Pilz PNOZ pe2p User manual

PNOZ pe2p
Operating Manual 21035-EN-03
}Safety relays

Preface
This document is a translation of the original document.
All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made
for internal purposes. Suggestions and comments for improving this documentation will be
gratefully received.
Source code from third-party manufacturers or open source software has been used for
some components. The relevant licence information is available on the Internet on the Pilz
homepage.
Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®,
SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks
of Pilz GmbH & Co. KG in some countries.
SD means Secure Digital

Contents
Operating Manual PNOZ pe2p
21035-EN-03 3
Introduction 4
Validity of documentation 4
Using the documentation 4
Definition of symbols 4
Safety 5
Intended use 5
Safety regulations 6
Use of qualified personnel 6
Warranty and liability 6
Disposal 6
Unit features 7
Block diagram/terminal configuration 7
Function Description 7
Operating modes 7
Installation 8
Wiring 9
Preparing for operation 9
Operation 9
Signal statuses of the inputs and outputs 9
Technical details 10
Order reference 11
EC declaration of conformity 11

PNOZ pe2p
Operating Manual PNOZ pe2p
21035-EN-03 4
Introduction
Validity of documentation
This documentation is valid for the product PNOZ pe2p. It is valid until new documentation
is published.
This operating manual explains the function and operation, describes the installation and
provides guidelines on how to connect the product.
Using the documentation
This document is intended for instruction. Only install and commission the product if you
have read and understood this document. The document should be retained for future ref-
erence.
Definition of symbols
Information that is particularly important is identified as follows:
DANGER!
This warning must be heeded! It warns of a hazardous situation that poses
an immediate threat of serious injury and death and indicates preventive
measures that can be taken.
WARNING!
This warning must be heeded! It warns of a hazardous situation that could
lead to serious injury and death and indicates preventive measures that can
be taken.
CAUTION!
This refers to a hazard that can lead to a less serious or minor injury plus
material damage, and also provides information on preventive measures
that can be taken.
NOTICE
This describes a situation in which the product or devices could be dam-
aged and also provides information on preventive measures that can be
taken. It also highlights areas within the text that are of particular import-
ance.

PNOZ pe2p
Operating Manual PNOZ pe2p
21035-EN-03 5
INFORMATION
This gives advice on applications and provides information on special fea-
tures.
Safety
Intended use
The PNOZ pe2p bus interface, together with an expansion module of the PNOZpower mod-
ular safety system, are used for the safety-related interruption of a safety circuit.
The bus interface consists of a
}Coupling plug with screw terminals for connecting to a master controller
}Terminator for terminating the PNOZpower bus
It is actuated by
}PNOZmulti range units,
}PSS range output modules,
}PNOZelog range units.
The bus interface may only be used in conjunction with units that evaluate a feedback loop.
The following is deemed improper use in particular:
}Any component, technical or electrical modification to the product
}Use of the product outside the areas described in this manual
}Use of the product outside the technical details (see Technical details [ 10]).
NOTICE
EMC-compliant electrical installation
The product is designed for use in an industrial environment. The product
may cause interference if installed in other environments. If installed in other
environments, measures should be taken to comply with the applicable
standards and directives for the respective installation site with regard to in-
terference.

PNOZ pe2p
Operating Manual PNOZ pe2p
21035-EN-03 6
Safety regulations
Use of qualified personnel
The products may only be assembled, installed, programmed, commissioned, operated,
maintained and decommissioned by competent persons.
A competent person is someone who, because of their training, experience and current pro-
fessional activity, has the specialist knowledge required to test, assess and operate the
work equipment, devices, systems, plant and machinery in accordance with the general
standards and guidelines for safety technology.
It is the company’s responsibility only to employ personnel who:
}Are familiar with the basic regulations concerning health and safety / accident preven-
tion
}Have read and understood the information provided in this description under "Safety"
}And have a good knowledge of the generic and specialist standards applicable to the
specific application.
Warranty and liability
All claims to warranty and liability will be rendered invalid if
}The product was used contrary to the purpose for which it is intended
}Damage can be attributed to not having followed the guidelines in the manual
}Operating personnel are not suitably qualified
}Any type of modification has been made (e.g. exchanging components on the PCB
boards, soldering work etc.).
Disposal
}When decommissioning, please comply with local regulations regarding the disposal of
electronic devices (e.g. Electrical and Electronic Equipment Act).

