
For more information, contact your local Carrier Controls Expert
©2023 Carrier. All Rights Reserved. Cat. No. 11-808-989-01
_ag‘ f[‘ X
1. Mount the Differential Pressure Sensor
using two #8-1.5” self-tapping screws as shown in
Figure 1. The transmitter is factory-calibrated and must be installed vertically with the air
inlet nozzles pointing perpendicular to the duct. To adjust the zero, both pressure ports
must be open to the atmosphere.
Figure 1
2. Mount the air pick-up pipe to the air inlet nozzles provided on the DPS. To fix the pipe,
push one end of the flexible pipe till the edge butts out to the back of the nozzle and the
other end to the crossflow tubes or pitot’s installed. See Figure 2.
Figure 2
i [d[‘ X
1. Turn off the power. Connect one end of the Sensor bus cable to one end of the RTS port
on the Smart Node and the other end to the IN port of the DPS as shown in Figure 3.
•Failure to wire devices with the correct polarity when using a shared transformer may
result in damage to any device powered by the shared transformer.
•Do NOT mount the tubing so that the inside or the outside tube ends are in direct line
of a breeze or draft.
•Turn off the power before wiring. Never connect or disconnect the wiring with the
power turned on. Do NOT allow live wires to touch the circuit boards.
•Install in accordance with all state and local codes.