Carrier SPS User manual

C
Ca
ar
rr
ri
ie
er
r
S
Se
en
ns
so
or
rs
s
I
In
ns
st
ta
al
ll
la
at
ti
io
on
n
G
Gu
ui
id
de
e
CARRIER CORPORATION ©2009
A member of the United Technologies Corporation family · Stock symbol UTX · Catalog No. 11-808-423-01 · 7/6/2009


Carrier Sensors i
Table of Contents
Introduction to Carrier sensors................................................................................................................................... 1
SPT sensors.................................................................................................................................................................. 3
SPT sensor specifications....................................................................................................................................4
Rnet Configuration ...............................................................................................................................................5
To address an SPT Standard sensor..................................................................................................................5
Rnet wiring specifications ...................................................................................................................................5
Mounting location.................................................................................................................................................6
To wire and mount the SPT sensor ....................................................................................................................6
Using an SPT sensor.............................................................................................................................................8
To change sensor properties...............................................................................................................................9
To communicate through the sensor's Local Access port........................................................................... 10
Troubleshooting SPT sensors........................................................................................................................... 10
Alternate space temperature sensor .......................................................................................................................11
Sensor specifications ........................................................................................................................................ 12
Wiring specifications......................................................................................................................................... 12
Mounting location.............................................................................................................................................. 13
To wire and mount the sensor ......................................................................................................................... 13
To change a T59 sensor's options................................................................................................................... 14
Supply Air Temperature sensor ................................................................................................................................17
SAT sensor specifications................................................................................................................................. 17
Wiring specifications......................................................................................................................................... 18
Mounting location.............................................................................................................................................. 19
To wire and mount the SAT sensor ................................................................................................................. 19
Duct Air Temperature sensor....................................................................................................................................20
DAT sensor specifications ................................................................................................................................ 20
Wiring specifications......................................................................................................................................... 21
Mounting location.............................................................................................................................................. 21
To wire and mount the DAT sensor................................................................................................................. 22
Outdoor Air Temperature sensor..............................................................................................................................23
OAT sensor specifications ................................................................................................................................ 23
Wiring specifications......................................................................................................................................... 24
Mounting location.............................................................................................................................................. 24
To wire and mount the OAT sensor................................................................................................................. 25
Primary Air Temperature sensor ..............................................................................................................................26
PAT sensor specifications................................................................................................................................. 26
Wiring specifications......................................................................................................................................... 27
Mounting location.............................................................................................................................................. 27
To wire and mount the PAT sensor................................................................................................................. 28
CO2 sensor.................................................................................................................................................................29
CO2 sensor specifications ................................................................................................................................ 30
Wiring specifications......................................................................................................................................... 30
Mounting location.............................................................................................................................................. 31
To wire and wall-mount the CO2 sensor ........................................................................................................ 31
To wire and duct-mount the sensor ................................................................................................................ 32
CO2/Temperature sensor .........................................................................................................................................33
CO2/Temperature sensor specifications ....................................................................................................... 34
Wiring specifications......................................................................................................................................... 34
Mounting location.............................................................................................................................................. 35
To wire and mount the CO2/Temperature sensor ....................................................................................... 35

Table of Contents
ii Carrier Sensors
Relative Humidity sensors ........................................................................................................................................37
Sensor specifications ........................................................................................................................................ 38
Wiring specifications......................................................................................................................................... 38
Mounting location.............................................................................................................................................. 39
To wire and mount the Space RH sensors..................................................................................................... 40
Typical power wiring diagrams for Space RH sensors ......................................................................42
To wire and mount the Duct RH sensor ......................................................................................................... 43
To wire and mount the Outdoor RH sensor ................................................................................................... 44
Typical power wiring diagrams for Duct RH and Outdoor RH sensors .............................................46
Calibrating and troubleshooting relative humidity sensors ........................................................................ 47
Troubleshooting the RH sensor ..........................................................................................................47
Using SW2 DIP switches to calibrate and troubleshoot....................................................................47
RH conversion formulas......................................................................................................................48
Enthalpy switch/receiver and Enthalpy sensor.......................................................................................................49
Enthalpy switch/sensor specifications........................................................................................................... 50
Wiring specifications......................................................................................................................................... 50
Mounting location.............................................................................................................................................. 50
To wire and mount the switch/sensor............................................................................................................ 51
Appendix: i-Vu System Wiring Specifications and Recommended Vendors........................................................53
Index ...........................................................................................................................................................................55

