEEN/01.2024 7
COMTRAXX® CP9xx – Control Panel
COMTRAXX® Start screen
Technical data
CP907
Display.......................................................................................7” (176 mm)
Front.....................................................................................glass, tempered
Supply voltage via A1/+; A2/-......................................... DC 24 V SELV/PELV
Supply via PoE
PoE standard ...................................................................... IEEE 802.3at
Nominal voltage ..........................................................DC 48 V, < 15 W
Max. cable length via AWG 26/7; 0.14 mm² ................................100 m
Dimensions......................................................................226 x 144 x 78 mm
Weight................................................................................................. 1.1 kg
CP915
Display.....................................................................................15” (386 mm)
Front................................................................. glass, tempered, white/grey
Supply voltage.......................................................AC 100…240 V / < 30 W
Dimensions......................................................................505 x 350 x 92 mm
Weight................................................................................................. 6.1 kg
CP924
Display.....................................................................................24” (610 mm)
Front................................................................. glass, tempered, white/grey
Supply voltage.......................................................AC 100…240 V / < 55 W
Dimensions....................................................................654 x 441 x 100 mm
Weight................................................................................................. 9.1 kg
COMTRAXX® Startbildschirm
TOOLS
ALARMS
BUS OVERVIEW
HOME
EN
System OK
DeviceName
1207990020-Bxxxxxxxx
Comtraxx CP900 V4.x
Device info
CP900
COMTRAXX®
DeviceName
20.12.2020 13:30 (+01:00)
Technische Daten
CP907
Display.......................................................................................7“ (176 mm)
Front........................................................................................Glas, gehärtet
Versorgung über A1/+; A2/- ........................................... DC 24 V SELV/PELV
Versorgung über PoE
PoE Norm............................................................................ IEEE 802.3at
Nennspannung.............................................................DC 48 V, < 15 W
Max. Leitungslänge bei AWG 26/7; 0,14 mm² .............................100 m
Maße................................................................................226 x 144 x 78 mm
Gewicht................................................................................................ 1,1 kg
CP915
Display.....................................................................................15“ (386 mm)
Front..................................................................... Glas, gehärtet, weiß/grau
Versorgungsspannung...........................................AC 100…240 V / < 30 W
Maße................................................................................505 x 350 x 92 mm
Gewicht................................................................................................ 6,1 kg
CP924
Display.....................................................................................24“ (610 mm)
Front..................................................................... Glas, gehärtet, weiß/grau
Versorgungsspannung...........................................AC 100…240 V / < 55 W
Maße..............................................................................654 x 441 x 100 mm
Gewicht................................................................................................ 9,1 kg

Bender GmbH & Co. KG
Londorfer Straße 65
35305 Grünberg
Germany
Tel.: +49 6401 807-0
info@bender.de
www.bender.de
© Bender GmbH & Co. KG, Germany
Subject to change! The specied
standards take into account the edition
valid until 01/2024 unless otherwise
indicated.
Alle Rechte vorbehalten.
Nachdruck und Vervielfältigung nur mit
Genehmigung des Herausgebers.
All rights reserved.
Reprinting and duplicating only with
permission of the publisher.
EU Declaration of Conformity
The full text of the EU Declaration of Conformity
is available via the QR Code:
Other Order numbers
Spare parts
EU-Konformitätserklärung
Der vollständige Text der EU-Konformitätser-
klärung ist über den QR-Code verfügbar:
Weitere Bestellnummern
Ersatzteile
Gerät/Device Zubehör/ Accessories Art.-Nr./ Art.-No.
CP907 Unterputzgehäuse/Flush-mounting enclosure B95100140
CP915
Displayeinheit, weiß/Displayunit, white B95061090
Displayeinheit, grau/Displayunit, grey B95061110
Unterputzgehäuse incl. Montageplatte mit Elektronik/
Flush-mounting enclosure with mounting plate and electronics B95061092
CP924
Displayeinheit, weiß/Displayunit, white B95061111
Displayeinheit, grau/Displayunit, grey B95061097
Unterputzgehäuse incl. Montageplatte mit Elektronik/
Flush-mounting enclosure with mounting plate and electronics B95061099
alle/All CP9xx Ersatz-Steckerkit/CP9xx replacement plug connector kit B95061910
CP915
CP924 CP9xx Saugheber/CP9xx vacuum lifter B95061911
nur/only CP907
B95100140
Other manuals for COMTRAXX CP9 Series
8
This manual suits for next models
3
Table of contents
Other Bender Control Panel manuals

Bender
Bender COMTRAXX CP9 Series User manual

Bender
Bender COMTRAXX CP9 Series User manual

Bender
Bender FP200 User manual

Bender
Bender TM800 User manual

Bender
Bender COMTRAXX CP305 User manual

Bender
Bender COMTRAXX CP9 Series User manual

Bender
Bender TMX-HA User manual

Bender
Bender COMTRAXX CP305 User manual

Bender
Bender COMTRAXX CP9 Series User manual

Bender
Bender COMTRAXX CP9 Series User manual