N° LEDs
behaviour Error Actuator
use
Actuator behaviour Typical
trouble
shooting
condition
Reset
procedure
Automatic calibration
(DIP N. 7 OFF)
Manual calibration
(DIP N. 7 ON)
1RED ON
Valve stroke
less than
5mm
Calibration/
rst
installation
The actuator pushes/pulls
2 times (unexpected stall)
trying to remove the possible
obstacle. After 2 tries an alarm
is signalled and the actuator
moves to initial position and
does not respond to control
signal. Stroke value is not
updated because out of range
The actuator pushes/pulls 2
times against endpoint during
calibration and the actuator
moves to the initial position and
then it does not respond to the
control signal. The actuator
keeps the previous stroke
Valve with a
stroke length
lower than
5mm
Remove
power and
power up
again
2
RED LED
quick
blinking +
GREEN ON
Stroke
longer than
60mm
Calibration/
rst
installation
The actuator exits the 60mm
stroke range and it moves
toward the new stroke limit
signalling an anomaly. The
actuator pushes/pulls 2 times
against the new stroke limit,
then it goes back to the initial
position still signalling the
anomaly until it is not within
60mm. The actuator does not
calibrate the stroke after 10s
(wrong range)
The actuator exits the 60mm
stroke range and it moves
toward the new stroke limit
signalling an anomaly. The
actuator pushes/pulls 2 times
against the new stroke limit,
then it goes back to the initial
position still signalling the
anomaly until it is not within
60mm. The actuator does not
calibrate the stroke after 10s
(wrong range)
Valve with a
stroke length
longer than
60mm
Remove
power and
power up
again
3RED Quick
Blinking
Unexpected
stall
within the
calibrated
stroke range
normal
operation
The actuator tries 5 times
against the new stall condition
and then after 10s the actuator
updates the new stroke length
The actuator tries 5 times
against the new stall condition.
At the end of the attempts
the fault will be signalled. The
actuator does not update the
new stroke length, but after 60s
makes other attempts to verify
the stall condition
Valve stuck Inverted
control signal
4RED Quick
Blinking
Stroke
longer than
expected
Normal
operation
The actuator moves toward the
new stall condition with a lower
speed; after 10s the actuator
updates the new stroke value
The actuator moves toward the
new stall condition with a lower
speed; after 10s the actuator
does not update the new
stroke value
Stem
connection
loose or
valve
damaged
Inverted
control signal
5RED slow
Blinking
Low Power
Voltage
Normal
operation
The actuator is still working
but performance cannot be
guaranteed
The actuator is still working
but performance cannot be
guaranteed
1. Wrong
transformer
size Correct
Voltage
Power
2. Unstable
power
LED STANDARD / STANDARD LEDs
Scheda di controllo Electronic control board
N° Comportamento
LED Stato servocomando
1 VERDE FISSO Il servocomando è arrivato
all’estremo della corsa appresa
2VERDE
LAMPEGGIANTE
Il servocomando è arrivato o si sta
muovendo verso un punto intermedio
della corsa appresa
3
ROSSO VERDE
LAMPEGGIANTE
ALTERNATO
Il servocomando sta apprendendo
la corsa o sta effettuando il
posizionamento iniziale
4 ROSSO VERDE FISSO
Comando manuale inserito, il
servocomando ignora il segnale di
comando.
ATTENZIONE! La scheda è alimentata
5
ROSSO VERDE
LAMPEGGIANTE
SIMULTANEO
Il servocomando è in fase di ritorno in
emergenza
N° LEDs behaviour Actuator status
1 GREEN ON The actuator arrived at the extreme
point of the stroke
2 GREEN BLINKING The actuator is moving or arrived at
the intermediate point of the stroke
3
RED GREEN
BLINKING
ALTERNATING
Calibration or initialization phase
4 RED GREEN ON
Manual control enabled, the
actuators ignores the control signal.
ATTENTION! The electronic board is
electrically supplied
5
RED GREEN
BLINKING
SIMULTANEOUS
The actuator is in emergency return
phase
1° Emissione / 1st Issue 05/17 7 DIM263