Carrier Sensors 1
The following Carrier sensors can be used with the specified Open controllers.
Controller
Sensor
Part number
VVT Zone
VVT Bypass
RTU Open
WSHP Open
UC Open
UC Open XP
Space temperature sensor (page 3) SPS
SPPL
SPP
SPPF
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Alternate space temperature sensor (page 11) 33ZCT55SPT
33ZCT56SPT
33ZCT59SPT
••
•
•
•
•
•
•
•
•
•
•
•
Supply Air Temperature sensor (page 17) 33ZCSENSAT
•
•••••
Duct Air Temperature sensor (page 20) 33ZCSENDAT
•
•••••
Outdoor Air Temperature sensor (page 23) 33ZCSENOAT ••••
Primary Air Temperature sensor (page 26) 33ZCSENPAT ••
CO2sensor (page 29) 33ZCSENCO2 •••••
CO2/Temperature sensor (page 33) 33ZCT55CO2
33ZCT56CO2
••
•
•
•
•
•
•
•
Wall Relative Humidity sensor OPNSENSRH-01
33ZCSENSRH-01
••
•
•
•
•
•
•
•
Duct Relative Humidity sensor 33ZCSENDRH-01 •••
Outdoor Relative Humidity sensor 33ZCSENORH-01 •••
Enthalpy switch/receiver (page 49)
Enthalpy sensor (page 49)
33CSENTHSW
3CSENTSEN
•
•
•
•
•
•
Disconnect electrical power to the controller or sensor before wiring it. Failure to follow this warning could
cause electrical shock, personal injury, or damage to the device.
Introduction to Carrier sensors

Introduction to Carrier sensors
2 Carrier Sensors
•Do not run sensor or relay wires in the same conduit or raceway with Class 1 AC or DC service wiring.
•Do not abrade, cut, or nick the outer jacket of the cable.
•Do not pull or draw cable with a force that may harm the physical or electrical properties.
•Avoid splices in any control wiring.

SPT sensors
Carrier Sensors 3
Part #SPS, SPPL, SPP, SPPF
An SPT sensor is a thermistor-based, wall-mounted temperature sensor that monitors zone temperature. An
SPT sensor is wired to a controller's Rnet port.
Carrier offers the following SPT sensors:
Sensor
Features
SPT Standard
Part #SPS
•Local access port
•No operator control
SPT Plus
Part #SPPL
•Slide potentiometer to adjust setpoint
•MANUAL ON button to override schedule
•LED to show occupied status
•Local access port
SPT sensors

SPT sensors
4 Carrier Sensors
Sensor
Features
SPT Pro
Part #SPP
•LCD display
•MANUAL ON button to override schedule
•WARMER and COOLER buttons to adjust
setpoint
•INFO button to cycle through zone and
outside air temperatures, setpoints, and
local override time
•Local access port
SPT Pro Plus
Part #SPPF
(Used with Water Source Heat Pump only)
•LCD display
•MANUAL ON button to override schedule
•WARMER and COOLER buttons to adjust
setpoint
•INFO button to cycle through zone and
outside air temperatures, setpoints, and
local override time, plus 4 additional inputs
that can be defined in EIKON LogicBuilder
•MODE button to cycle through custom
programmed modes
•FAN SPEED button to adjust fan speed
•Local access port
SPT sensor specifications
Sensor tolerance Precision Thermistor. Standard accuracy ±0.45°F (0.25°C). Less than
±0.18°F (0.1°C) drift over a 10 year period.
Power Supplied by the 4-conductor cable (+12 Vdc @ 250 mA) from the controller.
Communication 115 kbps
Local access port For local access to start up and troubleshoot system
Environmental operating
range
32–122°F (0–50°C), 10–90% relative humidity, non-condensing
Mounting Standard 4x2-in. electrical box using provided 6-32 by 1/2 in. mounting
screws.