PNOZ pe2p
Operating Manual PNOZ pe2p
21035-EN-03 7
Unit features
}Actuated via safety contacts or safe semiconductor outputs
}Expansion module control output via PNOZpower bus
}Max. 6 expansion modules can be connected via jumpers
}Plug-in connection terminals
Block diagram/terminal configuration
PNOZpower-BUS
A1
Y1
Y2
A2
K1
Function Description
The bus interface PNOZ pe2p, in conjunction with the expansion modules, is used to ex-
pand a safety circuit. It is driven from a master controller (e.g. safe outputs on a PSS).
The unit is ready for operation when when supply voltage is applied and the feedback loop
Y1-Y2 is closed
}24 V DC are available at the terminal K1 (e.g. the PSS output has a high signal):
– At the expansion module control output connected to the PNOZpower bus there is a
high signal.
}0 V DC are available at the terminal K1 (e.g. the PSS output has a low signal):
– At the expansion module control output connected to the PNOZpower bus there is a
low signal.
NOTICE
When controlling an expansion module via the den PNOZpower bus the
switch-on delay/delay-on de-energisation of the controlling device and the
expansion module are added together.
Operating modes
}Single-channel operation: no redundancy in the input circuit, earth faults in the start cir-
cuit are detected depending on the master controller.

PNOZ pe2p
Operating Manual PNOZ pe2p
21035-EN-03 8
Installation
}The unit should be installed in a control cabinet with a protection type of at least IP54.
}Connect the bus interface to the first expansion module via the coupling connector.
NOTICE
Always fit a terminator to the first and last device.
}Only use terminators, jumpers and terminals of the modular safety system PNOZpower.
}Layout:
– The PNOZ pe2p is installed on the left of the first expansion module.
}Maximum hardware:
– 1 bus interface
– 6 expansion modules
Expansion module 1 Expansion module 2 Expansion module 6
95579
Terminator
Order no. 779120
95425
Jumper
Order no. 774639
779125
PNOZ pe2p
Coupling connector with
screw terminals
WARNING!
Risk of electrocution!
When voltage is applied, contact with live components could result in seri-
ous or even fatal injury from an electric shock.
The plug-in connection terminals should only be connected and disconnec-
ted when the voltage is switched off.

PNOZ pe2p
Operating Manual PNOZ pe2p
21035-EN-03 9
Wiring
Please note:
}Information given in the "Technical details [ 10]" must be followed.
}Max. cable runs Imax at the input circuit and feedback loop: Short circuits and earth faults
are detected by the master controller. The maximum cable runs is therefore dependent
on the master controller.
}Use copper wire that can withstand 60/75°C.
}Ensure the EMC requirements of IEC 60204-1 are met.
}The bus interface and input circuits of the safety control system/ the safety relay must
always be supplied by a single power supply.
}The power supply must comply with the regulations for extra low voltages with protect-
ive electrical separation (SELV, PELV) in accordance with VDE 0100, Part 410.
Preparing for operation
Supply voltage AC DC
A1
A2
L+
L-
Connection
Control via safety system
(PNOZmulti, PSS) or safety relay
(PNOZelog)
K1Output 24 V DC
Input 24 V DC
A2
Y2
Y1
A1
24 V DC
0 V
PNOZpower-Bus
Operation
NOTICE
The safety function should be checked after initial commissioning and each
time the plant/machine is changed. The safety functions may only be
checked by qualified personnel.
Signal statuses of the inputs and outputs
}K1: PNOZpower input circuit
– "1" signal (+24 VDC): Expansion modules are actuated

PNOZ pe2p
Operating Manual PNOZ pe2p
21035-EN-03 10
– "0" signal (0 V): Expansion modules are not actuated
}Y2: Feedback loop output
– "1" signal (+24 VDC): Safety contacts of the expansion modules open
– "0" signal (0 V): Safety contacts of the expansion modules closed
Technical details
General
Approvals CCC, CE, EAC (Eurasian), TÜV, cULus Listed
Electrical data
Supply voltage
Voltage 24 V
Kind DC
Voltage tolerance -15 %/+10 %
Residual ripple DC 160 %
Duty cycle 100 %
Inputs
Number 1
Voltage at
Input circuit DC 24 V
Feedback loop DC 24 V
Current at
Input circuit DC 30 mA
Feedback loop DC 1 A
Environmental data
Climatic suitability EN 60068-2-78
Ambient temperature
Temperature range -10 - 55 °C
Storage temperature
Temperature range -25 - 70 °C
Climatic suitability
Humidity 93 % r. h. at 40 °C
Condensation during operation Not permitted
EMC EN 60947-5-1, EN 61000-6-2, EN 61326-3-1
Vibration
In accordance with the standard EN 60068-2-6
Frequency 10 - 55 Hz
Amplitude 0,35 mm
Airgap creepage
In accordance with the standard EN 60947-1
Overvoltage category III
Pollution degree 2
Rated insulation voltage 30 V
Rated impulse withstand voltage 0,8 kV

