
Easy-Start ES Instruction Manual
Pre-Installation
INSTALLATION
2-9
Application Considerations
NEMA Design C and D Motors, Wound
Rotor Motors
These motors are used due to their high starting
torque characteristics. When high starting
currents and high starting torques are required,
the extended time current option must be
supplied and the unit must be oversized (see
Section 4).
Reversing Starters
If all the limitations are understood and accepted
the Easy-Start ES can be used on line side of an
electro mechanical reversing starter. The
operation should be to start the motor in forward
or reverse after a complete stop. Plug reversing
i.e. going from forward to reverse directly will
damage the starter. It is recommended that
enough time delay be built into the reversing
starter circuit (by others) to prevent restarting
until the motor has come to complete stop.
Wye Delta (Six Lead) Motors
These should be connected in Delta and can
then be started with Easy-Start ES.
Part Winding Motors
Part winding motors are started by applying full
voltage to part of the winding and after a time
delay full voltage is applied to the remaining
winding.
For part winding motors the Easy-Start ES can
be used by connecting the two windings in
parallel.
2-Speed 2-Winding Motor
If all the limitations are understood and accepted
Easy-Start ES may be used on the line side of a
electromechanical 2-speed 2-winding motor but
will provide soft start only if the motor is started in
either speed from complete stop. The ramp (soft
start) can be optimized for one speed only.
Going directly from low speed to high speed or
high speed to low speed would not give smooth
transition and may cause a current surge. It is
recommended that enough time delay be built
into the 2-speed 2-winding starter circuit (by
others) to prevent changing speeds without
coming to full stop.
Another way is to connect Easy-Start ES
between low speed contactor of
electromechanical 2-speed starter and low speed
winding of the motor. This will provide a soft start
on low speed only.
2-Speed Single Winding Motors
The Easy-Start ES is not recommended for use
with 2-speed single winding motors.
Capacitors
Notice - Power factor correction capacitors
should not be connected between load side of
Easy-Start ES and the motor. This will cause
damage to the starter.
When the Easy-Start ES is operating at reduced
voltage on the motor, there may be small
amounts of harmonic current drawn from the AC
power line. There may be a resonant circuit
caused by capacitors across the line. The
capacitors may therefore have a higher
temperature rise than normal. This situation can
be minimized by the following:
- If a contactor is used to switch the capacitors,
it should have a time delay built in the circuit
so that the contactor closes after the Easy-
Start ES has ramped up to full voltage.
- The capacitors should be mounted as far
upstream from the solid state starter as
possible. If capacitors must be used they
must be connected on the line side of the
Easy-Start ES with at least 10 feet of cable
between starter and the capacitors.