SPT sensors
Carrier Sensors 5
Overall dimensions: Width:
Height:
Depth:
2 3/4 in. (6.9 cm)
4 3/4 in. (12.1 cm)
5/8 in. (1.6 cm)
Rnet Configuration
You wire SPT sensors to a controller's Rnet port. An Rnet can consist of any of the following combinations of
devices wired in a daisy-chain or hybrid configuration:
•1 SPT Plus, SPT Pro, or SPT Pro Plus
•1–4 SPT Standards
•1–4 SPT Standards, and 1 SPT Plus SPT Pro, or SPT Pro Plus
•Any of the above combinations, plus up to 2 BACview6's but no more than 6 devices total
NOTE You must set addresses only on the following Rnet devices:
•SPT Standard sensors if you have more than one on the Rnet. See To address an SPT Standard sensor
(page 5).
•BACview6's if you have two on the Rnet. See the BACview Installation and User Guide.
To address an SPT Standard sensor
If the Rnet has multiple SPT Standard sensors, the first sensor retains its default address of 1. You must give
each additional SPT Standard a unique address on the Rnet. To set the address:
1 Pull the back plate off the sensor, pulling from the bottom first.
2 Remove the two hexagonal screws that attach the circuit board to the cover plate.
3 Remove the cover plate.
4 On the circuit board, set the address jumper to 2, 3, or 4.
5 Attach the circuit board to the cover plate with the hexagonal screws.
Rnet wiring specifications
NOTE Use the specified type of wire and cable for maximum signal integrity.
Description 4 conductor, unshielded, CMP, plenum rated cable
Conductor 18 AWG
Maximum length 500 feet (152 meters)
Recommended coloring Jacket: White
Wiring: Black, white, green, red
UL temperature rating 32–167°F (0–75°C)

SPT sensors
6 Carrier Sensors
Voltage 300 Vac, power limited
Listing UL: NEC CL2P, or better
Mounting location
Mount the sensor:
•In an area representing the average temperature in the space
•On an interior wall
•Approximately 5 feet (1.5 meters) from the floor, or as required by local code
•At least 4 feet (1.2 meters) from any corner
•At least 2 feet (.6 meter) from an open doorway
Do not mount the sensor:
•In drafty locations such as near air conditioning or heating ducts, or near open windows
•Over heat sources such as baseboard heaters, radiators, directly above wall-mounted lighting dimmers,
or in direct sunlight
NOTE The sensor mounting plate accommodates the NEMA standard 4x2-in. electrical box. However, the
sensor can be mounted directly on the wall surface if local codes permit.
To wire and mount the SPT sensor
NOTE The sensor mounting plate accommodates the NEMA standard 4x2-in. electrical box. However, the
sensor can be mounted directly on the wall surface if local codes permit.
1 Remove the mounting plate from the SPT sensor. You may need to turn the setscrew in the bottom of the
sensor clockwise until you can remove the mounting plate.
2 Pull the Rnet communication cable through the wire guide in the mounting plate.
3.30 in.
(8.38 cm)
3 Use the 2 mounting screws provided to attach the mounting plate to the wall or electrical box.

SPT sensors
Carrier Sensors 7
4 Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick the inner insulation.
Strip about .25 inch (.6 cm) of the inner insulation from each wire.
Outer Jacket
Inner insulation
.25 in.
(.6 cm)
5 If wiring 1 cable to the SPT sensor, cut the shield wire off at the outer jacket, then wrap the cable with
tape at the outer jacket to cover the end of the shield wire.
If wiring 2 cables in a daisy-chain configuration, twist together the shield wires, then wrap the shield
wires with tape.
6 Insert the other 4 wires into the sensor's screw terminal connector. If wiring 2 cables, insert like-colored
wires into each terminal.
Carrier recommends that you use the
following Rnet wiring scheme:
Connect this
wire...
Red
Black
White
Green
To this terminal...
+12V
Rnet-
Rnet+
Gnd
CAUTION Allow no more than .06 inch (1.5 mm) bare communication wire to protrude. If bare
communication wire contacts the cable's foil shield, shield wire, or a metal surface other than the
terminal block, the sensor may not communicate correctly.
7 Attach the sensor's cover and circuit board to the mounting plate, inserting the top first.
8 Turn the setscrew one full turn counterclockwise to secure the cover to the mounting plate.
9 Wire the sensor to the Open controller. See the controller's Installation and Startup Guide for details.