PNOZ pe2p
Operating Manual PNOZ pe2p
21035-EN-03 11
Environmental data
Protection type
Mounting area (e.g. control cabinet) IP54
Housing IP00
Terminals IP20
Mechanical data
Mounting position Horizontal on top hat rail
Connection type Screw terminal
Mounting type Fixed
Conductor cross section with screw terminals
1 core flexible 0,5 - 1,5 mm², 28 - 14 AWG
2 core with the same cross section, flexible with
crimp connectors, no plastic sleeve 0,5 - 1,5 mm², 28 - 14 AWG
2 core with the same cross section, flexible without
crimp connectors or with TWIN crimp connectors 0,5 - 1,5 mm², 28 - 14 AWG
Torque setting with screw terminals 0,25 Nm
Dimensions
Height 29 mm
Width 23,5 mm
Depth 22,5 mm
Weight 15 g
Where standards are undated, the 2014-07 latest editions shall apply.
Order reference
Product type Features Connection type Order No.
PNOZ pe2p 24 VDC Screw terminals 779 125
EC declaration of conformity
This product/these products meet the requirements of the directive 2006/42/EC for ma-
chinery of the European Parliament and of the Council. The complete EC Declaration of
Conformity is available on the Internet at www.pilz.com/support/downloads.
Representative: Norbert Fröhlich, Pilz GmbH & Co. KG, Felix-Wankel-Str. 2, 73760 Ost-
fildern, Germany

The Best of
German
Engineering
Partner of:
Support
Technical support is available from Pilz round the clock.
Americas
Brazil
+55 11 97569-2804
Canada
+1 888-315-PILZ (315-7459)
Mexico
+52 55 5572 1300
USA (toll-free)
+1 877-PILZUSA (745-9872)
Asia
China
+86 21 60880878-216
Japan
+81 45 471-2281
South Korea
+82 31 450 0680
Australia
+61 3 95446300
Europe
Austria
+43 1 7986263-0
Belgium, Luxembourg
+32 9 3217575
France
+33 3 88104000
Germany
+49 711 3409-444
Ireland
+353 21 4804983
Italy
+39 0362 1826711
Scandinavia
+45 74436332
Spain
+34 938497433
Switzerland
+41 62 88979-30
The Netherlands
+31 347 320477
Turkey
+90 216 5775552
United Kingdom
+44 1536 462203
You can reach our
international hotline on:
+49 711 3409-444
CMSE®, InduraNET p®, PAS4000®, PAScal®, PASconfig®, Pilz®, PIT®, PLID®, PMCprimo®, PMCprotego®, PMCtendo®, PMD®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®,
SafetyEYE®, SafetyNET p®, THE SPIRIT OF SAFETY®are registered and protected trademarks of Pilz GmbH & Co. KG in some countries. We would point out that product features may vary
from the details stated in this document, depending on the status at the time of publication and the scope of the equipment. We accept no responsibility for the validity, accuracy
and entirety of the text and graphics presented in this information. Please contact our Technical Support if you have any questions.
Pilz develops environmentally-friendly products using
ecological materials and energy-saving technologies.
Oces and production facilities are ecologically designed,
environmentally-aware and energy-saving. So Pilz oers
sustainability, plus the security of using energy-ecient
products and environmentally-friendly solutions.
Pilz GmbH & Co. KG
Felix-Wankel-Straße 2
73760 Ostfildern, Germany
Tel.: +49 711 3409-0
Fax: +49 711 3409-133
www.pilz.com
100XXXX-DE-0X
0-0-1-3-000, 2015-00 Printed in Germany
© Pilz GmbH & Co. KG, 2015
21035-EN-03, 2016-03 Printed in Germany
© Pilz GmbH & Co. KG, 2015
Back cover
Table of contents
Other Pilz Relay manuals
Popular Relay manuals by other brands

Chenzhu
Chenzhu CZ3055 user manual

Microelettrica Scientifica
Microelettrica Scientifica MC2-30V Operation manual

GE
GE 750 Guide

Schweitzer Engineering Laboratories
Schweitzer Engineering Laboratories SEL-351-5 instruction manual

DAITEM
DAITEM SH701AX installation manual

AJAX Systems
AJAX Systems Relay user manual