11
Note 3.
You have a choice of 5 temperature sensors.
1.) Indoor Sens – Temperature sensor located in the
indoor unit.
2.) Master RC - Master controller sensor
3.) Sub RC - When using option BRCSZC Sub controller.
4.) Sens 1 - When using option KRCSO1-1
5.) Sens 2 - When using option KRCSO1-1
Only the indoor sensor will be activated
(factory set) all other sensors must be activated by
the field set codes, once activated sensor selection
can be achieved by pressing the SEL SENSOR
button on the remote controller.
Temperature sensor activation
Zone restriction
Note 4.
Example: You may only require the use of 4 zones out
of the 8 available zones. By applying the Field setting
1b - 3 - 0_ you can restrict the number of zones you
want to operate, for example 4 zones. The remaining
unused zones will not function when the zone buttons
are pressed. ( 1b - 3 - 04 )
Before setting zone restriction make sure all zones are
switched off.
001Sensor 1 OFF
101Sensor 2 OFF
002Sensor 1 ON
(Remote sensor KRCSO1-1 required)
102Sensor 2 ON
(Remote sensor KRCSO1-1 required)
301Zone 1 only
302Zones 1-2
303Zones 1-3
304Zones 1-4
305Zones 1-5
306Zones 1-6
307Zones 1-7
308Zones 1-8
401Keep 1 Zone ON
402All Zones OFF
501Master RC OFF
502Master RC ON
601Sub RC OFF
602Sub RC ON
(Sub controller BRCZSC required)
601Standard static pressure
(FDYQ(N)71-160 only)
602High static pressure
(FDYQ(N)71-160 only)
301Filter sign indication ON
302Filter sign indication OFF
Set item
1b
Field Settings
Mode Switch Position
23
20
001Sensor 1 OFF
101Sensor 2 OFF
3088 Zones available
402All zones OFF
501Master RC OFF
601Sub RC OFF
201Fan operation heating (Thermo off.)
701Fan operation cooling (Thermo off.)
23 601Standard static pressure
(FDYQ(N)71-160 only)
20 301Filter sign indication ON
1b
Default Settings Set item
Note 3.
Pg11
Note 4.
Pg11
Note 6.
Pg12
Note 3.
Pg11
Note 5.
Pg11
Fan static Pressure
Note 5.
When a higher airflow is required for example when the
pressure inside the ducting is high, use field setting
23-6-02 to increase the airflow.
For models with a capacity index of 180-250 please
refer to the installation instructions supplied with the air
conditioner.
Auto fan function with air sampling mode
Auto fan function will activate once the set point
temperature is achieved (thermo off) and will
deactivate when the room temperature is outside the
set point range (thermo on).
During Auto fan function the indoor fan will stop for a
period of 6 minutes and then start for a period of 30
seconds or more (depending on model) in order to
sample the room temperature.
Auto fan function will only activate when the “Indoor
Sens” (Indoor unit air temperature sensor) is selected.
Auto fan function will operate the same as Std. fan
function when other sensors are selected.
Fan operation during thermo. Off
Mode Switch Position
01 LL OFF (Air sampling LL)LLOFF (Air sampling LL)
02 Set speed OFF (Air sampling Set speed)Set speed OFF (Air sampling Set speed)
03 OFFOFF (Air sampling OFF) OFFOFF (Air sampling OFF)
1LL OFF (Air sampling LL)Set speed
2Set speed OFF (Air sampling Set speed)Set speed
3OFFOFF (Air Sampling OFF)Set speed
Set speed
Set speed
Set speed