SPT sensors
8 Carrier Sensors
Using an SPT sensor
All SPT sensors
Feature
Usage
Local Access port
See To communicate through the Local Access port (page 10).
SPT Plus
Feature
Usage
Slide potentiometer
Move the potentiometer to raise or lower the zone's setpoint. The maximum you
can adjust the setpoint is defined in the
Max Adjust
field*.
MANUAL ON button
Press this button one time to override the schedule and set the zone to occupied
for the amount of time defined in the
Each pulse
field*. Press the button again
to incrementally increase the time. For example, if the
Each pulse
field is set at
five minutes, press the button once for an occupancy of five minutes, twice for
ten minutes, and so on. The maximum length of time you can override the
schedule is defined in the
Max Accum
field*.
To cancel the override, hold down the
MANUAL ON
button until the
OCCUPIED
LED turns off.
OCCUPIED LED
The LED lights when the zone is occupied from a regular schedule or a manual
override.
*See To change sensor properties (page 9).
SPT Pro
Feature
Usage
Display
The display shows occupancy, zone temperature, and an alarm bell icon. Celsius
values are to the nearest 0.5 degree; Fahrenheit values are to the nearest full
degree.
The display shows
Occupied
when the zone is occupied from a regular schedule
or from a manual override.
MANUAL ON button
Press one time to override the schedule and set the zone to occupied for the
amount of time defined in the
Each pulse
field*. Press button again to
incrementally increase the time. For example, if the
Each pulse
field is set at five
minutes, press the button once for an occupancy of five minutes, twice for ten
minutes, and so on. The maximum length of time you can override the schedule
is defined in the
Max Accum
field*.
The display shows the duration of the override in minutes. If the override time
exceeds 199 minutes, the display shows the time in hours.
To cancel the override, hold the button down until
0
displays. Wait five seconds
for the display to show the current zone temperature again.

SPT sensors
Carrier Sensors 9
Feature
Usage
WARMER and COOLER
buttons
To raise or lower the zone's setpoint:
1 Press either button to display the current average setpoint (the average
between the heating and cooling setpoints).
2 Press either button again to raise or lower the setpoint. You can adjust the
setpoint by no more than the amount defined in the
Max Adjust
field*.
NOTE
Pressing either button overrides an unoccupied schedule and sets the
zone to occupied for the amount of time defined in the
Each pulse
field*.
INFO button
Press to cycle through the:
•zone temperature
•outside air temperature, if enabled in the control program
•override time, in minutes
•heating setpoint
•cooling setpoint
*See To change sensor properties (page 9).
SPT Pro Plus
The SPT Pro Plus has all the features of the SPT Pro plus the additional functionality described below.
Feature
Usage
MANUAL ON button
The
Timed Local Override
section of the microblock dialog box determines if
pressing the
MANUAL ON
button sets the zone to occupied for a set amount of
time in the same manner as the RS Pro or sets the zone to continuously
occupied.
INFO button
This button cycles through the same information as the RS Pro and up to 4
additional inputs defined in the
Optional Inputs
section of the microblock dialog
box in EIKON LogicBuilder.
MODE button
The
MODE
button lets you cycle through up to 4 operational modes defined with
custom programming. The sensor displays information for each mode based on
the setup in the
Mode
section of the microblock dialog box.
FAN button
Press
FAN
to select the controlled equipment's fan speed. A fan icon on the left
side of the display indicates when the fan is on.
To change sensor properties
You can use the following items, if included with your system, to change sensor properties such as the
override time or maximum setpoint adjustment:
•i-Vu Open
•Field Assistant
•BACview or Virtual BACview
Field Assistant and Virtual BACview run on a laptop that you connect to an SPT sensor's Local Access port.

SPT sensors
10 Carrier Sensors
To communicate through the sensor's Local Access port
You can connect laptop to an SPT sensor's Local Access port to make changes to any device on the network.
PREREQUISITES
•A computer with a USB port
•USB Link (USB-L)
1 Connect the USB-L to the computer and to the sensor's Local Access port.
Connect to
USB port
Connect to 5-pin
Local Access port
12 ft.73/4 in.
Part #USB-L
2 Launch your software (i-Vu Open, HyperTerminal, Field Assistant, Virtual BACview, Test and Balance).
3 Configure the port.
4 Verify that the baud rate is set to 115,200.
Troubleshooting SPT sensors
Use the following tables to troubleshoot an SPT sensor.
SPT Standard or SPT Plus
If LED on back of circuit board...
Then sensor...
Is not lit Has no power
Blinks 1 time per second Has power, but is not communicating
Blinks 2.5 times per second Is correctly wired and communicating
SPT Pro or SPT Pro Plus
If display shows...
Then sensor...
Nothing Has no power
All display elements Has power, but is not communicating
Only the temperature and current status Is correctly wired and communicating

Alternate space temperature sensor
Carrier Sensors 11
Part #33ZCT55SPT, 33ZCT56SPT, 33ZCT59SPT
The following wall-mounted space temperature sensors can be used instead of an SPT sensor to monitor zone
temperature.
Sensor
Features
T-55
Part #33ZCT55SPT
•Timed override button
T-56
Part #33ZCT56SPT
•Timed override button
•Setpoint adjustment
T-59
Part #33ZCT59SPT
•Timed override button
•Setpoint adjustment
•LCD display
NOTE The T-59 sensor requires a dedicated 24 Vac, 3 Va transformer to power the sensor.
Alternate space temperature sensor

Alternate space temperature sensor
12 Carrier Sensors
Sensor specifications
Operating range T55 and T56: 32° to 120°F (0° to 49°C) with a nominal resistance of
10,000 ohms at 77°F (25°C). See table below.
T59: 40° to 104°F (5° to 40°C) with a nominal resistance of 10,000 ohms
at 77°F (25°C). See table below.
Sensor tolerance T55 and T56: ±0.2°C from 0 to 70°C
T59: ±1°F from 40 to 104°C (±1°C from 4 to 40°C)
Humidity 0 to 95%, non-condensing
Power 24 Vac, 3 Va
Dimensions: Width:
Height:
Depth:
2 3/4 in. (6.98 cm)
4 1/2 in. (11.46 cm)
1 1/5 in. (2.92 cm)
Thermistor Resistance vs. Temperature Values for Space Temperature
Sensor
10K Type II (CP/MCI)
Temp (F)
Temp (C)
Resistance (Ohms)
-40
-31
-22
-13
-4
5
14
23
32
41
50
59
68
77
86
95
104
113
122
131
140
149
158
-40
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
335,651
242,195
176,683
130,243
96,974
72,895
55,298
42,315
32,651
25,395
19.903
15,714
12,494
10,000
8,056
6,530
5,325
4,367
3,601
2,985
2,487
2,082
1,752
Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
If >100 ft (30.5 meters) 22 AWG, shielded
Maximum length: 500 feet (152 meters)

Alternate space temperature sensor
Carrier Sensors 13
Mounting location
Mount the sensor:
•In an area representing the average temperature in the space
•On an interior wall
•Approximately 5 feet (1.5 meters) from the floor, or as required by local code
•At least 4 feet (1.2 meters) from any corner
•At least 2 feet (.6 meter) from an open doorway
Do not mount the sensor:
•In drafty locations such as near air conditioning or heating ducts, or near open windows
•Over heat sources such as baseboard heaters, radiators, directly above wall-mounted lighting dimmers,
or in direct sunlight
NOTE The sensor mounting plate accommodates the NEMA standard 4x2-in. electrical box. However, the
sensor can be mounted directly on the wall surface if local codes permit.
To wire and mount the sensor
1 Turn the 2 setscrews at the bottom of the sensor clockwise to release the sensor's cover from the
mounting plate.
2 Lift the cover from the bottom, and then release it from the top fasteners.
3 Feed the wires from the electrical box through the opening in the center of the sensor mounting plate.
4 Use the 2 mounting screws provided to attach the mounting plate to the electrical box.
5 Strip the outer jacket from the cable for at least 3 inches (7.62 cm). Strip .25 inch (.6 cm) of insulation
from each wire. Cut the shield and drain wire from the cable.
6 Use the appropriate diagram below to connect the wiring to the sensor's terminals.
7 Reattach the sensor's cover to the mounting plate, inserting the top first.
8 Turn the two Allen screws counterclockwise to secure the cover to the mounting plate.
9 Wire the sensor to the Open controller. See the controller's Installation and Startup Guide for details.
NOTE Clean sensor with damp cloth only. Do not use solvents.

Alternate space temperature sensor
14 Carrier Sensors
T-55 sensor T-56 sensor T-59 sensor
Red
Blk (Gnd)
White
Jumper
terminals
SEN SET
SEN
Blk (Gnd) Sensor
wiring
Red Sensor
wiring
Blu
Blk
Brn Sensor
wiring
PWR
+
COM
-
OPB
To change a T59 sensor's options
You can change user options and field service options in the T59's display. The options are displayed on
pages referenced by page number. See tables below.
NOTE Because the T-59 is not a communicating device, the T-59's setpoint and offset values must be set to
match the same values in the associated controller.
To display an
option page
3 In the User Options and Field Service Options tables below, find the option you
want to change and its page number.
4 With the sensor displaying the current temperature, simultaneously press and
hold the and keys. After 30 seconds, the sensor's display shows option
page 100.
5 Release the keys.
6 Press repeatedly until the display shows the page number you want.
NOTE
To display a field service option page (126 to 132), press the key
until you see 1- -, then simultaneously press and hold and . After
approximately 2 seconds, the display shows 126. Press until you see the
page you want.
NOTE
If you do not press a key for 30 seconds, the sensor automatically returns to
normal operation.
To edit a value
7 When the option page you want is displayed, press to enter edit mode.
8 Press repeatedly to cycle through the numbers 00 to 12. Stop at the
number that represents the value you want. See tables below.
9 Press to save the selected value and return to option page.
NOTE
If you do not press a key for 10 seconds, the sensor automatically returns to
option page.
To return sensor to
normal operation
From an option page, press until the display shows 1- -. Then press .

Alternate space temperature sensor
Carrier Sensors 15
User Options
Option page
Description
100 Firmware version
101 Temperature scale
00 = °F
01 = °C
102 Temperature Offset (Sensor Trim) °F
00 = -5
01 = -4
02 = -3
03 = -2
04 = -1
05 = 0 (typical)
06 = 1
07 = 2
08 = 3
09 = 4
10 = 5
103 Normal Setpoint Display
00 to 09 = Do Not Use
Offset Setpoint Display
10 = -02 to 02°F (-02 to 02°C)
11 = -03 to 03°F (-03 to 03°C)
12 = -05 to 05°F (-05 to 05°C)
104 Keep at 00
105 Setpoint Lockout
00 = Disable Lockout
01 = Enable Lockout
106 Keep at 00
107 Keep at 00
108 Display Mode
00 = Normal
01 = Setpoint Only
109 Keep at 00
Field Service Options
Page
Description
126 Setpoint mode
00 = Use option page 103 setting
01 = Display single offset setpoint
02 = Display Heat/Cool setpoints
03 = Display Heat/Cool setpoints w/Occupied
(Occupied icon is shown in setpoint display mode.)
127 Setpoint feedback
00 = Disable feedback
01 = Enable Occupied/unoccupied feedback
02 = Enable Heat/Cool feedback

Alternate space temperature sensor
16 Carrier Sensors
Page
Description
128 Maximum offset adjustment for setpoint
* Note: When using the -00° to +00° selection, option page 105 must be set to value 01.
* 00 = -00° to +00° (F or C)
01 = -01° to +01° (F or C)
02 = -02° to +02° (F or C) (Default)
03 = -03° to +03° (F or C)
04 = -04° to +04° (F or C)
05 = -05° to +05° (F or C)
06 = -06° to +06° (F or C)
07 = -07° to +07° (F or C)
08 = -08° to +08° (F or C)
09 = -09° to +09° (F or C)
10 = -10° to +10° (F or C)
129 Occupied heat setpoint
60 = Default (Range is 10 to 89)
130 Occupied cool setpoint
65 = Default (Range is 10 to 89)
131 Unoccupied heat setpoint
55 = Default (Range is 00 to 99)
132 Unoccupied cool setpoint
90 = Default (Range is 00 to 99)
This manual suits for next models
19
Table of contents
Other Carrier Security Sensor manuals

Carrier
Carrier BN Series User manual

Carrier
Carrier 7C-SE-C1X-DT User manual

Carrier
Carrier ARITECH VE1012PI Assembly instructions

Carrier
Carrier Aritech 6933AMP Assembly instructions

Carrier
Carrier HyperSense 7C-HS-C1W-X User manual

Carrier
Carrier 7C-SE-C68 Series User manual

Carrier
Carrier KIDDE 60WLDR-W User manual

Carrier
Carrier Graviner Mk6 Configuration guide

Carrier
Carrier Graviner Mk7 User manual

Carrier
Carrier DET-TRONICS Dual Spectrum PM-5MPX User manual